| 2007-12-24 13:36:25 | ** DENIEDREVIEW ** |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME DUE TO INCOMPLETE PLANS. |
| | |
| | ** THE FOLLOWING COMMENTS ARE BASED ON PLANS SUBMITTED |
| | ONLY. |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING ADOPTED CODES BY THE STATE. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING CODE |
| | COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE. |
| | FBC 106.3.5.4 ADMIN SECTION, CHAPTER 27 AND CHAPTER 9 |
| | EXISTING BUILDING CODE, ETC. |
| | AS PACKAGE SHOWS THIS ADDITION ALREADY STARTED AND |
| | MENTIONS THERE WILL BE A NEW LAUNDRY ROOM. |
| | PLEASE SUBMIT LOAD CALCULATIONS FOR NEW LOAD ON THE |
| | EXISTING SERVICE. |
| | PLEASE SUBMIT THE ELECTRICAL RISER SHOWING THE SIZE OF |
| | THE SERVICE. |
| | PLEASE SUBMIT A PANEL SCHEDULE FOR NEW CIRCUITS.408.4, |
| | |
| | PLEASE SHOW NEW BRANCH CIRCUITS, BREAKERS AND |
| | CONDUCTORS BEING ADDED. 220, 210, ETC |
| | PLEASE SEE MISSING EGRESS LIGHTING. 210.70 |
| | PLEASE SEE MISSING EXISTING OR NEW TO BE INSTALLED |
| | SMOKE ALARMS IN EXISTING DWELLING PER FBC R313 AND |
| | NFPA-72 11.5.1.1.1, 11.8.3 |
| | |
| | ** PLEASE SEE 2005 NECAND NFPA-72 2002. |
| | |
| | PLEASE KNOW AS NO ELECTRICAL PLANS WERE SUBMITTED THERE |
| | MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT ETC |
| | EVEN IF ANY ARE OWNER SUPPLIED. THIS VALUE IS BASED ON |
| | THE FBC TABLES AND ADOPTED STANDARDS SUCH AS MARSHALLS |
| | AND SWIFT. |
| | FBC 108.3 |
| | |
| | 4) NOTE: PLEASE SEE THAT ELECTRICAL PLANS TO BE |
| | SUBMITTED CONTAIN THE DESIGN PROFESSIONAL AS REQUIRED |
| | UNDER EITHER FLORIDA STATUTES 471, 481OR 489. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |