Plan Review Notes
Plan Review Notes For Permit 07120554
Permit Number 07120554
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-14 14:35:18RESIDENTIAL ADDITION, BUILDING REVIEW FIRST CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-PLOT PLAN SHOWN ON PLANS SUBMITTED DOESN'TMATCH
 SURVEY SUBMITTED. REVISE EITHER ONE AS REQUIRED TO
 MATCH.
  
 2-AFTER ALL PLANS ARE REVISED, BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD (561)233-5120)TO VERIFY
 IF IMPACT FEES ARE DUE. BRING BACK STAMPEDPLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.IT WAS UPDATED TO $8305.THEREFORE OWES $232.86
 AS REQUIRED BYSEC. 108.3 CITY AMENDMENTS TO FBC
 2004.VALUE NEED TO INCLUDE ALLBUILDING MATERIALS,
 LABOR,DESIGN FEES AND LAND PREPARATION.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE PROVIDED AT TIME OF PRINTING THE
 PERMIT.
  
 5-DRAWINGS NEED TO SPECIFYALL DESIGN CRITERIA.
 SPECIFYBUILDING CODE USED AND SPECIFY ALLROOF AND
 FLOOR DEAD LOADS, LIVE LOADS AND WIND LOADS AS REQUIRED
 BY SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- SPECIFY THE BUILDING EXPOSURE CATEGORY AS REQUIRED
 BY SEC. R301.2.1.4 OF 2004 FLORIDA RESIDENTIALCODE.
  
 7- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS AS REQUIRED BY SEC. R301.1
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 8- SPECIFYTHE BASIC WIND SPEED AS REQUIRED BY SEC.
 R301.2.1.5OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9- SPECIFY ROOF UPLIFT CALCULATIONS AS REQUIRED BY SEC.
 R301.1 OF 2004 FLORIDA RESIDENTIAL CODE AND SPECIFY ALL
 CONNECTORS THAT WILL RESISTTHE CALCULATED UPLIFT AND
 LATERAL LOADS. SEC. 106.1.2 CITY AMENDMENTSTO FBC
 2004 TO VERIFY COMPLIANCE WITH SEC. R301.1. OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 10- PROVIDE COMPLETEENGINEERING CALCULATIONS FOR TYPE
 OF FOOTING SHOWN ON PLANS.SPECIFY SIZE,
 REINFORCEMENT, EXACT LOCATION AND HOW ARE THEY DESIGNED
 TO RESIST ALL THE LOADS.SEC. 106.1CITY AMENDMENTS
 TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. R301.1 AND
 SEC. R401.2OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: ENGINERING REQUIRED BECAUSECONSTRUCTION
 DRAWINGS PROVIDEDDON'T FOLLOW ANYDESIGN
 PRESCRIPTIVE STANDARD ADOPTED BY THE CODEAND PROPOSED
 DESIGNIS NOT THE STANDARD CONSTRUCTION METHOD
 EITHER.
  
 11- PERSON RESPONSIBLE FOR THE DESIGN TO SPECIFY THE
 DESIGNCRITERIA FOR THE SOIL BEARING CAPACITY AS
 REQUIRED BYSEC. R401.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 12- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 13- PROVIDE COMPLETE ENGINEERING ANALYSISSHOWINGHOW
 ONLY ONE BEAM ASSHOWN ON FLOOR FRAMING PLANIS
 ADEQUATE TO RESIST THE DESIGN LOADS CALCULATEDBY SEC.
 R301.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 SEC. 106.1 CITY AMENDMENTS TO FBC 2004.
  
 14-DRAWINGSAND CALCULATIONS REQUIRED ON ITEM #10
 ABOVETOBE SIGNED AND SEALED AS REQUIRED BY CHAPTER
 471 AND CHAPTER 481 FLORIDA STATUTES AND PROFESSIONAL
 OF RECORD TO PROVIDE ALLTHEINFORMATION REQUIRED BY
 FLORIDA ADMINISTRATIVE CODE.
  
 15-PROVIDE COMPLETE WALL SECTION SHOWING HOW ALL THE
 LOADS ARE TRANSFERRED FROM THE ROOF TO THE FOOTING.
 SEC. 106.1.2 CITYAMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 16- ASPHALT SHINGLES CAN'T BE INSTALLED IN LOW PITCH
 ROOFS. SEE SEC. R905.2.2 OF 2004 FLORIDA RESIDENTIAL
 CODE. REVISE AS REQUIRED.
  
 17- SPECIFY ROOF PITCH AS REQUIRED BY SEC. 106.1.2 CITY
 AMENDMENTS TO VERIFY COMPLIANCE WITH SEC. R905.9 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 18- SPECIFY ROOF SHEATHING NAILING. SEE SEC. R803.2.3.1
 OF 2004 FLORIDA RESIDENTIAL CODE TO CHECK FOR MINIMUM
 TYPE AND NAIL TO BE USED ACCORDING TO THE ROOF ZONES.
  
 19- SPECIFYWALL SHEATHINGAS REQUIRED BY SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R601.2OF 2004 FLORIDA
 RESIDENTIALCODE.
  
 20- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.1 OF FBC 2004.PLEASE MAKE SURE CORRECT
 REVISED FORM IS USED TO AVOID UNNECESSARY DELAYS.
  
 21- SPECIFY INSULATION ON WALLS AND CEILINGS AND ON
 RAISED WOOD FLOOR. COORDINATE INFORMATION WITH ENERGY
 CALCULATIONS.SEC. 13-101.1.3FBC 2004.
  
 22- PROVIDE PRODUCT APPROVAL(TWO COPIES)AS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) EXTERIOR DOOR, INSWING TYPE AS SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOWS.
  
 C) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING.
 ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
  
 D) FLAT ROOF SYSTEM. AND CLEARLY IDENTIFY SPECIFY
 ASSEMBLY TO BE USED, SPECIFIC FASTENING OPTIONFOR THE
 BASE SHEET AND PROVIDE ENHANCED FASTENING FOR PERIMETER
 AND CORNER AREAS.
  
 E)ALL SIMPSON OR USP CONNECTORS SPECIFIEDIN
 PLANS AND DETAILS BY THE DESIGNER OF RECORD.
  
 23- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 24- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 COMPLIANCE WITH THE CRAWL SPACE UNDER THE RAISED FLOOR
 AS REQUIRED BY SEC. R408 OF 2004 FLORIDARESIDENTIAL
 CODE. SPECIFY VENTILATION AND ACCESS.
  
 25- PROVIDE COMPLETE FRAMING DETAILS FOR EXTERIOR DOORS
 AND WINDOWS. SECTION 106.1.2 CITY AMENDMENTSTO FBC
 2004 TO VERIFY COMPLIANCE WITH THE DESIGN LOADS
 CALCULATED PER R301.1 AND TO VERIFY COMPLIANCE WITH THE
 LOAD PATH REQUIRED BY SEC. R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 26- PROVIDE STEPSON THE OUTSIDE SIDE OF EXTERIOR DOOR
 TO COMPLY WITH SEC. R311.5.3 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 27- PROVIDE COMPLETE WOOD SPECIFICATIONS AND DETAILS TO
 SHOW COMPLIANCE WITH SEC. R319 OF 2004 FLORIDA
 RESIDENTIAL CODE REGARDING PROTECTION OF WOOD AGAINST
 DECAY.
  
 28- RAFTER DETAIL X:PROVIDE SPECIFICATIONS FORROOF
 "CROSS" VENTILATION TO COMPLY WITH SEC. R806 OF 2004
 FLORIDA RESIDENTIAL CODE.
 NOTE:TAKE INTO CONSIDERATION THAT THIS IS A FLAT ROOF
 AND NEED TO PROVIDE CONTINUOUS CROSS VENTILATION.
 ALSO, PROVIDE COMPLETE SPECIFICATIONS FOR SOFFIT
 CONSTRUCTION.
  
 29- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR
 ATTACHMENT OF NEW ROOF RAFTERS TO EXISTING ROOF FRAMING
 TO VERIFY COMPLIANCE WITH THE DESIGN LOADS CALCULATED
 TOCOMPLY WITH SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 30- ACCORDING TO PICTURES SUBMITTED:
 A)THERE IS AN OPENINGON BOTH SIDES OF THE
 ADDITION AT THE TRANSITION FROM ROOF TO WALL FRAMING.
 PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING HOW ARE
 THE LOADS CONTINUOUSLY TRANSFERRED FROM ROOF TO WALL
 AND FOOTING AS REQUIRED BY SEC.R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) WOOD STUDS USED ARE 2X4, WHILE DRAWINGS CALL FOR
 2X6 STUDS. REVISE/CLARIFY AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712