| Date |
Text |
| 2008-01-14 14:35:18 | RESIDENTIAL ADDITION, BUILDING REVIEW FIRST CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-PLOT PLAN SHOWN ON PLANS SUBMITTED DOESN'TMATCH |
| | SURVEY SUBMITTED. REVISE EITHER ONE AS REQUIRED TO |
| | MATCH. |
| | |
| | 2-AFTER ALL PLANS ARE REVISED, BRING THEM TO PALM |
| | BEACH COUNTY (2300 N. JOG RD (561)233-5120)TO VERIFY |
| | IF IMPACT FEES ARE DUE. BRING BACK STAMPEDPLANS AND |
| | COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW.IT WAS UPDATED TO $8305.THEREFORE OWES $232.86 |
| | AS REQUIRED BYSEC. 108.3 CITY AMENDMENTS TO FBC |
| | 2004.VALUE NEED TO INCLUDE ALLBUILDING MATERIALS, |
| | LABOR,DESIGN FEES AND LAND PREPARATION. |
| | |
| | 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE PROVIDED AT TIME OF PRINTING THE |
| | PERMIT. |
| | |
| | 5-DRAWINGS NEED TO SPECIFYALL DESIGN CRITERIA. |
| | SPECIFYBUILDING CODE USED AND SPECIFY ALLROOF AND |
| | FLOOR DEAD LOADS, LIVE LOADS AND WIND LOADS AS REQUIRED |
| | BY SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- SPECIFY THE BUILDING EXPOSURE CATEGORY AS REQUIRED |
| | BY SEC. R301.2.1.4 OF 2004 FLORIDA RESIDENTIALCODE. |
| | |
| | 7- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE |
| | EXTERIOR DOORS AND WINDOWS AS REQUIRED BY SEC. R301.1 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 8- SPECIFYTHE BASIC WIND SPEED AS REQUIRED BY SEC. |
| | R301.2.1.5OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- SPECIFY ROOF UPLIFT CALCULATIONS AS REQUIRED BY SEC. |
| | R301.1 OF 2004 FLORIDA RESIDENTIAL CODE AND SPECIFY ALL |
| | CONNECTORS THAT WILL RESISTTHE CALCULATED UPLIFT AND |
| | LATERAL LOADS. SEC. 106.1.2 CITY AMENDMENTSTO FBC |
| | 2004 TO VERIFY COMPLIANCE WITH SEC. R301.1. OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- PROVIDE COMPLETEENGINEERING CALCULATIONS FOR TYPE |
| | OF FOOTING SHOWN ON PLANS.SPECIFY SIZE, |
| | REINFORCEMENT, EXACT LOCATION AND HOW ARE THEY DESIGNED |
| | TO RESIST ALL THE LOADS.SEC. 106.1CITY AMENDMENTS |
| | TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. R301.1 AND |
| | SEC. R401.2OF 2004 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: ENGINERING REQUIRED BECAUSECONSTRUCTION |
| | DRAWINGS PROVIDEDDON'T FOLLOW ANYDESIGN |
| | PRESCRIPTIVE STANDARD ADOPTED BY THE CODEAND PROPOSED |
| | DESIGNIS NOT THE STANDARD CONSTRUCTION METHOD |
| | EITHER. |
| | |
| | 11- PERSON RESPONSIBLE FOR THE DESIGN TO SPECIFY THE |
| | DESIGNCRITERIA FOR THE SOIL BEARING CAPACITY AS |
| | REQUIRED BYSEC. R401.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 12- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 13- PROVIDE COMPLETE ENGINEERING ANALYSISSHOWINGHOW |
| | ONLY ONE BEAM ASSHOWN ON FLOOR FRAMING PLANIS |
| | ADEQUATE TO RESIST THE DESIGN LOADS CALCULATEDBY SEC. |
| | R301.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | SEC. 106.1 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14-DRAWINGSAND CALCULATIONS REQUIRED ON ITEM #10 |
| | ABOVETOBE SIGNED AND SEALED AS REQUIRED BY CHAPTER |
| | 471 AND CHAPTER 481 FLORIDA STATUTES AND PROFESSIONAL |
| | OF RECORD TO PROVIDE ALLTHEINFORMATION REQUIRED BY |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 15-PROVIDE COMPLETE WALL SECTION SHOWING HOW ALL THE |
| | LOADS ARE TRANSFERRED FROM THE ROOF TO THE FOOTING. |
| | SEC. 106.1.2 CITYAMENDMENTS TO FBC 2004 TO VERIFY |
| | COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 16- ASPHALT SHINGLES CAN'T BE INSTALLED IN LOW PITCH |
| | ROOFS. SEE SEC. R905.2.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. REVISE AS REQUIRED. |
| | |
| | 17- SPECIFY ROOF PITCH AS REQUIRED BY SEC. 106.1.2 CITY |
| | AMENDMENTS TO VERIFY COMPLIANCE WITH SEC. R905.9 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 18- SPECIFY ROOF SHEATHING NAILING. SEE SEC. R803.2.3.1 |
| | OF 2004 FLORIDA RESIDENTIAL CODE TO CHECK FOR MINIMUM |
| | TYPE AND NAIL TO BE USED ACCORDING TO THE ROOF ZONES. |
| | |
| | 19- SPECIFYWALL SHEATHINGAS REQUIRED BY SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY |
| | COMPLIANCE WITH SEC. R601.2OF 2004 FLORIDA |
| | RESIDENTIALCODE. |
| | |
| | 20- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.1.C.1 OF FBC 2004.PLEASE MAKE SURE CORRECT |
| | REVISED FORM IS USED TO AVOID UNNECESSARY DELAYS. |
| | |
| | 21- SPECIFY INSULATION ON WALLS AND CEILINGS AND ON |
| | RAISED WOOD FLOOR. COORDINATE INFORMATION WITH ENERGY |
| | CALCULATIONS.SEC. 13-101.1.3FBC 2004. |
| | |
| | 22- PROVIDE PRODUCT APPROVAL(TWO COPIES)AS REQUIRED |
| | BY DCA RULE 9B-72 FOR: |
| | A) EXTERIOR DOOR, INSWING TYPE AS SHOWN ON PLANS. |
| | |
| | B) SINGLE HUNG WINDOWS. |
| | |
| | C) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. |
| | ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. |
| | |
| | D) FLAT ROOF SYSTEM. AND CLEARLY IDENTIFY SPECIFY |
| | ASSEMBLY TO BE USED, SPECIFIC FASTENING OPTIONFOR THE |
| | BASE SHEET AND PROVIDE ENHANCED FASTENING FOR PERIMETER |
| | AND CORNER AREAS. |
| | |
| | E)ALL SIMPSON OR USP CONNECTORS SPECIFIEDIN |
| | PLANS AND DETAILS BY THE DESIGNER OF RECORD. |
| | |
| | 23- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 24- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | COMPLIANCE WITH THE CRAWL SPACE UNDER THE RAISED FLOOR |
| | AS REQUIRED BY SEC. R408 OF 2004 FLORIDARESIDENTIAL |
| | CODE. SPECIFY VENTILATION AND ACCESS. |
| | |
| | 25- PROVIDE COMPLETE FRAMING DETAILS FOR EXTERIOR DOORS |
| | AND WINDOWS. SECTION 106.1.2 CITY AMENDMENTSTO FBC |
| | 2004 TO VERIFY COMPLIANCE WITH THE DESIGN LOADS |
| | CALCULATED PER R301.1 AND TO VERIFY COMPLIANCE WITH THE |
| | LOAD PATH REQUIRED BY SEC. R601.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 26- PROVIDE STEPSON THE OUTSIDE SIDE OF EXTERIOR DOOR |
| | TO COMPLY WITH SEC. R311.5.3 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 27- PROVIDE COMPLETE WOOD SPECIFICATIONS AND DETAILS TO |
| | SHOW COMPLIANCE WITH SEC. R319 OF 2004 FLORIDA |
| | RESIDENTIAL CODE REGARDING PROTECTION OF WOOD AGAINST |
| | DECAY. |
| | |
| | 28- RAFTER DETAIL X:PROVIDE SPECIFICATIONS FORROOF |
| | "CROSS" VENTILATION TO COMPLY WITH SEC. R806 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | NOTE:TAKE INTO CONSIDERATION THAT THIS IS A FLAT ROOF |
| | AND NEED TO PROVIDE CONTINUOUS CROSS VENTILATION. |
| | ALSO, PROVIDE COMPLETE SPECIFICATIONS FOR SOFFIT |
| | CONSTRUCTION. |
| | |
| | 29- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR |
| | ATTACHMENT OF NEW ROOF RAFTERS TO EXISTING ROOF FRAMING |
| | TO VERIFY COMPLIANCE WITH THE DESIGN LOADS CALCULATED |
| | TOCOMPLY WITH SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 30- ACCORDING TO PICTURES SUBMITTED: |
| | A)THERE IS AN OPENINGON BOTH SIDES OF THE |
| | ADDITION AT THE TRANSITION FROM ROOF TO WALL FRAMING. |
| | PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING HOW ARE |
| | THE LOADS CONTINUOUSLY TRANSFERRED FROM ROOF TO WALL |
| | AND FOOTING AS REQUIRED BY SEC.R601.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) WOOD STUDS USED ARE 2X4, WHILE DRAWINGS CALL FOR |
| | 2X6 STUDS. REVISE/CLARIFY AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |