 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
  
 2} INDICATE THE LOCATION OF THE PANELTO BE
 CHANGED.106.3.1 FBC.
  
 3} 210.52(C)(2) ISLAND COUNTER SPACES AT LEAST ONE
 RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN
 ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE
 RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE
 RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND
 INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN
 210.52(C)(4), GFI PER 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 .
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718