| Plan Review Notes For Permit 07120540 |
| Permit Number |
07120540 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-28 15:16:38 | ***DENIED*** | | | | | | 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY | | | DESIGN PROFESSIONAL. | | | | | | 2) WORK SHALL COMPLY WITH NFPA 101, SEC. 7.2.1.6.2 | | | REGARDING ACCESS CONTROLLED EGRESS DOORS. | | | | | | 3) HOW WILL EXIT DOORS OPERATE REGARDING EGRESS DURING | | | A FIRE ALARM? | | | | | | 4) WHAT FAILSAFE MECHANISM IS PROVIDED SHOULD THERE BE | | | A LOSS OF POWER? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|