| Plan Review Notes For Permit 07120532 |
| Permit Number |
07120532 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-02-06 07:36:28 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1) THE DESIGN PRESSURES FOR THE CASEMENT WINDOWS | | | (CIRCLED ON PAGE 4 OF NOA 05-1129.09 ARE FOR 3/16" | | | ANNEALED GLASS) ARE + & - 40 PSF. THE PLANS SUBMITTED | | | SPECIFY + 35 & - 47.2AS THE REQUIRED DESIGN PRESSURES | | | FOR THESE WINDOWS. THE NEGATIVE PRESSURE OF THE | | | SPECIFIED PRODUCT IS NOT ADEQUATE. PLEASE CORRECT. SEE | | | FBC R301.2.1. | | | | | | 2) SUBMIT 2 COPIES OF THE SCOPE OF WORK DOCUMENT OR | | | LIST THE SCOPE OF WORK ON THE DRAWINGS. | | | | | | 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDING SECTION | | | 604.4.3 FOR SMOKE ALARMS. | | | | | | 4) THE DRAWINGS SPECIFY THE 2004 FBC WITH 2006 | | | REVISIONS. THE CORRECT CODE FOR THIS PROJECT IS THE | | | 2004 FBC WITH 2007 REVISIONS. PLEASE CORRECT. | | | | | | 5) ADDRESS COMMENTS OF OTHER TRADES. | | | | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|