| 2007-12-23 14:57:21 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE |
| | STATED ON PLANS FOR MINIMUM DESIGN. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | ** FBC 2004 W/2007 REVISIONS (NOTED BY OTHER TRADES) |
| | |
| | 2) NOTE: PLEASE SUBMIT A COMPLETE PLAN INCLUDING PANEL |
| | SCHEDULE, RISER, LOAD CALCULATIONS ETC FOR NEW SCOPE OF |
| | WORK. |
| | PLEASE INDICATE THE NEW DEDICATED CIRCUITS WHICH ARE |
| | REQUIRED PER 210.52, 210.11, 220. |
| | AS SCOPE OF WORK IS NOT SHOWN DETERMINATION OF MINIMUM |
| | ELECTRICAL CODE COMPLIANCE CAN BE DONE AT THIS TIME. |
| | 2005 NEC. |
| | PLEASE SEE 210.70, LS 101 7.8 FOR CONTROLS OF NEW |
| | LIGHTING WHICH IS STATED ON SCOPE. |
| | PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS. |
| | PLEASE B SURE TO LIST ALL OVER CURRENT PROTECTION |
| | DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC |
| | 408.4, 240.4, 310.16 ETC |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12 |
| | AWG. |
| | |
| | 4) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING |
| | DWELLING SLEEPING ROOMS PER FBC R313 AND NFPA-72 |
| | 11.5.1.1.1, 11.8.3 |
| | PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING |
| | DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE |
| | CURRENT VERSION OF NFPA-72 11.5.1.1.1 AND 11.8.3 OR NEW |
| | TO BE INSTALLED. |
| | |
| | 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C |
| | CONDENSING UNIT AND AH UNITPER 440.11. |
| | PLEASE ALSO SEE THE MISSING GFI PER 210.8, 210.63. |
| | |
| | 7) NOTE: PLEASE SHOW LAYOUT OF NEW PROPOSED KITCHEN |
| | CABINETS SHOWING KITCHEN COUNTER SPACE GFI RECEPTACLES |
| | NEW MEETING CODE OR EXISTING MEETING MINIMUM CODE PER |
| | 210.52B1, 210.52C1-5, 210.8A6. |
| | |
| | 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED |
| | LIGHTING PER FBC 13-606.ABC.1.2.4 |
| | |
| | 9) NOTE: PLAN TITLE BLOCKS MENTIONS DESIGNER FOR |
| | RESIDENTIAL AND COMMERCIAL WORK. PLEASE SEE FLORIDA |
| | STATUTES 481.229 AS SCOPE OF WORK ON COMMERCIAL |
| | PROJECTS REQUIRE LICENSE UNDER ARCHITECTURAL |
| | REGULATIONS. PLEASE COMPLETE TITLE BLOCKS WITH REQUIRED |
| | LICENSING PER FAC 61G1-16.004, FS 481.219. |
| | PLANS WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED |
| | BY ANY LICENSED DESIGNER OF RECORD. FS 481.221. |
| | |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |