| 2007-12-26 13:10:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT. |
| | |
| | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR |
| | GENERATOR. |
| | |
| | 3) PLEASE BE ADVISED.PER 2004 FBC, FUEL GAS - POWERED |
| | EQUIPMENT PERMANENTLY INSTALLED EQUIPMENT POWERED BY |
| | INTERNALCOMBUSTION ENGINES SHALL BE INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS AND NFPA 37.NFPA 37 INSTALLATION & |
| | USE OF STATIONARY COMBUSTION ENGINES & GAS TURBINES: |
| | 4.1.4ENGINES (GENERATORS) LOCATED OUTDOORS SHALL BE |
| | MINIMUM OF 5 FT FROM OPENINGS IN WALLS & AT LEAST 5 FT |
| | FROM STRUCTURES HAVING COMBUSTIBLE WALLS.A MINIMUM |
| | CLEARANCE IS NOT REQUIRED WHEN (1) THE ADJACENT WALL |
| | HAS A MINIMUM FIRE RESISTANCE RATING OF 1 HOUR OR (2) |
| | THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NON-COMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED |
| | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| | COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 |
| | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES |
| | OR |
| | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION |
| | INTAKES. |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS |
| | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE |
| | TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF |
| | STRUCTURE. |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL |
| | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, |
| | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED |
| | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. |
| | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES |
| | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| | FOR THE FIELD INSPECTOR. . |
| | |