| 2008-01-14 13:29:26 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. ENERGY CALCULATIONS METHOD A FORM IS NOT SIGNED AND |
| | SEALED BY THE ARCHITECT. COMPLETION OF PROCEDURES |
| | DEMONSTRATING COMPLIANCE WITH THIS CODE FOR COMMERCIAL |
| | BUILDINGS SHALL BE SIGNED AND SEALED BY AN ARCHITECT OR |
| | ENGINEER LICENSED TO PRACTICE IN THE STATE OF FLORIDA |
| | IN ACCORDANCE WITH FBC 13-103.1.1.1. PLEASE CORRECT AND |
| | RESUBMIT ENERGY CALCULATIONS FOR REVIEW. |
| | |
| | 2. ENERGY CALCULATIONS: PLEASE SEE PAGE 2 "COMPLIANCE |
| | SUMMARY" CONTAINS AN IMPORTANT NOTE IN BOLD TYPE WHICH |
| | STATES THAT THE INPUT DATA REPORTFOR THE DESIGN |
| | BUILDING MUST BE SUBMITTED ALONG WITH THE COMPLIANCE |
| | REPORT. PLEASE ATTACH THE INPUT DATA REPORT TO THE |
| | ENERGY CALCULATIONS AND RESUBMIT FOR REVIEW. |
| | |
| | 3. PG M-0 EXHAUST FAN SCHEDULE INDICATES EXHAUST FANS |
| | ARE TO BE CONTROLLED BY LIGHT SWITCHES. AS THE |
| | RESTROOMS IN THESE AREAS ARE PROVIDED WITH SUPPLY AIR, |
| | PLEASE SHOW COMPLIANCE WITH FBC, M 403.2.1(3). ALL AIR |
| | SUPPLIED TO RESTROOMS SHALL BE EXHAUSTED, INCLUDING ANY |
| | AIR IN EXCESS OF THAT REQUIRED BY TABLE 403.3. |
| | |
| | 4. OUTSIDE AIR CALCULATIONS: OCCUPANCY IS SHOWN AS |
| | "OFFICE" BUT PLANS SHOW THESE TO BE RECREATION AREAS OR |
| | "TV ROOMS." THE OFFICE OCCUPANCY IS NOT APPROPRIATE FOR |
| | THIS USE. PLEASE NOTE THAT ARCHITECTURAL PLANS HAVE |
| | DECLARED THESE AREAS AS AN A2 (ASSEMBLY) OCCUPANCY. |
| | ALSO, THE CALCULATIONS STATE ASHRAE 62.1-2004 AND FBC, |
| | M 403.3 USED FOR CALCULATIONS. PLEASE DECLARE ONE |
| | DESIGN METHOD OR THE OTHER IN ACCORDANCE WITH FBC, M |
| | 403.4. SELECT THE CLOSEST MATCHING OCCUPANCY TYPE |
| | DEPENDING ON THE METHOD USED AND SHOW CACLULATIONS FOR |
| | EACH OF THE INDIVIDUAL (NORTH AND EAST) SPACES TO |
| | DETERMINE HOW MUCH OUTSIDE AIR IS NEEDED FOR EACH |
| | SPACE. |
| | NOTE: IF ASHRAE 62.1-2004 IS USED, COMMENT #3 ABOVE IS |
| | NOT APPLICABLE AND CAN BE DISREGARDED. |
| | |