| Plan Review Notes For Permit 07120517 |
| Permit Number |
07120517 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-07 15:54:59 | ***DENIED*** | | | | | | 1) RAMPS SHALL HAVE HANDRAILS ON BOTH SIDES. | | | | | | 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS TO BE PROVIDED AT | | | LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE. | | | | | | 5) PLEASE PROVIDE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS | | | A,B OR C. | | | | | | 6) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 7) PLEASE PROVIDE DOOR SCHEDULE IF NEW DOORS ARE BEING | | | INSTALLED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|