| 2007-12-24 11:29:36 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED ARE NOT SIGNED, DATED OR SEALED BY THE |
| | DESIGNER(S) OF RECORD. PLEASE SEE FBC 103.1.1.1, FS |
| | 481.221, 471.025 |
| | PLEASE SEE THAT NO INPUT DATA REPORT WAS SUBMITTED |
| | WHICH IS SPECIFICALLY REQUIRED TO BE PART OF THE ENERGY |
| | CALCULATIONS AND SUMMARY SHEETS. SEE NOTE ON SHEET #2 |
| | OF THIS FLA COM PROGRAM WHICH STATES THE IDR MUST |
| | ACCOMPANY CALCULATIONS. |
| | PLEASE SEE THE OCCUPANCY AS STATED ON COVER SHEET |
| | STATES *DORMITORY*. HOW IS THIS POSSIBLE UNLESS THE |
| | BUILDING OCCUPANCY HAS CHANGED? |
| | PLEASE SEE THE TOTAL SQ FT FOR THE CALCULATIONS FOR NEW |
| | AIR CONDITIONED SPACE NEEDS TO CORRELATE WITH THE |
| | PLANS. |
| | PLEASE SEE 13-415.2 |
| | PLEASE SEE FAC 61G15-33.004 FOR REQUIRED LIGHTING |
| | DESIGNS. |
| | |
| | 2) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR NEW MTS DEVICES. PLEASE CLARIFY WHY THE 125AMP |
| | TRANSFER SWITCH IS BEING NOTED AS *SERVICE ENTRANCE |
| | RATED*? THIS IS NOT PART OF THE SERVICE ENTRANCE |
| | EQUIPMENT AND WOULD ONLY NEED TO BE RATED FOR *SERVICE |
| | EQUIPMENT*. |
| | THIS IS QUESTIONED AS THE 400A MTS IS NOT NOTED AS |
| | *SERVICE ENTRANCE RATED*. |
| | PLEASE CALL TO GO OVER. |
| | 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 3) NOTE: PLEASE CLARIFY THE SIZE OF THE MTS GOING IN |
| | FOR THE 400AMP SERVICE AS THE PLANS ON E-2 SHOW A MTS |
| | AS 300AMP. IS THIS ANOTHER MTS? IS THIS THE 125AMP MTS |
| | OR THE 400AMP MTS? |
| | PLEASE COORDINATE AND CLARIFY. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE RISER. PLEASE SEE THE HOUSE PANEL |
| | IS BEING SHOWN TAPPED FROM THE 400AMP GUTTER AND ALSO |
| | IS BEING FED FROM THE 125AMP MTS. |
| | PLEASE SEE THERE ARE A FEW ITEMS WHICH NEED TO BE |
| | ADDRESSED: |
| | |
| | A) PLEASE SEE THIS HOUSE PANEL AND CONDUCTORS IF TAPPED |
| | FROM THE 400AMP GUTTER WITH 400AMP OVER CURRENT |
| | PROTECTION MUST TERMINATE IN OVER CURRENT PROTECTION |
| | PER 240.21, 240.4, 310.16, AND 408.36. THIS PANEL IS |
| | SHOWN AS MAIN LUG ONLY. |
| | |
| | B) PLEASE SEE THIS HOUSE PANEL IF TAPPED FROM THE |
| | 400AMP GUTTER IS ALSO SHOWN FED FROM TWO SEPARATE |
| | SOURCES WHICH WOULD BE FEED FROM THE MTS FROM THE |
| | 200AMP MLO ON RISER. THIS MUST BE SOME SORT OF |
| | MISPRINT, AS THIS PANEL COULD BE SUBJECT TO NORMAL |
| | POWER AND EMERGENCY POWER AT THE SAME TIME. 702.6 |
| | |
| | C) PLEASE PROVIDE THE OVER CURRENT PROTECTION IN THE |
| | 200AMP MLO PANEL SHOWN ON RISER FEEDING THE NEW 125AMP |
| | MTS AND HOUSE PANEL. PROVIDE CONDUCTORS ETC. 240.4, |
| | 310.16 ETC AS NOTED ABOVE. |
| | |
| | 5) NOTE: PLEASE PROVIDE LOCATIONS ON PLANS FOR NEW |
| | PANELS *SP1 AND SP2*. |
| | 110.26, 408.17, 240.24 ETC |
| | FBC106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 6) NOTE: PLEASE SEE THE LOAD BEING SHOWN ON THE |
| | GENERATOR IS SHOWN EXCEEDING THE RATING OF CONDUCTORS |
| | AND EQUIPMENT. |
| | PLEASE SEE THE LOAD IS SHOWN AS 402AMPS AND EQUIPMENT |
| | HAS A MAXIMUM RATING SHOWN AT 400AMPS. |
| | 225.39, 240.4, 310.16, 702.5 ETC |
| | |
| | 7) NOTE: PLEASE COMPLETE GROUNDING ELECTRODE RISER FOR |
| | SERVICE EQUIPMENT PER 250.50. |
| | PLEASE SEE THE ONE NEW 400AMP SERVICE CONTAINS A NOTED |
| | FOR GROUNDING ELECTRODE HOWEVER THE OTHER RISER DOES |
| | NOT. |
| | PLEASE SEE A COMMON BONDING OF ALL SERVICE MAINS IS |
| | REQUIRED. |
| | PLEASE SEE 250.66, 250.50, 250.58, 250.92, 250.94, |
| | 250.96 ETC. |
| | |
| | 8) NOTE: PLEASE SEE 700.12F FOR CIRCUITING FOR |
| | EMERGENCY AND EXIT LIGHTS. PLEASE SEE E-1 AS EM LT IS |
| | CIRCUITED TO LIGHTING ON ANOTHER ROOM. |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |