Plan Review Notes
Plan Review Notes For Permit 07120517
Permit Number 07120517
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-24 11:29:36** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE NOT SIGNED, DATED OR SEALED BY THE
 DESIGNER(S) OF RECORD. PLEASE SEE FBC 103.1.1.1, FS
 481.221, 471.025
 PLEASE SEE THAT NO INPUT DATA REPORT WAS SUBMITTED
 WHICH IS SPECIFICALLY REQUIRED TO BE PART OF THE ENERGY
 CALCULATIONS AND SUMMARY SHEETS. SEE NOTE ON SHEET #2
 OF THIS FLA COM PROGRAM WHICH STATES THE IDR MUST
 ACCOMPANY CALCULATIONS.
 PLEASE SEE THE OCCUPANCY AS STATED ON COVER SHEET
 STATES *DORMITORY*. HOW IS THIS POSSIBLE UNLESS THE
 BUILDING OCCUPANCY HAS CHANGED?
 PLEASE SEE THE TOTAL SQ FT FOR THE CALCULATIONS FOR NEW
 AIR CONDITIONED SPACE NEEDS TO CORRELATE WITH THE
 PLANS.
 PLEASE SEE 13-415.2
 PLEASE SEE FAC 61G15-33.004 FOR REQUIRED LIGHTING
 DESIGNS.
  
 2) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR NEW MTS DEVICES. PLEASE CLARIFY WHY THE 125AMP
 TRANSFER SWITCH IS BEING NOTED AS *SERVICE ENTRANCE
 RATED*? THIS IS NOT PART OF THE SERVICE ENTRANCE
 EQUIPMENT AND WOULD ONLY NEED TO BE RATED FOR *SERVICE
 EQUIPMENT*.
 THIS IS QUESTIONED AS THE 400A MTS IS NOT NOTED AS
 *SERVICE ENTRANCE RATED*.
 PLEASE CALL TO GO OVER.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE CLARIFY THE SIZE OF THE MTS GOING IN
 FOR THE 400AMP SERVICE AS THE PLANS ON E-2 SHOW A MTS
 AS 300AMP. IS THIS ANOTHER MTS? IS THIS THE 125AMP MTS
 OR THE 400AMP MTS?
 PLEASE COORDINATE AND CLARIFY.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE RISER. PLEASE SEE THE HOUSE PANEL
 IS BEING SHOWN TAPPED FROM THE 400AMP GUTTER AND ALSO
 IS BEING FED FROM THE 125AMP MTS.
 PLEASE SEE THERE ARE A FEW ITEMS WHICH NEED TO BE
 ADDRESSED:
  
 A) PLEASE SEE THIS HOUSE PANEL AND CONDUCTORS IF TAPPED
 FROM THE 400AMP GUTTER WITH 400AMP OVER CURRENT
 PROTECTION MUST TERMINATE IN OVER CURRENT PROTECTION
 PER 240.21, 240.4, 310.16, AND 408.36. THIS PANEL IS
 SHOWN AS MAIN LUG ONLY.
  
 B) PLEASE SEE THIS HOUSE PANEL IF TAPPED FROM THE
 400AMP GUTTER IS ALSO SHOWN FED FROM TWO SEPARATE
 SOURCES WHICH WOULD BE FEED FROM THE MTS FROM THE
 200AMP MLO ON RISER. THIS MUST BE SOME SORT OF
 MISPRINT, AS THIS PANEL COULD BE SUBJECT TO NORMAL
 POWER AND EMERGENCY POWER AT THE SAME TIME. 702.6
  
 C) PLEASE PROVIDE THE OVER CURRENT PROTECTION IN THE
 200AMP MLO PANEL SHOWN ON RISER FEEDING THE NEW 125AMP
 MTS AND HOUSE PANEL. PROVIDE CONDUCTORS ETC. 240.4,
 310.16 ETC AS NOTED ABOVE.
  
 5) NOTE: PLEASE PROVIDE LOCATIONS ON PLANS FOR NEW
 PANELS *SP1 AND SP2*.
 110.26, 408.17, 240.24 ETC
 FBC106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE THE LOAD BEING SHOWN ON THE
 GENERATOR IS SHOWN EXCEEDING THE RATING OF CONDUCTORS
 AND EQUIPMENT.
 PLEASE SEE THE LOAD IS SHOWN AS 402AMPS AND EQUIPMENT
 HAS A MAXIMUM RATING SHOWN AT 400AMPS.
 225.39, 240.4, 310.16, 702.5 ETC
  
 7) NOTE: PLEASE COMPLETE GROUNDING ELECTRODE RISER FOR
 SERVICE EQUIPMENT PER 250.50.
 PLEASE SEE THE ONE NEW 400AMP SERVICE CONTAINS A NOTED
 FOR GROUNDING ELECTRODE HOWEVER THE OTHER RISER DOES
 NOT.
 PLEASE SEE A COMMON BONDING OF ALL SERVICE MAINS IS
 REQUIRED.
 PLEASE SEE 250.66, 250.50, 250.58, 250.92, 250.94,
 250.96 ETC.
  
 8) NOTE: PLEASE SEE 700.12F FOR CIRCUITING FOR
 EMERGENCY AND EXIT LIGHTS. PLEASE SEE E-1 AS EM LT IS
 CIRCUITED TO LIGHTING ON ANOTHER ROOM.
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]