Date Text
2008-01-16 16:56:36 
 BUILDING PLAN REVIEW
 PERMIT: 07120517
 ADD: 3700 N FLAGLER DR
 CONT: AITEK STEEL INDUSTRIES INC
 TEL: (561)662-8352
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) PERMIT APPLICATION THE OWNER INFORMATION DOES NOT
 MATCH THAT FOUND IN THE PROPERTY APPRAISERS OFFICE,
 PLEASE SEE ATTACHMENT. EITHER CORRECT THE OWNER
 INFORMATION FOUND ON THE PERMIT APPLICATION OR SHOW
 PROOF OF OWNERSHIP. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 3) THE BOUNDRY SURVEY INDICATES A ONE STORY ADDITION TO
 A THREE STORY BUILDING,PLEASE PROVIDE SOILS REPORTS.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 4) SHEET A0 :
 4A) DISCREPANCIES, CENTER OF THE SHEET THE PLANS
 INDICATE THE 2004 FBC CODE AND INDICATE THE BUILDING
 CATEGORY AS A MIXED A2/ MR, WHERE AS FURTHER TOWRARDS
 THE RIGHT OF THE SHEET A SECOND SQUARE INDICATES
 BUILDING DATA "USE" AS AN ASSISTED LIVING
 FACILITY(I-1). PLEASE ALSO NOTE THE PERMIT APPLICATION
 UNDER DESCRIPTION OF WORK INDICATES THIS BUILDING IS A
 NURSING HOME OR (I-2) OCCUPANCY. PLEASE UPDATE THE
 PERMIT APPLICATION AND PLANS TO REFLECT THE TRUE
 OCCUPANCY TYPE, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. 302.1.
  
 4B) PLANS INDICATE THIS BUILDING IS A BUILDING TYPE III
 PLANS DO NOT INDICATE IF THIS IS A "A OR B"
 CLASSIFICATION? SEE TABLE 503 AND 601 FOR
 CLARIFICATION.
  
 4C) SHEET A0 INDICATES THERE TO BE (4) BUILDINGS ON
 THIS SITE BUT THE PLANS DO NOT INDENTIFY AS TO WHICH
 BUILDING WORK IS TO BE COMPLETED UNDER THIS PERMIT AND
 OR IS THERE ANY FIRE WALLS SEPERATING STRUCTURES INTO
 "TRUE BUILDINGS".106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 4D) SHEET A0 ALSO INDICATES FIRE SPRINKLERED BUILDING,
 ARE THERE FIRE SPRINKLERS IN ALL PORTIONS OF THE
 BUILDING, AND WHAT TYPE OF SYSTEM IS INCORPORATED INTO
 THE BUILDING?
 106.1.2 ADDITIONAL INFORMATION REQUIRED, HAVE AREA
 INCREASES BEEN TAKEN, PROVIDE CALCULATIONS FOR THE AREA
 INCREASES. PLANS CURRENTLY DO NOT HAVE FIRE SPRINKLER
 PLANS INCORPERATED INTO THE PLANS, FOR AREA INCREASES
 TO BE TAKEN WE WILL NEED UPDATES FOR THE FIRE SPRIKLERS
 SECTION 506.3., & 902.3 EXISTING BUILDING CODE.
  
 4E)SHEET A0 THE CENTER BOX WITH THE 2004 FBC MENTIONS
 THE MEAN ROOF HEIGTH OF 19'-10" PLEASE EXPLAIN THE MEAN
 ROOF HEIGTH, PLANS INDICATE THIS BUILDING TO BE (3)
 STORIES TALL, IS THERE A FIRE WALL SEPERATING OUT THE
 VARIOUS BUILDINGS, THUS MAKING THE ADDITIONS A SINGLE
 STORY BUILDING? 106.1.2 AADDITIONAL INFORMATION
 REQUIRED. NOTE , THE WAY INFORMATION IS PRESENTED ON
 THE PLAN IT APPEARS THAT IF MULTIPLE BUILDING ARE ON
 THE SAME LOT THE DESIGNER MAY BE TAKING ADVANTAGE OF
 503.1.3? NOTE ALSO UNDER THE FIREWALL PORTION OF THE
 CODE IF THIS IS TAKEN THEN THE CLOSENESS OF BUILDING TO
 BUILDING WILL NEED TO BE CONSIDERED, TABLE602.
  
 4F) PLEASE PROVIDE HOW MANY RESIDENTPATIENTS ARE AT
 THIS FACILITY? PLEASE SEE ASCE 7-02 TABLE 1-1HEALTH
 CARE FACILITIES WITH 50 OR MORE PATIENTS THE BUILDING
 CATEGORY IS III, IMPORTANCE FACTOR IS 1.15 TABLE 6.1.
  
 4G) IN THE FLORIDA BUILDING CODE BOX THERE IS NO
 MENTION OF THE 2004 EXISTING BUILDING CODE, WHAT LEVEL
 OF ALTERATIONSIN THE EXISTING BUILDING PORTION OF
 WORK TO BE COMPLETED AND REQUIREMENTS FOR CHAPTER # 9
 FOR ADDITIONS.
  
 5)ACCESSIBILITY: 2004 EXISTING BUILDING CODE, 905.1
 PLEASE SEE MINIMUM REQUIREMENTS. ADDITIONS 11-4.1.5
 EACH SPACE OR ELEMENT ADDED TO THE EXISTING BUILDING OR
 FACILITY SHALL COMPLY WITH THE APPLICABLE PROVISONS OF
 11-4.1.1 TO 11-4.1.3 MINIMUM REQUIREMENTS FOR NEW
 CONSTRUCTION.
  
 5A) SHEET A2 & A6 BOTH INDICATE A NEW ACCESIBLE
 HANDICAPPED RAMP SHOWN ARE THREE ISSUES:
 1)11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR WIDTH
 OF A RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART
 OF A REQUIRED MEANS OF EGRESS SHALL NOT BELESS THAN
 44
 INCHES WIDE. LOCATED AT THE BOTTOM OF THE
 RAMP THERE APPEARS TO BE LESS THAN 30" CLEAR ACROSS THE
 RAMP.
  
  
 2) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARENCE.
 PLANS (A6) DO NOT INDICATE A BOTTOM LANDING.
  
  
 3) 11.4.8.5. (1-7)HANDRAILS: IF A RAMP HAS A RISE
 GREATER THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN
 72", THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE
 HANDRAIL
 EXTENSIONSARE MISSING, SEE FIGURE 17. NOTE
 HANDRAILS NOT GAURDRAILS!
  
 5B) SHEET A-6) ROOMS 108, 109 AND THE NEW RESTROOM
 (BATHROOM)ALL INDICATE NEW WALLS AND DOORWAYS, THEY
 ALSO INDICATE 32" WIDE DOORWAYS, PLEASE COMPLY WITH:
 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE
 A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN
 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND
 OPPOSITE STOP.
  
 5C) NEW RESTROOM (BATHROOM) ON SHEET A-6 IS REQUIRED TO
 BE ACCESSIBLE, PLEASE REVIEW 11-6.1(3) NURSING HOMES
 PUBLIC USE AND COMMON USE AREAS ARE REQUIRED TO BE
 DESIGNED AND CONSTRUCTED AS ACCESSIBLE.
  
 5D) SHOWER, PLEASE PROVIDE SECTIONS AND DETAILS FOR THE
 ACCESSIBLE SHOWER, PLEASE INCLUDE 11-4.21 (1-8),&
 11-4.26.3 (BACKING REQUIEMENTS).
  
 5E)NEW ACCESSIBLE RESTROOM WITHIN THE SHOWER
 ENCLOSURE IS TO COMPLY WITH:
 A)AN UNOBSTRUCTED TURNING RADIUS 11-4.2.3
 B) CLEAR FLOOR SPACE FOR FIXTURES 11-4.22.3. C)
 WHAT TYPE OF BACKING FOR GRAB BARS 11-4.26.3
  
 5F) SHEET A-4 PLANS INDICATE IN THE NORTH ADDITION WITH
 HANDICAPPED RESTROOM PLEASE PROVIDEADDITIONAL
 INFORMATION FOR THIS RESTROOM:
 A)AN UNOBSTRUCTED TURNING RADIUS 11-4.2.3
 B) CLEAR FLOOR SPACE FOR FIXTURES 11-4.22.3. C)
 WHAT TYPE OF BACKING FOR GRAB BARS 11-4.26.3
  
 5G) SHEET A-4 IN THE NEW TV ROOM THERE IS AN EXISTING
 WINDOW THAT IS BEING BEING DELETED AND A NEW DOORWAY.
 THIS NEW DOORWAY INDICATES IT A 2'-8" WIDE DOORWAY
 LEAVING LESS THAN THE REQUIRED 32" ,
 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE
 A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN
 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND
 OPPOSITE STOP.
  
 5H)A-6PLEASE PROVIDE ADDITONAL INFORMATION ON THE
 SINK IN THE NEW TV ROOM.11-4.24.2 HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34"
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5I) SHEET A-4 NEW TV ROOM INDICATES EXTERIOR STAIRS,
 PLEASE PROVIDE A SITE PLAN THAT PROVIDES THE ACCESSIBLE
 ROUTE : ADDITIONS 11-4.1.5 EACH SPACE OR ELEMENT ADDED
 TO THE EXISTING BUILDING OR FACILITY SHALL COMPLY WITH
 THE APPLICABLE PROVISONS OF 11-4.1.1 TO 11-4.1.3
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION.11-4.1.3(1)
 AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL CONNECT ACCESSIBLE
 BUILDING OR FACILITY ENETRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY.
 THIS STAIR MAY OR MAY NOT BE REQUIRED TO BE A RAMP
 DEPENDING ON THE ACCESSIBLE SITE PLAN TO BE PROVIDED.
  
 5J) PLEASE PROVIDE COMPLIANCE WITH 11-2.1(4)(B) ALTERED
 PATIENT BEDROOMS.
  
 6) PLANS ARE NOT CLEAR AS TO OCCUPANCY I-1 VERSES I-2,
 SEE EXISTING BUILDING CODE LEVEL II 605.1 WHEN WORK IS
 BEING COMPLETED IN CORRIDORS SHARED BY MORE THAN 1
 TENANT.
 1016.2(6) 96" CORRIDORS, ALSO SEE 407.3 FOR I-2
 OCCUPANCY.EXISTING BUILDING CODE
  
  
 7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 A) EXTERIOR GLAZED DOORS
 B) EXTERIOR HOLLOW METAL DOORS
 C) TRUSS ANCHORS
 D) ROOFING ASSEMBLIES
  
 8)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 9)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10)THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH
 THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2& 3__ .
  
 _XX__ SUBSYSTEM NOT HIGHLIGHTED- THE SYSTEM PROVIDED
 STATESLIMITATION# 7, SHOULD THE FASTENERRESISTANCE
 BE LESS THAN THAT REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISEDFASTENER SPACING,
 PREPARED , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTEREDARCHITECT OR
 REGISTERED ROOFCONSULTANT MAY BE SUBMITTED.
  
 _XX__SUBSYSTEM NOT HIGHLIGHTED- THE SYSTEM PROVIDED
 INDICATES LIMITATION# 9, NO ENHANCED FASTENING
 ALLOWED.
  
 11)109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 12)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved