| 2008-01-16 16:56:36 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120517 |
| | ADD: 3700 N FLAGLER DR |
| | CONT: AITEK STEEL INDUSTRIES INC |
| | TEL: (561)662-8352 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS. |
| | |
| | 2) PERMIT APPLICATION THE OWNER INFORMATION DOES NOT |
| | MATCH THAT FOUND IN THE PROPERTY APPRAISERS OFFICE, |
| | PLEASE SEE ATTACHMENT. EITHER CORRECT THE OWNER |
| | INFORMATION FOUND ON THE PERMIT APPLICATION OR SHOW |
| | PROOF OF OWNERSHIP. 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 3) THE BOUNDRY SURVEY INDICATES A ONE STORY ADDITION TO |
| | A THREE STORY BUILDING,PLEASE PROVIDE SOILS REPORTS. |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | |
| | 4) SHEET A0 : |
| | 4A) DISCREPANCIES, CENTER OF THE SHEET THE PLANS |
| | INDICATE THE 2004 FBC CODE AND INDICATE THE BUILDING |
| | CATEGORY AS A MIXED A2/ MR, WHERE AS FURTHER TOWRARDS |
| | THE RIGHT OF THE SHEET A SECOND SQUARE INDICATES |
| | BUILDING DATA "USE" AS AN ASSISTED LIVING |
| | FACILITY(I-1). PLEASE ALSO NOTE THE PERMIT APPLICATION |
| | UNDER DESCRIPTION OF WORK INDICATES THIS BUILDING IS A |
| | NURSING HOME OR (I-2) OCCUPANCY. PLEASE UPDATE THE |
| | PERMIT APPLICATION AND PLANS TO REFLECT THE TRUE |
| | OCCUPANCY TYPE, 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. 302.1. |
| | |
| | 4B) PLANS INDICATE THIS BUILDING IS A BUILDING TYPE III |
| | PLANS DO NOT INDICATE IF THIS IS A "A OR B" |
| | CLASSIFICATION? SEE TABLE 503 AND 601 FOR |
| | CLARIFICATION. |
| | |
| | 4C) SHEET A0 INDICATES THERE TO BE (4) BUILDINGS ON |
| | THIS SITE BUT THE PLANS DO NOT INDENTIFY AS TO WHICH |
| | BUILDING WORK IS TO BE COMPLETED UNDER THIS PERMIT AND |
| | OR IS THERE ANY FIRE WALLS SEPERATING STRUCTURES INTO |
| | "TRUE BUILDINGS".106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 4D) SHEET A0 ALSO INDICATES FIRE SPRINKLERED BUILDING, |
| | ARE THERE FIRE SPRINKLERS IN ALL PORTIONS OF THE |
| | BUILDING, AND WHAT TYPE OF SYSTEM IS INCORPORATED INTO |
| | THE BUILDING? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED, HAVE AREA |
| | INCREASES BEEN TAKEN, PROVIDE CALCULATIONS FOR THE AREA |
| | INCREASES. PLANS CURRENTLY DO NOT HAVE FIRE SPRINKLER |
| | PLANS INCORPERATED INTO THE PLANS, FOR AREA INCREASES |
| | TO BE TAKEN WE WILL NEED UPDATES FOR THE FIRE SPRIKLERS |
| | SECTION 506.3., & 902.3 EXISTING BUILDING CODE. |
| | |
| | 4E)SHEET A0 THE CENTER BOX WITH THE 2004 FBC MENTIONS |
| | THE MEAN ROOF HEIGTH OF 19'-10" PLEASE EXPLAIN THE MEAN |
| | ROOF HEIGTH, PLANS INDICATE THIS BUILDING TO BE (3) |
| | STORIES TALL, IS THERE A FIRE WALL SEPERATING OUT THE |
| | VARIOUS BUILDINGS, THUS MAKING THE ADDITIONS A SINGLE |
| | STORY BUILDING? 106.1.2 AADDITIONAL INFORMATION |
| | REQUIRED. NOTE , THE WAY INFORMATION IS PRESENTED ON |
| | THE PLAN IT APPEARS THAT IF MULTIPLE BUILDING ARE ON |
| | THE SAME LOT THE DESIGNER MAY BE TAKING ADVANTAGE OF |
| | 503.1.3? NOTE ALSO UNDER THE FIREWALL PORTION OF THE |
| | CODE IF THIS IS TAKEN THEN THE CLOSENESS OF BUILDING TO |
| | BUILDING WILL NEED TO BE CONSIDERED, TABLE602. |
| | |
| | 4F) PLEASE PROVIDE HOW MANY RESIDENTPATIENTS ARE AT |
| | THIS FACILITY? PLEASE SEE ASCE 7-02 TABLE 1-1HEALTH |
| | CARE FACILITIES WITH 50 OR MORE PATIENTS THE BUILDING |
| | CATEGORY IS III, IMPORTANCE FACTOR IS 1.15 TABLE 6.1. |
| | |
| | 4G) IN THE FLORIDA BUILDING CODE BOX THERE IS NO |
| | MENTION OF THE 2004 EXISTING BUILDING CODE, WHAT LEVEL |
| | OF ALTERATIONSIN THE EXISTING BUILDING PORTION OF |
| | WORK TO BE COMPLETED AND REQUIREMENTS FOR CHAPTER # 9 |
| | FOR ADDITIONS. |
| | |
| | 5)ACCESSIBILITY: 2004 EXISTING BUILDING CODE, 905.1 |
| | PLEASE SEE MINIMUM REQUIREMENTS. ADDITIONS 11-4.1.5 |
| | EACH SPACE OR ELEMENT ADDED TO THE EXISTING BUILDING OR |
| | FACILITY SHALL COMPLY WITH THE APPLICABLE PROVISONS OF |
| | 11-4.1.1 TO 11-4.1.3 MINIMUM REQUIREMENTS FOR NEW |
| | CONSTRUCTION. |
| | |
| | 5A) SHEET A2 & A6 BOTH INDICATE A NEW ACCESIBLE |
| | HANDICAPPED RAMP SHOWN ARE THREE ISSUES: |
| | 1)11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR WIDTH |
| | OF A RAMP SHALL BE 36". EXCEPTION: RAMPS THAT ARE PART |
| | OF A REQUIRED MEANS OF EGRESS SHALL NOT BELESS THAN |
| | 44 |
| | INCHES WIDE. LOCATED AT THE BOTTOM OF THE |
| | RAMP THERE APPEARS TO BE LESS THAN 30" CLEAR ACROSS THE |
| | RAMP. |
| | |
| | |
| | 2) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS |
| | SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH |
| | RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL |
| | CLEARENCE. |
| | PLANS (A6) DO NOT INDICATE A BOTTOM LANDING. |
| | |
| | |
| | 3) 11.4.8.5. (1-7)HANDRAILS: IF A RAMP HAS A RISE |
| | GREATER THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN |
| | 72", THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE |
| | HANDRAIL |
| | EXTENSIONSARE MISSING, SEE FIGURE 17. NOTE |
| | HANDRAILS NOT GAURDRAILS! |
| | |
| | 5B) SHEET A-6) ROOMS 108, 109 AND THE NEW RESTROOM |
| | (BATHROOM)ALL INDICATE NEW WALLS AND DOORWAYS, THEY |
| | ALSO INDICATE 32" WIDE DOORWAYS, PLEASE COMPLY WITH: |
| | 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE |
| | A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN |
| | 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND |
| | OPPOSITE STOP. |
| | |
| | 5C) NEW RESTROOM (BATHROOM) ON SHEET A-6 IS REQUIRED TO |
| | BE ACCESSIBLE, PLEASE REVIEW 11-6.1(3) NURSING HOMES |
| | PUBLIC USE AND COMMON USE AREAS ARE REQUIRED TO BE |
| | DESIGNED AND CONSTRUCTED AS ACCESSIBLE. |
| | |
| | 5D) SHOWER, PLEASE PROVIDE SECTIONS AND DETAILS FOR THE |
| | ACCESSIBLE SHOWER, PLEASE INCLUDE 11-4.21 (1-8),& |
| | 11-4.26.3 (BACKING REQUIEMENTS). |
| | |
| | 5E)NEW ACCESSIBLE RESTROOM WITHIN THE SHOWER |
| | ENCLOSURE IS TO COMPLY WITH: |
| | A)AN UNOBSTRUCTED TURNING RADIUS 11-4.2.3 |
| | B) CLEAR FLOOR SPACE FOR FIXTURES 11-4.22.3. C) |
| | WHAT TYPE OF BACKING FOR GRAB BARS 11-4.26.3 |
| | |
| | 5F) SHEET A-4 PLANS INDICATE IN THE NORTH ADDITION WITH |
| | HANDICAPPED RESTROOM PLEASE PROVIDEADDITIONAL |
| | INFORMATION FOR THIS RESTROOM: |
| | A)AN UNOBSTRUCTED TURNING RADIUS 11-4.2.3 |
| | B) CLEAR FLOOR SPACE FOR FIXTURES 11-4.22.3. C) |
| | WHAT TYPE OF BACKING FOR GRAB BARS 11-4.26.3 |
| | |
| | 5G) SHEET A-4 IN THE NEW TV ROOM THERE IS AN EXISTING |
| | WINDOW THAT IS BEING BEING DELETED AND A NEW DOORWAY. |
| | THIS NEW DOORWAY INDICATES IT A 2'-8" WIDE DOORWAY |
| | LEAVING LESS THAN THE REQUIRED 32" , |
| | 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE |
| | A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN |
| | 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND |
| | OPPOSITE STOP. |
| | |
| | 5H)A-6PLEASE PROVIDE ADDITONAL INFORMATION ON THE |
| | SINK IN THE NEW TV ROOM.11-4.24.2 HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" |
| | ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 5I) SHEET A-4 NEW TV ROOM INDICATES EXTERIOR STAIRS, |
| | PLEASE PROVIDE A SITE PLAN THAT PROVIDES THE ACCESSIBLE |
| | ROUTE : ADDITIONS 11-4.1.5 EACH SPACE OR ELEMENT ADDED |
| | TO THE EXISTING BUILDING OR FACILITY SHALL COMPLY WITH |
| | THE APPLICABLE PROVISONS OF 11-4.1.1 TO 11-4.1.3 |
| | MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION.11-4.1.3(1) |
| | AT LEAST ONE ACCESSIBLE |
| | ROUTE COMPLYING WITH 11-4.3 SHALL CONNECT ACCESSIBLE |
| | BUILDING OR FACILITY ENETRANCES WITH ALL ACCESSIBLE |
| | SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY. |
| | THIS STAIR MAY OR MAY NOT BE REQUIRED TO BE A RAMP |
| | DEPENDING ON THE ACCESSIBLE SITE PLAN TO BE PROVIDED. |
| | |
| | 5J) PLEASE PROVIDE COMPLIANCE WITH 11-2.1(4)(B) ALTERED |
| | PATIENT BEDROOMS. |
| | |
| | 6) PLANS ARE NOT CLEAR AS TO OCCUPANCY I-1 VERSES I-2, |
| | SEE EXISTING BUILDING CODE LEVEL II 605.1 WHEN WORK IS |
| | BEING COMPLETED IN CORRIDORS SHARED BY MORE THAN 1 |
| | TENANT. |
| | 1016.2(6) 96" CORRIDORS, ALSO SEE 407.3 FOR I-2 |
| | OCCUPANCY.EXISTING BUILDING CODE |
| | |
| | |
| | 7)FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | A) EXTERIOR GLAZED DOORS |
| | B) EXTERIOR HOLLOW METAL DOORS |
| | C) TRUSS ANCHORS |
| | D) ROOFING ASSEMBLIES |
| | |
| | 8)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 9)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10)THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH |
| | THE FOLLOW ITEMS: |
| | |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. |
| | |
| | _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| | USED. |
| | |
| | _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | _2& 3__ . |
| | |
| | _XX__ SUBSYSTEM NOT HIGHLIGHTED- THE SYSTEM PROVIDED |
| | STATESLIMITATION# 7, SHOULD THE FASTENERRESISTANCE |
| | BE LESS THAN THAT REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISEDFASTENER SPACING, |
| | PREPARED , SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTEREDARCHITECT OR |
| | REGISTERED ROOFCONSULTANT MAY BE SUBMITTED. |
| | |
| | _XX__SUBSYSTEM NOT HIGHLIGHTED- THE SYSTEM PROVIDED |
| | INDICATES LIMITATION# 9, NO ENHANCED FASTENING |
| | ALLOWED. |
| | |
| | 11)109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 12)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 13)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |