2008-02-14 13:27:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE CORRECT ASCE REFERENCE IS ASCE7-02; ASCE7-05
 CANNOT BE USED UNTIL INCORPORATED INTO FBC CHAPTER 35.
  
 2.PLEASE PROVIDE CALCULATIONS FOR THE DESIGN PRESSURE
 SPECIFIED OF -50.8, 280' HIGH BUILDING, EXPOSURE C,
 213SF OPENING.
  
 3.DOCUMENTS PREPARED BY AN ARCHITECT ARE TO CONTAIN
 ALL INFORMATION REQUIRED BY FAC61G1-16.003,004.