| 2008-08-13 15:28:44 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | 1. SHTS P1.2 & P2.1, THE FLOOR DRAIN AT THE LOADING |
| | DOCK IS NOT VENTED. SECTION 901.2.1. |
| | |
| | 2. SHTS P1.2 & P2.1, THE RUNNING TRAP DOWNSTREAM OF THE |
| | FLOOR SINK S-4 IN THE LABORATORY 110 SHALL HAVE A |
| | CLEANOUT ON THE INLET SIDE UP TO FLOOR LEVEL. |
| | |
| | 3. SHTS P1.2 & P2.1, THE TRAPS IN THE FREEZER ROOM 109. |
| | PLEASE INDICATE HOW THE WATER IN THE TRAPS WILL NOT |
| | FREEZE. SECTION 106.1.2.--ALSO THE 2" TRAP RUNNING |
| | THRU THE FLOOR DRAIN TRAP AND THEN THRU THE RUNNING |
| | TRAP IS TRIPLE TRAPPED. THE FLOOR DRAIN IN THE FREEZER |
| | ROOM IS DOUBLE TRAPPED. THIS IS NOT PERMITTED PER |
| | SECTION 1002.1. PLEASE INDICATE WHAT IS BEING DRAINED |
| | INTO THE 2" DRAIN AND THE FLOOR DRAIN INSIDE THE |
| | FREEZER ROOM. SECTION 106.1.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |