Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop P
Sequence Number 7
Notes
Date Text
2008-08-13 15:28:44DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHTS P1.2 & P2.1, THE FLOOR DRAIN AT THE LOADING
 DOCK IS NOT VENTED. SECTION 901.2.1.
  
 2. SHTS P1.2 & P2.1, THE RUNNING TRAP DOWNSTREAM OF THE
 FLOOR SINK S-4 IN THE LABORATORY 110 SHALL HAVE A
 CLEANOUT ON THE INLET SIDE UP TO FLOOR LEVEL.
  
 3. SHTS P1.2 & P2.1, THE TRAPS IN THE FREEZER ROOM 109.
 PLEASE INDICATE HOW THE WATER IN THE TRAPS WILL NOT
 FREEZE. SECTION 106.1.2.--ALSO THE 2" TRAP RUNNING
 THRU THE FLOOR DRAIN TRAP AND THEN THRU THE RUNNING
 TRAP IS TRIPLE TRAPPED. THE FLOOR DRAIN IN THE FREEZER
 ROOM IS DOUBLE TRAPPED. THIS IS NOT PERMITTED PER
 SECTION 1002.1. PLEASE INDICATE WHAT IS BEING DRAINED
 INTO THE 2" DRAIN AND THE FLOOR DRAIN INSIDE THE
 FREEZER ROOM. SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  