Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop M
Sequence Number 6
Notes
Date Text
2008-11-15 11:28:21REVIEW #: REVISION
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1.1: NOTE ON PLAN INDICATES SHOP DRAWINGS ARE TO
 BE USED TO SHOW DEVIATIONS FROM THE MECHANICAL PLANS.
 NO SHOP DRAWINGS HAVE BEEN SUBMITTED OR REVIEWED FOR
 CODE COMPLIANCE. SHOP DRAWINGS MAY NOT BE USED TO AMEND
 OR REVISE THE APPROVED CONSTRUCTION DOCUMENTS. ANY
 DEVIATIONS FROM THE PERMIT SET OF MECHANICAL PLANS
 SHALL BE DOCUMENTED AS A REVISION TO THE PERMIT SET OF
 MECHANICAL PLANS. FBCB 106.4: WORK SHALL BE INSTALLED
 IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS,
 AND ANY CHANGES MADE DURING CONSTRUCTION THAT ARE NOT
 IN COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS
 SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF
 CONSTRUCTION DOCUMENTS.
  
 2. PG M1.1: THERE ARE MULTIPLE CHANGES ON THIS PAGE
 WHICH ARE NOT IDENTIFIED AS CHANGES ON THE PLANS.
 PLEASE IDENTIFY THE NATURE AND LOCATION OF ALL CHANGES
 FROM THE CURRENT PERMIT PLANS WITH THE USE OF CLOUDS OR
 OTHER ESTABLISHED AND RECOGNIZED MEANS. SEE FBCB
 106.1.3.
  
 3. CHANGES ON OTHER PAGES CAN NOT BE INCORPORATED INTO
 THE PERMIT SET OF PLANS UNTIL REVISED M1.1 IS
 INCORPORATED INTO THE PERMIT SET. THIS WILL PREVENT
 CONFLICTS BETWEEN THESE PAGES AND THE MAIN DUCTWORK
 FLOOR PLAN.
  