| 2008-11-15 11:28:21 | REVIEW #: REVISION |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PG M1.1: NOTE ON PLAN INDICATES SHOP DRAWINGS ARE TO |
| | BE USED TO SHOW DEVIATIONS FROM THE MECHANICAL PLANS. |
| | NO SHOP DRAWINGS HAVE BEEN SUBMITTED OR REVIEWED FOR |
| | CODE COMPLIANCE. SHOP DRAWINGS MAY NOT BE USED TO AMEND |
| | OR REVISE THE APPROVED CONSTRUCTION DOCUMENTS. ANY |
| | DEVIATIONS FROM THE PERMIT SET OF MECHANICAL PLANS |
| | SHALL BE DOCUMENTED AS A REVISION TO THE PERMIT SET OF |
| | MECHANICAL PLANS. FBCB 106.4: WORK SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS, |
| | AND ANY CHANGES MADE DURING CONSTRUCTION THAT ARE NOT |
| | IN COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS |
| | SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PG M1.1: THERE ARE MULTIPLE CHANGES ON THIS PAGE |
| | WHICH ARE NOT IDENTIFIED AS CHANGES ON THE PLANS. |
| | PLEASE IDENTIFY THE NATURE AND LOCATION OF ALL CHANGES |
| | FROM THE CURRENT PERMIT PLANS WITH THE USE OF CLOUDS OR |
| | OTHER ESTABLISHED AND RECOGNIZED MEANS. SEE FBCB |
| | 106.1.3. |
| | |
| | 3. CHANGES ON OTHER PAGES CAN NOT BE INCORPORATED INTO |
| | THE PERMIT SET OF PLANS UNTIL REVISED M1.1 IS |
| | INCORPORATED INTO THE PERMIT SET. THIS WILL PREVENT |
| | CONFLICTS BETWEEN THESE PAGES AND THE MAIN DUCTWORK |
| | FLOOR PLAN. |
| | |