2008-08-25 16:20:58REVIEW #: REVISION 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1.1: KEYED NOTE #6 CALLS FOR 4 INCH DRYER DUCT
 UP TO THE ROOF. IS THIS DUCT ISOLATED FROM OR EXPOSED
 TO THE RETURN AIR PLENUM CEILING? CLOTHES DRYER EXHAUST
 DUCTS SHALL NOT EXTEND INTO OR THROUGH DUCTS OR PLENUMS
 IN ACCORDANCE WITH FBCM 504.4.
  
 2. PAGE M1.1: KEYED NOTE #12 REFERS TO 35X18 RETURN
 DUCTS. HOWEVER, ON THE FLOOR PLAN, NOTE #12 IS
 ASSOCIATED WITH TWO 12X12 TRANSFER OPENINGS. PLEASE
 CLARIFY PER FBCB 106.1.1 AND FBCM 603.1.
  
 3. PAGE M1.2: WHAT IS THE PURPOSE OF THE ROUND
 GOOSENECK DETAIL #1 ON THIS PAGE? THERE IS NO
 INDICATION OF THIS TYPE OF TERMINATION ON THE ROOF
 PLAN. THE DRYER EXHAUST ON THE ROOF HAS A DETAIL ON
 M3.1. PLEASE CLARIFY PER FBCB 106.1.1.
  
 4. PAGE M3.1: IS THE BACKDRAFT DAMPER ON THE DRYER
 EXHAUST OUTLET DESIGNED TO KEEP RAIN OUT OF THE DUCT?
 EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED AGAINST LOCAL WEATHER CONDITIONS IN
 ACCORDANCE WITH FBCM 401.6.
  