| 2008-04-18 10:31:20 | ** DENIED3RD REVIEW** |
| | |
| | 1) NOTE: PLEASE PROVIDE THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE MTS. THE SUBMITTALS FOR THE QUICK |
| | CONNECT CABINET ARE FOR THE OUTSIDE EQUIPMENT ONLY. |
| | 110.7, 702.6, 90.7 |
| | PLEASE SUBMIT. |
| | |
| | 2) NOTE: PLEASE SUBMIT INFORMATION ON THE MDP1 FOR |
| | COMPLIANCE WITH 230.76 AND 230.79. |
| | THIS WAS NOT A PREVIOUS COMMENT HOWEVER AS THE RISER |
| | INDICATES A *SHUNT TRIP* ONLY AND NEITHER THE RISER OR |
| | THE MDP1 SCHEDULE INDICATES AN ACTUAL MAIN CIRCUIT |
| | BREAKER THERE IS A CONCERN THAT THIS BREAKER MAY BE A |
| | SHUNT TIP ONLY BREAKER. PLEASE PROVIDE MORE INFORMATION |
| | ON RISER/SCHEDULE SHEET OR PROVIDE ACTUAL SPECS/CUT |
| | SHEETS WHICH SHOW THE MAIN CIRCUIT BREAKER WITH A |
| | MANUAL HANDLE ETC. |
| | ** SHUNT TIP ONLY BREAKERS WITHOUT MANUAL MEANS OF |
| | DISCONNECT ON OUTSIDE OF EQUIPMENT ARE NOT PERMITTED BY |
| | CODE AND SECTIONS ARE GIVEN ABOVE. |
| | 110.3, 90.7. |
| | |
| | |
| | 3) NOTE: PLEASE SEE THE RTU-3 IS SHOWING A 90AMP |
| | BREAKER WHEN THE RISER SHOWS A 125AMP BREAKER FEEDING |
| | THIS UNIT. THE SHEET M0.2 SHOWS MAXIMUM OCP AS 90AMP. |
| | THIS COULD BE REDLINED *IF* NO OTHER CHANGES WERE NEED |
| | HOWEVER DUE TO COMMENT NUMBER TWO ABOVE THIS MAY BE |
| | CORRECTED AT THE SAME TIME. |
| | FBC 106.1.2ADMIN SECTION FOR COORDINATION. |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | DO NOT COORDINATE WITH THE LIGHTING AS SHOWN ON THE |
| | PLANS. |
| | THE BELOW ARE SOME EXAMPLES HOWEVER IS NOT AN EXHAUSTED |
| | LIST. PLEASE BE SURE ALL LIGHTING ON PLANS IS PLACED |
| | INTO THE INPUT DATA REPORT. |
| | ** PLEASE KNOW THE WATTAGE FIGURED INTO THE INPUT DATA |
| | REPORT (IDR) SHALL BE BASED ON THE FIXTURE AVAILABLE |
| | WATTAGE OR OUTPUT AND NOT THE WATTAGE OF THE BULB(S) |
| | INSTALLED. |
| | ** PLEASE SEE THE JURISDICTION ALSO NEEDS TO BE UPDATED |
| | AS THIS IS SHOWN AS PALM BEACH, PALM BEACH COUNTY. THIS |
| | SHOULD BE CITY OF WEST PALM BEACH, PALM BEACH COUNTY. |
| | THERE IS A PALM BEACH LOCATED ON PALM BEACH COUNTY |
| | WHICH IS NOT THIS JURISDICTION. PLEASE ADJUST. |
| | |
| | ******* |
| | FOR EXAMPLE: |
| | PLEASE SEE EXTERIOR LIGHTING ON PLANS WHICH SHOW MORE |
| | *R* FIXTURES THAN WHAT IS SHOWN ON THE IDR FOR EXTERIOR |
| | LIGHTS. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INTERIOR LIGHTING FOR ROOM/AREA 147. |
| | PLANS SHOW 2-A3 FIXTURES AND 2-A3E FIXTURES. THE |
| | WATTAGE AS SHOWN ON THE FIXTURE LEGEND FOR EACH OF |
| | THESE FIXTURES IS 96W, YET THE INPUT DATA REPORT ONLY |
| | SHOWS 56W EACH. |
| | FOR EXAMPLE: |
| | PLEASE SEE CONFERENCE ROOM #118 WHICH APPEARS TO SHOW A |
| | FIXTURE I1; HOWEVER THE IDR FOR THIS SAME ROOM DOES NOT |
| | INDICATE ANY WATTAGE FOR THIS SAME FIXTURE. |
| | FOR EXAMPLE: |
| | PLEASE SEE DISPLAY AREA AT FRONT ENTRY. WHERE ARE THESE |
| | FIXTURES SHOWN ON THE IDR? WHERE IS THE FIXTURE M1? M1 |
| | IS SHOWN AS A METAL HALIDE FIXTURE AND DOES NOT APPEARS |
| | ON THE COMPANY WEBSITE AS A CURRENT 3INCH HID FIXTURE. |
| | THERE ARE 3INCH FIXTURES HOWEVER THE WATTAGE IS HIGHER. |
| | THE SMALLEST HID FIXTURE LISTED IS 4INCH. |
| | PLEASE PROVIDE SPEC/CUT SHEET SHOWING THIS FIXTURE. |
| | FOR EXAMPLE: |
| | PLEASE SEE SOME AREAS ARE SHOWING THE EXIT SIGN FIGURED |
| | INTO THE CALCULATIONS HOWEVER SOME AREAS THESE ARE NOT |
| | FIGURED. PLEASE KNOW THAT THE EXIT SIGNS WHICH ARE NOT |
| | A PART OF THE NORMAL LIGHTING ARE EXEMPT. PLEASE ALSO |
| | SEE THE IDR SHOWS THE EXIT SIGNS AS BEING PART OF THE |
| | CENTRAL LIGHTING CONTROL SYSTEM. PLEASE EXPLAIN WHY TWO |
| | OF THESE EXIT SIGNS ARE ON THE IDR. |
| | FOR EXAMPLE: |
| | PLEASE SEE ROOM 130 WHICH SHOWS A6 AND A6E FIXTURES. |
| | THE FIXTURE LEGEND SHOWS 192W FOR EACH, YET THE IDR |
| | ONLY SHOWS 128W. WHAT IS THE POWER FACTOR ON THESE? |
| | EVEN WITH SOME OF THE HIGHEST EFFICIENCY FIXTURES THIS |
| | LEVEL OF 128W COULD NOT BE FOUND. BASED ON THE FIXTURE, |
| | THE FIXTURE LEGEND THE COMPANY WEBSITE SHOWS 219 INPUT |
| | WATTS WITH A POWER FACTOR OF .97. |
| | |
| | *** PLEASE GO THOUGH ALL LIGHTING ON PLANS AND |
| | COORDINATE WITH THE IDR. |
| | PLEASE SEE ATTACHED SPEC SHEET FOR THE A6 FIXTURES IS |
| | ATTACHED TO THE PLAN REVIEW NOTES. |
| | 13-400.3.A, 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | THE 4X FEE ATTRIBUTED TO PLAN REVIEW IS NOT ASSESSED |
| | ONLY DUE TO THE FACT THE INPUT DATA REPORT WAS NOT |
| | SUBMITTED AND REVIEWED ON THE SECOND REVIEW. THE CODE |
| | SECTIONS FOR CODE COMPLIANCE REMAIN AND NOTICE IS BEING |
| | GIVEN THAT THE ENERGY CALCULATIONS ALONG WITH THE INPUT |
| | DATA REPORT MUST COMPLY WITH THE MINIMUM CODE. UPON THE |
| | NEXT REVIEW IF THE CALCULATIONS DO NOT MEET MINIMUM |
| | CODE AND DO NOT CORRELATE WITH PLANS A FEE OF $30,600 |
| | WILL BE STATUTORILY REQUIRED TO BE ASSESSED. |
| | ONE SET OF PLANS/LIGHTING AND ENERGY CALCULATIONS ARE |
| | BEING RETAINED BY THIS OFFICE AND WILL BE PLACED WITH |
| | PREVIOUS DOCUMENTS WHICH HAVE BEEN RETAINED. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |