Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop P
Sequence Number 2
Notes
Date Text
2008-03-15 14:16:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 NFPA-99C
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 1 OF 1 NOT SIGNED AND DATED AS REQUIRED IN
 SECTION 106.1 AS WELL AS THE FLORIDA ADMINISTRATIVE
 CODE AND THE FLORIDA STATUTES.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 3. SHT A2.1 THE SINKS IN THE BREAKROOM, (104), AND THE
 CCM/CONFERENCE ROOM, (118), SHALL BE ACCESSIBLE. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. FORWARD APPROACH REQUIRED AT SINKS,
 CABINET DOORS NOT ALLOWED. SHOW ELVATIONS FOR
 CABINETS.
 ****RESPONSE NOTED, BUT THE MINIMUM KNEE CLEARANCE
 REQUIRED IS 27". DETAIL 6 ON SHT A7.2 SHOWS THE
 CLEARANCE AT 26-1/2". PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.24.3.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT P2.1 DOMESTIC WATER RISER DIAGRAM. ALL WALL
 HYDRANTS & HOSE BIBBS REQUIRE A SHUT OFF VALVE ON THE
 WATER SUPPLY LINE PER SECTION 606.2(2). PLEASE SHOW ON
 THE RISER DIAGRAM.--A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE ICE MACHINE-1. SECTION 604.9.--ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR THE
 WATER HAMMER ARRESTORS TO BE NEAR THE FIXTURES AND NOT
 IN THE CEILING IS ILLUSTRATED WITH THE ATTACHED SHEET.
 THE WATER HAMMER ARRESTORS WILL NOT BE APPORVED IN THE
 CEILING. AS FOR THE REQUIREMENT FOR ACCESS PANELS, MOST
 WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS.
  
 12. OK
 13. OK (MED GAS PERMIT REQUIRED) (INFORMATIONAL)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved