Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop M
Sequence Number 2
Notes
Date Text
2008-03-16 14:41:22REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. WIND LOAD CALCULATIONS FOR ATTACHMENTS HAVE BEEN
 INCLUDED WITH THIS SUBMITTAL. THEY WILL BE REVIEWED BY
 THE BUILDING PLAN REVIEWER. INFORMATION REGARDING
 OUTDOOR EQUIPMENT AND WIND PRESSURES IS STILL PENDING.
 SHOULD SUBSEQUENT MECHANICAL REVIEW SHOW THIS TO BE THE
 ONLY OUTSTANDING ISSUE, A PROVISO WILL BE ISSUED,
 ALLOWING THIS INFORMATION TO BE PROVIDED PRIOR TO
 INSTALLATION AND INSPECTION OF EQUIPMENT. FBCM 301.13.
  
 2. OK
  
 3. OK
  
 4. THE INPUT DATA REPORT WAS NOT SUBMITTED WITH ENERGY
 CALCULATIONS. PLEASE CORRECT AND RESUBMIT. THE INPUT
 DATA REPORT IS A REQUIRED PART OF THE FLA/COM PROGRAM.
 FBCB 13-400.0.A.
  
 5. OK
  
 6. COOLING LOAD CALCULATIONS COULD NOT BE FOUND IN THIS
 SUBMITTAL. PLEASE CORRECT AND RESUBMIT. FBC
 13-407.1.ABC.1.
  