| Date |
Text |
| 2008-02-16 17:27:01 | 2008-02-16 17:27:01 |
| | |
| | ** DENIED 2NDREVIEW ** |
| | |
| | *** PLEASE SEE THAT THERE ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO BE |
| | AWARE THAT DUE TO INCOMPLETE DOCUMENTS SUBMITTED SOME |
| | ITEMS COULD NOT BE REVIEWED AT THIS TIME AND WILL BE |
| | NOTED BELOW. |
| | PLEASE ALSO KNOW AS SOME OTHER INFORMATION WAS STILL |
| | NOT YET SHOWN ON PLANS REVIEW FOR OTHER ITEMS WERE ALSO |
| | NOT ABLE TO BE REVIEWED AT THIS TIME. |
| | |
| | ** PLEASE KNOW THAT ANY INFORMATION WHICH WAS NOT |
| | SUBMITTED WHICH IS SUBMITTED ON THE FOLLOWING REVIEW |
| | MAY HAVE COMMENTS WHICH CAN NOT POSSIBLY BE MADE AT |
| | THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW. |
| | PLEASE SEE THE PLANS STILL NEED TO SHOW THE PROPOSED |
| | SYSTEM, SCHEDULING, ZONES, OVER RIDES ETC. |
| | THE PLANS DO NOT SHOW ANY SYSTEM AND RESPONSE MENTIONS |
| | TO SEE DIVISION SPECIFICATIONS. PLEASE NO DIVISION |
| | SPECIFICATIONS WERE SUBMITTED AND IN EITHER CASE THE |
| | PLANS ARE STILL REQUIRED TO SHOW ALL INFORMATION FOR |
| | MINIMUM CODE COMPLIANCE. |
| | PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH STANDARD |
| | TYPE DEVICES ARE STILL BEING SHOWN. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | ALL SEPARATE SPACES REQUIRE OVER RIDES OF ANY SYSTEM. |
| | IF THAT SEPARATE SPACE CONTAINS ITS OWN DEVICE FOR |
| | CONTROL THAT IS THE OTHER OPTION. IN ANY CASE THE |
| | LIGHTING IN BUILDING IS REQUIRED TO BE AUTOMATED. FOR |
| | EXAMPLE: STANDARD THREE-WAY SWITCHES IN 118, 114, 115. |
| | ETC |
| | PLEASE ALSO SEE 13-415.1.ABC.1.2 WHICH SPECIFICALLY |
| | REQUIRES OCCUPANCY SENSORS WHICH ARE REQUIRED TO |
| | CONTROL CONFERENCE ROOMS. THIS MUST BE AN OCCUPANT |
| | SENSOR TYPE DEVICE WHICH REQUIRES LIGHTING TO BE TURNED |
| | OFF WITHIN 30MINS OF AN OCCUPANT LEAVING THE SPACE. |
| | PLEASE SEE 13-415.1.ABC .1.4 FOR EXTERIOR LIGHTING. NO |
| | SURE HOW THIS IS MET. ARE ALL LIGHTS ON PHOTO-SENSORS? |
| | ONE OF TWO METHODS IS PERMITTED PER SECTION OF THE CODE |
| | GIVEN. |
| | IF ON ASTRONOMICAL TIME CLOCKS, PLEASE SEE REQUIRED |
| | BATTERY BACK UP OF 10HRS. |
| | AS THESE EXTERIOR LIGHTS ARE INDICATED ON THE SAME |
| | RELAY PANEL AS INTERIOR IT IS NOT CLEAR WHAT CONTROLS |
| | ARE PROVIDED TO MEET CODE. |
| | |
| | ** PLEASE ADJUST PLANS. |
| | |
| | 3) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE |
| | NOTES ON PLANS ACCORDINGLY. RESPONSE MENTIONS DIVISION |
| | SPECIFICATIONS HOWEVER THE CODE IS CLEAR WHICH STATES |
| | THESE TWO SECTIONS ARE TO BE STATED ON PLANS. |
| | THIS WAS CONFIRMED WITH THE FLORIDA BUILDING COMMISSION |
| | SOME TIME AGO. |
| | PLEASE ALSO BE AWARE THAT THE DIVISION SPECS ARE NOT |
| | REQUIRED AND ARE NOT ALWAYS PART OF THE DESIGN |
| | DOCUMENTS FOR RECORD WHICH ARE IN DESIGN FOR CODE |
| | COMPLIANCE WITH PLANS |
| | |
| | 4) NOTE:PLEASE SEE PREVIOUS NOTE # 5 |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT A |
| | VERSION ADOPTED BY FBC 13-400.3.A. |
| | PLEASE ALSO SEE THE ENERGY CALCULATIONS SUBMITTED ALSO |
| | DO NOT CONTAIN ANY INPUT DATA REPORTS WHICH ARE NOT |
| | ONLY REQUIRED AS SPECIFIED ON SHEET #2 OF COMPLIANCE |
| | SUMMARY BUT IS ALSO NEEDED IN ORDER TO PERFORM A |
| | REVIEW. |
| | PLEASE BE SURE WHEN RESUBMITTING PLANS FOR THE NEXT |
| | REVIEW THAT THE IDR COORDINATES WITH ALL LIGHTING ON |
| | PLANS. |
| | PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3. |
| | |
| | ** PLEASE SEE RESPONSE MENTIONS HEALTHCARE/CLINIC, |
| | HOWEVER THIS IS A BUSINESS OCCUPANCY. |
| | PLEASE SEE THE ADDRESS ON THE ENERGY CALCULATIONS NEEDS |
| | TO COORDINATE WITH PLANS AND OTHER SUPPORTING |
| | DOCUMENTS. SHOWS 1301 SUMMIT BLVD. |
| | PLEASE BE SURE THE OWNER AGENT HAS FILLED OUT |
| | CERTIFICATION SHEET AND SIGNED. |
| | PLEASE SEE 13-103.1.1.1. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #7 WITH RESPECT TO |
| | THE FACT THE MTS WAS AND IS SHOWN IN THE MAIN |
| | ELECTRICAL ROOM AND WE REQUESTED TO SEE HOW CABLES WERE |
| | GOING TO BE CONNECTED TO EQUIPMENT WITHOUT PASSING |
| | THROUGH DOOR IN MAIN ELECTRICAL ROOM. |
| | THE RESPONSE LETTER SPECIFICALLY STATES THE CONNECTION |
| | ARE OUTSIDE AND TO SEE E0.2. SHEET E0.2 IS THE |
| | ELECTRICAL RISER AND LOCATION OF THIS EQUIPMENT IS NOT |
| | SHOWN ON PLANS. PLEASE SEE E1.1 WHICH DOES NOT INDICATE |
| | THE LOCATION. PLEASE SHOW ON PLANS. |
| | |
| | 6) NOTE: PLEASE INDICATE HOW EGRESS LIGHTING WILL BE |
| | CONTROLLED IF THE LIGHTING CONTROL SYSTEM IN COMMON |
| | AREAS WITH REQUIRED EGRESS PATHS SWEEPS AND SHUTS OFF |
| | LIGHTING. PLEASE SEE FBC 1006.1.2 AND NFPA-101 |
| | 7.8.1.2.2 WHICH INDICATES AN OCCUPANCY SENSOR TYPE |
| | DEVICES FOR REQUIRED EGRESS LIGHTING SHALLBE 15MINS |
| | MINIMUM TIME AND SHALL BE FAIL SAFE ON. |
| | SOME LOCATIONS SHOW OVER RIDERS ALTHOUGH ONLY STANDARD |
| | SWITCHES AS NOTED ABOVE IN NOTED #1 AND MOST AREAS DO |
| | NOT SHOW ANY. |
| | |
| | 7 NOTE:THIS NOTE REMAINS AS LIGHTNING SHEETS ARE |
| | STILL BEING SUBMITTED. |
| | PLEASE KNOW THE LIGHTNING PROTECTION SYSTEM AS SHOWN |
| | WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT. |
| | |
| | 8) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B)WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS GIVEN |
| | AT THIS TIME. THIS IS ONLY A NOTICE. |
| | PLEASE BE AWARE THAT THIS IS ONLY A NOTICE GIVEN AT |
| | THIS TIME. |
| | PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND SUBMITTED |
| | ENERGY CALCULATIONS WILL BE RETAINED BY THIS OFFICE. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |