| Date |
Text |
| 2008-03-20 17:34:39 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1A. WHEN RESUBMITTING, PLEASE INDICATE THE REVISIONS |
| | AND REMOVE AND REPLACE SHEETS WHICH HAVE CHANGED.ALL |
| | CHANGES TO BE CLOUDED AND INDICATED WITH A REVISION |
| | NUMBER.PLEASE INCLUDE A RESPONSE LETTER STATING HOW |
| | EACH ITEM WAS ADDRESSED. |
| | |
| | 1B. ONE OF THE SETS IS MISSING THE ELECTRIC SHEETS. |
| | |
| | 1C-1E, INFORMATIONAL. |
| | |
| | 2.INFORMATIONAL; A FORM BOARD ELEVATION CERTIFICATE |
| | REQUIRED BEFORE CONCRETE POUR, ELEVATION CERTIFICATE |
| | REQUIRED FOR CO DUE TO LOCATION IN FLOOD ZONE A. |
| | |
| | 3-5. INFORMATIONAL OR COMMENT ADDRESSED. |
| | |
| | 6. SEE PREVIOUS LIST REGARDING COMPLIANCE WITH |
| | FBC435.5.THE RESPONSE LETTER STATES THAT SPECS ARE |
| | ATTACHED, NONE FOUND. |
| | |
| | 7.THE SKETCH PREPARED BY TLC FOR THE SCUPPERS ARE TO |
| | BE SIGNED, SEALED, AND DATED FS471. THE CALCS SHOULD |
| | INCLUDE TITLE BLOCK INFORMATION FAC61G15-23.002 AND |
| | SHOULD BE SIGNED, SEALED, AND DATED. |
| | |
| | 8.THE RESPONSE LETTER STATES THAT THE ROOF HATCH |
| | PRODUCT APPROVAL IS ATTACHED; NOT FOUND.THIS CAN BE A |
| | PROVISO ITEM. |
| | |
| | 9.ROOF A/C CURB INFORMATION WAS PROVIDED BUT NOTE THE |
| | FOLLOWING: |
| | |
| | A. EACH SHEET TO INCLUDE ALL INFORMATION REQUIRED BY |
| | FAC61G15-23.002. |
| | |
| | B. DESIGN TO BE IN ACCORDANCE WITH ASCE7-02, NOT 7-05, |
| | FBC 35. |
| | |
| | C.FAC61G15-23 REQUIRES THAT EITHER EACH SHEET BE |
| | SIGNED, SEALED, AND DATED WITH ALL REQUIRED INFORMATION |
| | (SEE 9A) OR AN INDEX SHEET USED. |
| | |
| | 10-12. ADDRESSED. |
| | |
| | 13.SHOP DRAWINGS FOR THE FIBERGLASS CORNICE MOLDING |
| | WILL BE REQUIRED. |
| | |
| | 14-17. ADDRESSED. |
| | |
| | 18. SEE PREVIOUS LIST REGARDING USE OF COMBUSTIBLE |
| | MATERIALS OVER THE EXIT, TYPE II BUILDING.THE |
| | ARCHITECT REMOVED LAM BEAMS, BUT FRP AND WATERPROOF |
| | FABRIC ARE STILL SHOWN.PLEASE ADDRESS. |
| | |
| | 19. ADDRESSED. |
| | |
| | 20. SEE PREVIOUS LIST.MAIN FRAMING MEMBERS TO RESIST |
| | LOADS FBC1609.6.1.IT IS NOT CLEAR HOW THIS WAS |
| | ADDRESSED, NO STRAPS ADDED. |
| | |
| | 21-22. ADDRESSED. |
| | |
| | 23. PRODUCT APPROVALS, PLEASE NOTE THE FOLLOWING: |
| | |
| | A. THE CUSTOM GLASS COMPANY DOOR PRODUCT APPROVAL IS |
| | MISSING THE DRAWINGS SHEETS 1 THROUGH 12; NOA |
| | INCOMPLETE. |
| | |
| | B.ROOF, SIPLAST NOA 03-1211.06, ENHANCED FASTENING |
| | NOT PROVIDED FOR ZONES 2 AND 3.THIS MAY BE PROVIDED |
| | AT THE TIME OF ROOF PERMIT APPLICATION BY THE ROOFING |
| | CONTRACTOR. |
| | |
| | 24.SEE PREVIOUS LIST REGARDING FLORIDA STATE PRODUCT |
| | APPROVAL, REQUIRED FOR ALL PRODUCTS REGULATED BY |
| | FAC9B72.THIS IS REQUIRED IN ADDITION TO THE NOAS. |
| | PLEASE PRINT FOR EACH PRODUCT, IF AVAILABLE, |
| | WWW.FLORIDABUILDING.ORG.IF NOT AVAILABLE, PLEASE |
| | ADVISE AND A LOCAL PRODUCT APPROVAL WILL BE ISSUED. |
| | |
| | 25.ADDRESSED. |
| | |
| | 26.RESPONSE NOTED; SEPARATE PERMITS WILL BE REQUIRED |
| | FOR THE CANOPIES. |
| | |
| | 27.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| | PERMIT APPLICATION. |
| | |
| | NEW COMMENT: |
| | |
| | 28.PLEASE HAVE ENGINEER CLARIFY ZONE 3 ROOF PRESSURE |
| | ON SHEET S1.0.IT APPEARS THAT ZONE 2 PRESSURES WERE |
| | SPECIFIED FOR ZONE 3, BUT A 3FT CONTINUOUS PARAPET WALL |
| | IS REQUIRED ASCE7-02.ON THE WALL SECTIONS, THE |
| | PARAPET WALL DOES NOT APPEAR TO BE 3FT.PLEASE EITHER |
| | REVISE PRESSURES OR PROVIDE CALCULATIONS. |
| | |