Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop B
Sequence Number 2
Notes
Date Text
2008-03-20 17:34:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1A. WHEN RESUBMITTING, PLEASE INDICATE THE REVISIONS
 AND REMOVE AND REPLACE SHEETS WHICH HAVE CHANGED.ALL
 CHANGES TO BE CLOUDED AND INDICATED WITH A REVISION
 NUMBER.PLEASE INCLUDE A RESPONSE LETTER STATING HOW
 EACH ITEM WAS ADDRESSED.
  
 1B. ONE OF THE SETS IS MISSING THE ELECTRIC SHEETS.
  
 1C-1E, INFORMATIONAL.
  
 2.INFORMATIONAL; A FORM BOARD ELEVATION CERTIFICATE
 REQUIRED BEFORE CONCRETE POUR, ELEVATION CERTIFICATE
 REQUIRED FOR CO DUE TO LOCATION IN FLOOD ZONE A.
  
 3-5. INFORMATIONAL OR COMMENT ADDRESSED.
  
 6. SEE PREVIOUS LIST REGARDING COMPLIANCE WITH
 FBC435.5.THE RESPONSE LETTER STATES THAT SPECS ARE
 ATTACHED, NONE FOUND.
  
 7.THE SKETCH PREPARED BY TLC FOR THE SCUPPERS ARE TO
 BE SIGNED, SEALED, AND DATED FS471. THE CALCS SHOULD
 INCLUDE TITLE BLOCK INFORMATION FAC61G15-23.002 AND
 SHOULD BE SIGNED, SEALED, AND DATED.
  
 8.THE RESPONSE LETTER STATES THAT THE ROOF HATCH
 PRODUCT APPROVAL IS ATTACHED; NOT FOUND.THIS CAN BE A
 PROVISO ITEM.
  
 9.ROOF A/C CURB INFORMATION WAS PROVIDED BUT NOTE THE
 FOLLOWING:
  
 A. EACH SHEET TO INCLUDE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002.
  
 B. DESIGN TO BE IN ACCORDANCE WITH ASCE7-02, NOT 7-05,
 FBC 35.
  
 C.FAC61G15-23 REQUIRES THAT EITHER EACH SHEET BE
 SIGNED, SEALED, AND DATED WITH ALL REQUIRED INFORMATION
 (SEE 9A) OR AN INDEX SHEET USED.
  
 10-12. ADDRESSED.
  
 13.SHOP DRAWINGS FOR THE FIBERGLASS CORNICE MOLDING
 WILL BE REQUIRED.
  
 14-17. ADDRESSED.
  
 18. SEE PREVIOUS LIST REGARDING USE OF COMBUSTIBLE
 MATERIALS OVER THE EXIT, TYPE II BUILDING.THE
 ARCHITECT REMOVED LAM BEAMS, BUT FRP AND WATERPROOF
 FABRIC ARE STILL SHOWN.PLEASE ADDRESS.
  
 19. ADDRESSED.
  
 20. SEE PREVIOUS LIST.MAIN FRAMING MEMBERS TO RESIST
 LOADS FBC1609.6.1.IT IS NOT CLEAR HOW THIS WAS
 ADDRESSED, NO STRAPS ADDED.
  
 21-22. ADDRESSED.
  
 23. PRODUCT APPROVALS, PLEASE NOTE THE FOLLOWING:
  
 A. THE CUSTOM GLASS COMPANY DOOR PRODUCT APPROVAL IS
 MISSING THE DRAWINGS SHEETS 1 THROUGH 12; NOA
 INCOMPLETE.
  
 B.ROOF, SIPLAST NOA 03-1211.06, ENHANCED FASTENING
 NOT PROVIDED FOR ZONES 2 AND 3.THIS MAY BE PROVIDED
 AT THE TIME OF ROOF PERMIT APPLICATION BY THE ROOFING
 CONTRACTOR.
  
 24.SEE PREVIOUS LIST REGARDING FLORIDA STATE PRODUCT
 APPROVAL, REQUIRED FOR ALL PRODUCTS REGULATED BY
 FAC9B72.THIS IS REQUIRED IN ADDITION TO THE NOAS.
 PLEASE PRINT FOR EACH PRODUCT, IF AVAILABLE,
 WWW.FLORIDABUILDING.ORG.IF NOT AVAILABLE, PLEASE
 ADVISE AND A LOCAL PRODUCT APPROVAL WILL BE ISSUED.
  
 25.ADDRESSED.
  
 26.RESPONSE NOTED; SEPARATE PERMITS WILL BE REQUIRED
 FOR THE CANOPIES.
  
 27.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 NEW COMMENT:
  
 28.PLEASE HAVE ENGINEER CLARIFY ZONE 3 ROOF PRESSURE
 ON SHEET S1.0.IT APPEARS THAT ZONE 2 PRESSURES WERE
 SPECIFIED FOR ZONE 3, BUT A 3FT CONTINUOUS PARAPET WALL
 IS REQUIRED ASCE7-02.ON THE WALL SECTIONS, THE
 PARAPET WALL DOES NOT APPEAR TO BE 3FT.PLEASE EITHER
 REVISE PRESSURES OR PROVIDE CALCULATIONS.
  