Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop B
Sequence Number 15
Notes
Date Text
2009-02-25 17:04:16****CORRECTIONS****
 ***CANVAS AWNING CALCULATIONS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. SCOPE OF WORK ISN'T CLEAR. THIS WAS SUBMITTED AS A
 "SUBMITTAL", AND DESCRIPTION STATES "ALUMINUM CORNICE."
 THE ENGINEERING IS ENTITLED "STRUCTURAL CALCULATIONS
 FOR CANVAS AWNING." NO CANVAS IS SHOWN ON THE DRAWINGS.
 THE CALCULATIONS GIVE DESIGN CRITERIA AS 90MPH,
 FBC3105.4.2.1, CODE SECTION FOR REMOVABLE FABRIC. IF
 THIS IS AN AWNING WITH REMOVABLE FABRIC, SEPARATE
 PERMIT REQUIRED AS WELL AS THE FOLLOWING:
  
 A. FRAME TO BE DESIGNED TO WITHSTAND 140MPH FBC3105
 B. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 C. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 IF THIS IS NOT REMOVABLE FABRIC, PROVIDE CODE
 REFERENCES WHICH ALLOW DESIGN TO 90MPH IN A 140MPH WIND
 ZONE.
  
  
  
  