| 2009-02-25 17:04:16 | ****CORRECTIONS**** |
| | ***CANVAS AWNING CALCULATIONS*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | |
| | 1. SCOPE OF WORK ISN'T CLEAR. THIS WAS SUBMITTED AS A |
| | "SUBMITTAL", AND DESCRIPTION STATES "ALUMINUM CORNICE." |
| | THE ENGINEERING IS ENTITLED "STRUCTURAL CALCULATIONS |
| | FOR CANVAS AWNING." NO CANVAS IS SHOWN ON THE DRAWINGS. |
| | THE CALCULATIONS GIVE DESIGN CRITERIA AS 90MPH, |
| | FBC3105.4.2.1, CODE SECTION FOR REMOVABLE FABRIC. IF |
| | THIS IS AN AWNING WITH REMOVABLE FABRIC, SEPARATE |
| | PERMIT REQUIRED AS WELL AS THE FOLLOWING: |
| | |
| | A. FRAME TO BE DESIGNED TO WITHSTAND 140MPH FBC3105 |
| | B. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW |
| | COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE |
| | INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. |
| | THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | C. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT |
| | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER |
| | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO |
| | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT |
| | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE |
| | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT |
| | BE NOTARIZED. |
| | |
| | IF THIS IS NOT REMOVABLE FABRIC, PROVIDE CODE |
| | REFERENCES WHICH ALLOW DESIGN TO 90MPH IN A 140MPH WIND |
| | ZONE. |
| | |
| | |
| | |
| | |