Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop P
Sequence Number 13
Notes
Date Text
2009-02-13 18:37:38DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. SHT P-2.1 THE LATEST SHEET P-2.1 SIGNED, SEALED AND
 DATED 3-31-08 SHOWS REVISIONS 1, (2/08/08) & 2,
 (3/31/08). THE REVISION FOR SHEET SUBMITTED FOR REVIEW
 DELETED REVISION 1 FROM THE REVISION INDEX. THE
 REVISION INDEX SHALL REMAIN THROUGH THE HISTORY OF THE
 JOB AND REVISION NUMBERS SHALL NOT BE DELETED. ALSO
 REVISIONS 5, 6, 7, 8, 9, 10 & 11 ARE INDICATED ON THE
 REVISION INDEX. THE ONLY REVISION CLOUDED AND NUMBERED
 IS REVISION 11. THERE ARE REVISIONS ON THE SHEET THAT
 ARE NOT CLOUDED, NOR DO THEY HAVE A REVISION NUMBER.
 PLEASE CLOUD ALL REVISIONS FROM SHEET SIGNED, SEALED
 AND DATED 3-31-08 AND INDICATE THE REVISION WITH THE
 CORRESPONDING REVISION NUMBER 5 THRU 11 FROM THE
 REVISION INDEX. SECTION 106.1.3. (ADMINISTRATION).
  
 2. SHT P2.1 THE PIPING INDICATED AS CAPPED OFF IN THE
 FREEZER STILL APPEARS TO HAVE A FLOOR DRAIN AND A HUB
 DRAIN. PER SECTION 704.5 DEAD ENDS ARE PROHIBITED.
 PLEASE INDICATE WHERE THE PIPING IS CAPPED AND SHOW
 CAPS ON RISER DIAGRAM. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  