Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop P
Sequence Number 11
Notes
Date Text
2008-12-22 15:00:08REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P1.2 & P2.1. THE SANITARY TO THE FREEZER IS NOT
 APPROVED. FLOOR DRAINS WITHIN WALK IN REFRIGERATORS OR
 FREEZERS SHALL BE INDIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM BY MEANS OF AN AIR GAP. WHERE A FLOOR
 DRAIN IS LOCATED WITHIN AN AREA SUBJECT TO FREEZING,
 THE WASTE LINE SERVING THE FLOOR DRAIN SHALL NOT BE
 TREPPED AND SHALL INDIRECTLY DISCHARGE INTO A WASTE
 RECPTOR LOCATED OUTSIDE OF THE AREA SUBJECT TO
 FREEZING. *EXCEPTION: WHERE PROTECTED AGAINST BACKFLOW
 BY A BACK WATER VALVE, SUCH FLOOR DRAINS SHALL BE
 INDIIIRECTLY CONNECTED TO THE SANITARY DRAINAGE SYSTEM
 BY MEANS OF AN AIR BREAK OR AN AIR GAP. (SEE ATTACHED
 SHEET). SECTION 802.1.2. -- INFORMATIONAL: PIPING FROM
 THE FREEZER SHALL DISCHARGE DOWNSTREAM OF THE RUNNING
 TRAP. SECTION 1002.1.
  
 2. SHTS P1.2 & P2.1. TWO NEW HUB DRAINS ARE INDICATED
 BY STORAGE ROOM 137. PLEASE INDICATE WHAT WILL BE
 DRAINING INTO THE HUB DRAINS. ALSO PLANS STATE "SEE
 CIVIL DWGS FOR CONTINUATION". CIVIL PLANS SHOW
 CONTINUATION. PLEASE CLARIFY. (SEE CIVIL SHEET 4).
 SECTION 106.1.1 & SECTION 1003.
  
 3. SHT P1.2 CLOUD REVISION SHOWING KEY NOTE 1 AND VTR.
 ONLY NOTE 3/4" VTR CLOUDED. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  