| Plan Review Notes For Permit 07120513 |
| Permit Number |
07120513 |
|
| Review Stop |
B |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2008-10-29 17:43:30 | ****CORRECTIONS**** | | | EXTERIOR FRAMING W/CALCS | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | EXTERIOR FRAMING CALCS: | | | | | | 1. THE PLANS ARE TO BE SIGNED, SELED AND DATED | | | FAC61G15-23.002. SOME SHEETS ARE LACKING THE DATE. | | | | | | 2. SS-5, IMPORTANCE FACTOR OF 1 REQUIRED, FBC TABLE | | | 1604.5. AN IMPORTANCE FACTOR OF "0.77 OR 1.00 | | | (DEPENDENT ON ELEMENT OF DESIGN)" WAS DECLARED ON SHEET | | | SS-5, AND .77 USED IN THE CALCULATIONS. PLEASE REVISE. | | | | | | 3. THIS IS A TYPE IIB BUILDING, NON COMBUSTIBLE. A NOTE | | | WAS PLACED ON THE PLAN THAT THE PLYWOOD IS TO BE | | | FIRE-RATED IN ACCORDANCE WITH BUILDING TYPE. THIS IS A | | | NON-COMBUSTIBLE BUILDING; ALL SPECIFICATIONS ARE TO BE | | | INCLUDED IN THIS REVISION AND ANY EXCEPTIONS TO THE | | | NON-COMBUSTIBLE REQUIREMENT ARE TO BE NOTED ON THE | | | PLAN. | | | | | | 4. ALL INFORMATION REQUIED BY FAC61G15-23.002 IS TO BE | | | INCLUDED ON EACH SHEET OF THE PLAN (PRINTED NAME AND | | | LICENSE NUMBER OF THE PERSON SEALING THE DOCUMENT, | | | CERTIFICATE OF AUTHORIZATION NUMBER). | | | | | | |
|