2008-10-29 17:43:30****CORRECTIONS****
 EXTERIOR FRAMING W/CALCS
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 EXTERIOR FRAMING CALCS:
  
 1. THE PLANS ARE TO BE SIGNED, SELED AND DATED
 FAC61G15-23.002. SOME SHEETS ARE LACKING THE DATE.
  
 2. SS-5, IMPORTANCE FACTOR OF 1 REQUIRED, FBC TABLE
 1604.5. AN IMPORTANCE FACTOR OF "0.77 OR 1.00
 (DEPENDENT ON ELEMENT OF DESIGN)" WAS DECLARED ON SHEET
 SS-5, AND .77 USED IN THE CALCULATIONS. PLEASE REVISE.
  
 3. THIS IS A TYPE IIB BUILDING, NON COMBUSTIBLE. A NOTE
 WAS PLACED ON THE PLAN THAT THE PLYWOOD IS TO BE
 FIRE-RATED IN ACCORDANCE WITH BUILDING TYPE. THIS IS A
 NON-COMBUSTIBLE BUILDING; ALL SPECIFICATIONS ARE TO BE
 INCLUDED IN THIS REVISION AND ANY EXCEPTIONS TO THE
 NON-COMBUSTIBLE REQUIREMENT ARE TO BE NOTED ON THE
 PLAN.
  
 4. ALL INFORMATION REQUIED BY FAC61G15-23.002 IS TO BE
 INCLUDED ON EACH SHEET OF THE PLAN (PRINTED NAME AND
 LICENSE NUMBER OF THE PERSON SEALING THE DOCUMENT,
 CERTIFICATE OF AUTHORIZATION NUMBER).
  
  