2008-10-10 15:38:48****CORRECTIONS****
 ****MECHANICAL EQUIPMENT****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. A SEAL ACCEPTABLE TO THE BOARD IS TO BE USED,
 FAC61G15-23.001.
  
 2. ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO BE
 INCLUDED (CERTIFICATE OF AUTHORIZATION).
  
 3. SHOP DRAWING REVIEW REQUIRED BY STRUCTURAL ENGINEER,
 FAC61G31.
  
 4. SEE SHEET S1; STRUCTURAL ENGINEER HAS DECLARED THIS
 JOB AS EXPOSURE C AND SPECIFIED DESIGN CRITERIA AS
 SUCH. PLEASE REVISE.
  
 5. C&C PRESSURES FOR ZONE 5 WALL AND ZONE 1 ROOF WERE
 USED. PLEASE EXPLAIN WHY THIS WOULD BE ZONE 1;
 SHOULDN'T THIS STRUCTURE BE ANALYZED AS A BUILDING,
 WHICH WOULD INCLUDE BOTH ZONES 2 AND 3 FOR THE ROOF?
 NORMALLY EACH ROOF SECTION AT DIFFERENT ELEVATIONS
 WOULD BE TREATED AS INDIVIDUAL ROOFS; PLEASE EXPLAIN
 REASONING AS IT APPEARS THAT THIS STRUCTURE IS BEING
 TREATED AS A PART OF THE ROOF ALTHOUGH IT IS HIGHER
 THAN THE ROOF OF THE BUILDING. THE STRUCTURAL ENGINEER
 HAS SPECIFIED BUILDING DESIGN PRESSURES OF -42.7,
 -71.7, AND -107.7 FOR C&C ZONES 1,2,3 RESPECTIVELY. THE
 ROOF OF THE MECHANICAL EQUIPMENT WAS ANALYZED FOR A
 ROOF NEGATIVE PRESSURE OF -35.3. PLEASE FEEL FREE TO
 CONTACT ME.
  
 6. NUMBER OF SCREWS ANALYZED WITH NO INFORMATION
 REGARDING THE STRUCTURE, HINGES, DOOR LATCH, RAIN HOOD,
 ETC. PLEASE PROVIDE AN ANALYSIS OF THE COMPONENTS OF
 THE STRUCTURE; ONLY SCREWS PROVIDED. FBC M 301.13, FBC
 1609.
  
  
  
  