| Date |
Text |
| 2008-01-23 15:42:21 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | NFPA-99C |
| | |
| | 1. SHT A1.0 MINIMUM PLUMBING FACILITIES REQUIRE 4 WATER |
| | CLOSETS, 3 LAVS AND 2 DRINKING FOUNTAINS PER TABLE |
| | 403.1. PLEASE CORRECT REQUIRED AMOUNTS AS WELL AS THE |
| | PROVIDED AMOUNT FOR THE DRINKING FOUNTAIN IN TABLE |
| | SUBMITTED. |
| | |
| | 2. SHT 1 OF 1 NOT SIGNED AND DATED AS REQUIRED IN |
| | SECTION 106.1 AS WELL AS THE FLORIDA ADMINISTRATIVE |
| | CODE AND THE FLORIDA STATUTES. |
| | |
| | 3. SHT A2.1 THE SINKS IN THE BREAKROOM, (104), AND THE |
| | CCM/CONFERENCE ROOM, (118), SHALL BE ACCESSIBLE. SUBMIT |
| | A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND |
| | ALL SUBSECTIONS. FORWARD APPROACH REQUIRED AT SINKS, |
| | CABINET DOORS NOT ALLOWED. SHOW ELVATIONS FOR |
| | CABINETS. |
| | |
| | 4. SHT A7.2 DETAIL 1 SHOW THE CLEAR FLOOR SPACE FOR THE |
| | W/C'S PER 11-4.16.2, THE LAVS PER 11-4.19.3 IN TOILET |
| | ROOM 111 AND THE BATHROOMS IN ROOMS 121 & 124. |
| | |
| | 5. SHT A7.2 DETAIL 2 SHOW THE CLEAR FLOOR SPACE FOR THE |
| | BREAKROOM SINK, (104), PER SECTION 11-4.24.5. |
| | |
| | 6. SHT A7.2 DETAIL 3(B), DETAIL 4(D) AND DETAIL 5(A) |
| | THE WATER CLOSET SHALL BE 1'6" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE. (SEE FIG 28 IN CHAPTER 11). |
| | |
| | 7. SHT A7.2 DETAILS 1 & 2 THE SHOWER STALL SIZE SHALL |
| | COMPLY WITH SECTION 11-4.21.2 & FIGURES 35A OR 35B. |
| | PLEASE SHOW COMPLIANCE. |
| | |
| | 8. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING FOUNTAIN |
| | PER SECTION 11-4.15 AND ALL SUBSECTIONS. |
| | |
| | 9. SHT P0.2 THE SINKS IN S-1 AND S-3 ARE NOT APPROVED |
| | PER SECTION 11-4.24.4, (SINK DEPTH). MAX 6-1/2" PLEASE |
| | SUBMIT SINKS THAT COMPLY WITH DEPTH REQUIREMENT. |
| | |
| | 10. SHT P2.1 SANITARY RISER DIAGRAM, THE WASH MACHINE |
| | STACK REQUIRES A TRAP, A STANDPIPE AND A CLEANOUT. THE |
| | CLEANOUT SHALL BE LOCATED 4' ABOVE THE FLOOR. SECTIONS |
| | 802.4, 1002.1 & 708.9. |
| | |
| | 11. SHT P2.1 DOMESTIC WATER RISER DIAGRAM. ALL WALL |
| | HYDRANTS & HOSE BIBBS REQUIRE A SHUT OFF VALVE ON THE |
| | WATER SUPPLY LINE PER SECTION 606.2(2). PLEASE SHOW ON |
| | THE RISER DIAGRAM.--A WATER HAMMER ARRESTOR IS |
| | REQUIRED ON THE ICE MACHINE-1. SECTION 604.9.--ALL |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 12 SHT P3.1 WATER HEATER DETAIL. THE FLOOR DRAIN IS NOT |
| | AN APPROVED INDIRECT WASTE RECEPTOR. A FLOOR SINK OR |
| | HUB DRAIN IS REQUIRED PER SECTIONS 802.3 & 802.3.2. |
| | |
| | 13. A SEPARATE MED-GAS PERMIT IS REQUIRED. |
| | CERTIFICATIONS ARE REQUIRED AT THE TIME OF APPLICATION |
| | FOR THE CONTRACTOR, THE INSTALLER AND THE BRAZER PER |
| | NFPA-99C. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |