Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop P
Sequence Number 1
Notes
Date Text
2008-01-23 15:42:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 NFPA-99C
  
 1. SHT A1.0 MINIMUM PLUMBING FACILITIES REQUIRE 4 WATER
 CLOSETS, 3 LAVS AND 2 DRINKING FOUNTAINS PER TABLE
 403.1. PLEASE CORRECT REQUIRED AMOUNTS AS WELL AS THE
 PROVIDED AMOUNT FOR THE DRINKING FOUNTAIN IN TABLE
 SUBMITTED.
  
 2. SHT 1 OF 1 NOT SIGNED AND DATED AS REQUIRED IN
 SECTION 106.1 AS WELL AS THE FLORIDA ADMINISTRATIVE
 CODE AND THE FLORIDA STATUTES.
  
 3. SHT A2.1 THE SINKS IN THE BREAKROOM, (104), AND THE
 CCM/CONFERENCE ROOM, (118), SHALL BE ACCESSIBLE. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. FORWARD APPROACH REQUIRED AT SINKS,
 CABINET DOORS NOT ALLOWED. SHOW ELVATIONS FOR
 CABINETS.
  
 4. SHT A7.2 DETAIL 1 SHOW THE CLEAR FLOOR SPACE FOR THE
 W/C'S PER 11-4.16.2, THE LAVS PER 11-4.19.3 IN TOILET
 ROOM 111 AND THE BATHROOMS IN ROOMS 121 & 124.
  
 5. SHT A7.2 DETAIL 2 SHOW THE CLEAR FLOOR SPACE FOR THE
 BREAKROOM SINK, (104), PER SECTION 11-4.24.5.
  
 6. SHT A7.2 DETAIL 3(B), DETAIL 4(D) AND DETAIL 5(A)
 THE WATER CLOSET SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. (SEE FIG 28 IN CHAPTER 11).
  
 7. SHT A7.2 DETAILS 1 & 2 THE SHOWER STALL SIZE SHALL
 COMPLY WITH SECTION 11-4.21.2 & FIGURES 35A OR 35B.
 PLEASE SHOW COMPLIANCE.
  
 8. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING FOUNTAIN
 PER SECTION 11-4.15 AND ALL SUBSECTIONS.
  
 9. SHT P0.2 THE SINKS IN S-1 AND S-3 ARE NOT APPROVED
 PER SECTION 11-4.24.4, (SINK DEPTH). MAX 6-1/2" PLEASE
 SUBMIT SINKS THAT COMPLY WITH DEPTH REQUIREMENT.
  
 10. SHT P2.1 SANITARY RISER DIAGRAM, THE WASH MACHINE
 STACK REQUIRES A TRAP, A STANDPIPE AND A CLEANOUT. THE
 CLEANOUT SHALL BE LOCATED 4' ABOVE THE FLOOR. SECTIONS
 802.4, 1002.1 & 708.9.
  
 11. SHT P2.1 DOMESTIC WATER RISER DIAGRAM. ALL WALL
 HYDRANTS & HOSE BIBBS REQUIRE A SHUT OFF VALVE ON THE
 WATER SUPPLY LINE PER SECTION 606.2(2). PLEASE SHOW ON
 THE RISER DIAGRAM.--A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE ICE MACHINE-1. SECTION 604.9.--ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 12 SHT P3.1 WATER HEATER DETAIL. THE FLOOR DRAIN IS NOT
 AN APPROVED INDIRECT WASTE RECEPTOR. A FLOOR SINK OR
 HUB DRAIN IS REQUIRED PER SECTIONS 802.3 & 802.3.2.
  
 13. A SEPARATE MED-GAS PERMIT IS REQUIRED.
 CERTIFICATIONS ARE REQUIRED AT THE TIME OF APPLICATION
 FOR THE CONTRACTOR, THE INSTALLER AND THE BRAZER PER
 NFPA-99C.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved