2008-01-25 13:45:37***DENIED***
  
 1) NFPA 1, 2003 EDITION SHALL BE REFERENCED. SHT A1.0
  
 2) FIRE EXTINGUISHERS SHALL BE LOCATED AT CLEAR AND
 OBVIOUS LOCATIONS, NOT TO EXCEED 75' TRAVEL DISTANCE.
  
 3) IN ADDITION TO FIRE SPRINKLER, SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM SYSTEM.
  
 4) FIRE ALARM TO BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE. CERTIFICATE WILL BE REQUIRED BY THE FINAL
 INSPECTION.
  
 5) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 6) PLANS MENTION A NEW 3" UNDERGROUND FIRE MAIN, BUT
 ILLUSTRATE A 4" LINE. PLEASE CLARIFY. SHT FP1.1
  
 7) KNOX LOCKING CAPS ARE REQUIRED FOR FIRE DEPARTMENT
 CONNECTION.
  
 8) NEW GATE INSTALLATION SHALL BE PROVIDED WITH KNOX
 KEY SWITCH ENTRY SYSTEM FOR AFTER NORMAL BUSINESS
 HOURS. IN ADDITION, A KNOX BOX SHALL BE PROVIDED ON THE
 BUILDING CLOSE TO THE FRONT ENTRANCE.
  
 9) PLANS SHOW NO ACTUAL BUILDING ADDRESS IN TITLE BLOCK
 OF EACH SHEET. BUILDING ADDRESS TO BE MINIMUM OF 6" IN
 HEIGHT AND 1" IN WIDTH CONTRASTING WITH BACKGROUND.
  
 10) DUCT SMOKE DETECTORS IN ACCORDANCE WITH LOCAL
 REQUIREMENTS SHALL INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED.
  
 11) WHEN SUBMITTING PLANS FOR FIRE SPRINKLER WORK,
 PLEASE ADD THE WORD SAFETY MARGIN WHICH SHALL BE A
 MINIMUM OF 5 PSI.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756