| 2008-01-25 13:45:37 | ***DENIED*** |
| | |
| | 1) NFPA 1, 2003 EDITION SHALL BE REFERENCED. SHT A1.0 |
| | |
| | 2) FIRE EXTINGUISHERS SHALL BE LOCATED AT CLEAR AND |
| | OBVIOUS LOCATIONS, NOT TO EXCEED 75' TRAVEL DISTANCE. |
| | |
| | 3) IN ADDITION TO FIRE SPRINKLER, SEPARATE SHOP |
| | DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM SYSTEM. |
| | |
| | 4) FIRE ALARM TO BE UL CERTIFIED FOR CENTRAL STATION |
| | SERVICE. CERTIFICATE WILL BE REQUIRED BY THE FINAL |
| | INSPECTION. |
| | |
| | 5) PLEASE PROVIDE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING. |
| | |
| | 6) PLANS MENTION A NEW 3" UNDERGROUND FIRE MAIN, BUT |
| | ILLUSTRATE A 4" LINE. PLEASE CLARIFY. SHT FP1.1 |
| | |
| | 7) KNOX LOCKING CAPS ARE REQUIRED FOR FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | 8) NEW GATE INSTALLATION SHALL BE PROVIDED WITH KNOX |
| | KEY SWITCH ENTRY SYSTEM FOR AFTER NORMAL BUSINESS |
| | HOURS. IN ADDITION, A KNOX BOX SHALL BE PROVIDED ON THE |
| | BUILDING CLOSE TO THE FRONT ENTRANCE. |
| | |
| | 9) PLANS SHOW NO ACTUAL BUILDING ADDRESS IN TITLE BLOCK |
| | OF EACH SHEET. BUILDING ADDRESS TO BE MINIMUM OF 6" IN |
| | HEIGHT AND 1" IN WIDTH CONTRASTING WITH BACKGROUND. |
| | |
| | 10) DUCT SMOKE DETECTORS IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS SHALL INITIATE A GENERAL FIRE ALARM WHEN |
| | ACTIVATED. |
| | |
| | 11) WHEN SUBMITTING PLANS FOR FIRE SPRINKLER WORK, |
| | PLEASE ADD THE WORD SAFETY MARGIN WHICH SHALL BE A |
| | MINIMUM OF 5 PSI. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |