Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-25 14:19:362007-12-25 14:19:36
  
 ** DENIEDREVIEW **
  
 ** PLEASE KNOW THE ADDRESS MAY BE NEEDED TO BE
 ADDRESSED AS THIS IS NEW BUILDING. INFORMATION WAS
 ROUTED TO THE ADDRESSING REVIEWER. PLEASE PLACE ADDRESS
 ON PLANS/TITLE BLOCKS ONCE DETERMINED.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES WHICH WERE
 ADOPTED BY THE STATE SHALL BE STATED ON PLANS. SOME ARE
 LISTED, HOWEVER NOT ALL.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THIS IS NOTED BY THIS REVIEWER
 ONLY. PLEASE SEE THE SURVEY SHEETS SUBMITTED ARE
 SEALED, HOWEVER NOT SIGNED/DATED.
 PLEASE SEE FS 472.025
  
 3) NOTE: PLEASE SEE FBC 2004 W/2006/07 REVISIONS.
 CHAPTER 13 AND SUBMIT PLANS IN COMPLIANCE FOR THE
 FLORIDA ENERGY CODE.
 PLEASE SUBMIT COMPLETED INFORMATION ON LIGHTING
 CONTROLS/PANEL WHICH IS SHOWN.
 PLEASE SEE MANY LOCATIONS WHICH INDICATE A *S* WITH O,
 HOWEVER SYMBOL LEGEND DOES NOT INDICATE WHAT THIS IS.
 THIS CAN BE ASSUMED TO BE AN OCCUPANCY SENSOR TYPE
 SWITCH. PLEASE SEE NO MAXIMUM TIMES WERE PROVIDED FOR
 ANY OCCUPANCY SENSOR DEVICES.
 PLEASE SEE OTHER AREAS WHICH CONTAIN A SWITCH WITH A
 NOTATION FOR CONTROLLED HOWEVER NO INFORMATION ON THESE
 DEVICES OR OVER RIDES, OR OVER RIDE TIMES SUBMITTED.
 PLEASE SUBMIT COMPLETED INFORMATION.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME AREA DO NOT INDICATE ANY CONTROLS AS
 REQUIRED. FOR EXAMPLE: ROOMS 114, 115. ONLY NOTED THESE
 TWO, PLEASE GO OVER THE ENTIRE SYSTEM.
  
 4) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINGLY.
  
 5) NOTE: PLEASE SEE 13-415.1.A, 13-415.2. PLEASE SEE
 THE ENERGY CALCULATIONS AS SUBMITTED DO NOT CORRELATE
 WITH THE PLANS AND INFORMATION SHOWN ON PLANS. PLEASE
 KNOW THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE
 REST OF THIS COMMENT.
 PLEASE SEE FOR EXAMPLE:
 PLEASE SEE COVER SHEET STATES OCCUPANCY IS HEALTHCARE,
 PLEASE SEE ARCHITECTURAL PLANS. (NOT UNDER HEALTHCARE
 FOR THIS OCCUPANCY).
 PLEASE SEE SQ FT ON PLANS WHICH DOES NOT CORRELATE WITH
 THE COVER SHEET.
 PLEASE SEE THE METHOD OF CONTROLS ON THE IDR SHOWS
 *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AN AUTOMATED
 SYSTEM AND DEVICES ARE BEING INSTALLED.
 PLEASE SEE THE INFORMATION ON THE IDR FOR ALL INTERIOR
 AND EXTERIOR LIGHTING FIXTURES NEEDS TO MATCH WITH
 PLANS. FOR EXAMPLE:
 PLEASE SEE THE LIGHTING ON PLANS WHICH SHOWS MORE 250W
 FIXTURES THAN WHAT IS LOCATED ON THE IDR.
 PLEASE SEE FOR EXAMPLE THE PLANS WHICH SHOWS 70W MH
 FIXTURES AND THE IDR SHOWS 100W AND THE NUMBER OF
 FIXTURES SHOWN ARE DIFFERENT THAN ON PLANS.
 ** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2
  
 5) NOTE: PLEASE SEE THE DOOR SWING IN THE MAIN
 ELECTRICAL ROOM SHALL SWING OUT. 110.26
 PLEASE PROVIDE INFORMATION TO THE ARCHITECT AND OTHER
 DESIGNERS FOR CHANGES ON ALL SHEETS.
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS.
 90.7, 110.3.
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE PROPOSED CABLE
 CONNECTION CABINET.
 NEED TO BE SURE THE CABLES TO BE INSTALLED. PLEASE KNOW
 CABLES MAY NOT RUN THROUGH DOOR WAY OF ELECTRICAL ROOM
 AS DOOR IS TO REMAIN CLOSED/LOCKED.
 110.26
  
 8) NOTE: PLEASE SEE THE MDP! ON RISER IS SHOWN AS
 1000AMPS YET THE SCHEDULE FOR THE SAME MAIN SHOWS THIS
 AS 1600AMPS.
 PLEASE CORRELATE.
 230.70, 230.71, 240.4, 310.16 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 9) NOTE: PLEASE SEE PLANS SHOWS LIGHTING FIXTURES NOTED
 AS EMERGENCY LIGHTS, HOWEVER THERE IS NO BATTERY BACK
 UP BALLAST?
 PLEASE SEE NFPA-101 7.8, 7.9.
  
 10) NOTE: PLEASE SEE RISER SHOWS AN *EQUIPMENT
 GROUNDING CONDUCTOR* ON THE LINE SIDE OF THE MAIN WHICH
 IS NOT PERMITTED PER 250.6, 250.24.
 PLEASE SEE THAT *EQUIPMENT GROUNDING CONDUCTORS* ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF DISCONNECT.
  
 11) NOTE: PLEASE SEE 250.66 FOR SIZING THE GROUNDING
 ELECTRODE CONDUCTOR. TOO SMALL AS SHOWN.
  
 12) NOTE: PLEASE KNOW THE LIGHTNING PROTECTION SYSTEM
 AS SHOWN WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT.
  
 13) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR
 HORN AND STROBE DEVICE LOCATIONS AND LEVELS FOR ADA
 COMPLIANCE.
 PLEASE INDICATE ALL LOCATIONS AND LEVELS.
  
 ** PLEASE SEE COMMENTS FROM ANY OTHER TRADE WHICH MAY
 AFFECT THE ELECTRICAL PLANS AS SUBMITTED.
  
 ** PLEASE KNOW AS COMPLETED ELECTRICAL PLANS FOR
 MINIMUM CODE COMPLIANCE WAS NOT SUBMITTED THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved