| Date |
Text |
| 2007-12-25 14:19:36 | 2007-12-25 14:19:36 |
| | |
| | ** DENIEDREVIEW ** |
| | |
| | ** PLEASE KNOW THE ADDRESS MAY BE NEEDED TO BE |
| | ADDRESSED AS THIS IS NEW BUILDING. INFORMATION WAS |
| | ROUTED TO THE ADDRESSING REVIEWER. PLEASE PLACE ADDRESS |
| | ON PLANS/TITLE BLOCKS ONCE DETERMINED. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES WHICH WERE |
| | ADOPTED BY THE STATE SHALL BE STATED ON PLANS. SOME ARE |
| | LISTED, HOWEVER NOT ALL. |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THIS IS NOTED BY THIS REVIEWER |
| | ONLY. PLEASE SEE THE SURVEY SHEETS SUBMITTED ARE |
| | SEALED, HOWEVER NOT SIGNED/DATED. |
| | PLEASE SEE FS 472.025 |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 W/2006/07 REVISIONS. |
| | CHAPTER 13 AND SUBMIT PLANS IN COMPLIANCE FOR THE |
| | FLORIDA ENERGY CODE. |
| | PLEASE SUBMIT COMPLETED INFORMATION ON LIGHTING |
| | CONTROLS/PANEL WHICH IS SHOWN. |
| | PLEASE SEE MANY LOCATIONS WHICH INDICATE A *S* WITH O, |
| | HOWEVER SYMBOL LEGEND DOES NOT INDICATE WHAT THIS IS. |
| | THIS CAN BE ASSUMED TO BE AN OCCUPANCY SENSOR TYPE |
| | SWITCH. PLEASE SEE NO MAXIMUM TIMES WERE PROVIDED FOR |
| | ANY OCCUPANCY SENSOR DEVICES. |
| | PLEASE SEE OTHER AREAS WHICH CONTAIN A SWITCH WITH A |
| | NOTATION FOR CONTROLLED HOWEVER NO INFORMATION ON THESE |
| | DEVICES OR OVER RIDES, OR OVER RIDE TIMES SUBMITTED. |
| | PLEASE SUBMIT COMPLETED INFORMATION. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SOME AREA DO NOT INDICATE ANY CONTROLS AS |
| | REQUIRED. FOR EXAMPLE: ROOMS 114, 115. ONLY NOTED THESE |
| | TWO, PLEASE GO OVER THE ENTIRE SYSTEM. |
| | |
| | 4) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE |
| | NOTES ON PLANS ACCORDINGLY. |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.A, 13-415.2. PLEASE SEE |
| | THE ENERGY CALCULATIONS AS SUBMITTED DO NOT CORRELATE |
| | WITH THE PLANS AND INFORMATION SHOWN ON PLANS. PLEASE |
| | KNOW THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE |
| | REST OF THIS COMMENT. |
| | PLEASE SEE FOR EXAMPLE: |
| | PLEASE SEE COVER SHEET STATES OCCUPANCY IS HEALTHCARE, |
| | PLEASE SEE ARCHITECTURAL PLANS. (NOT UNDER HEALTHCARE |
| | FOR THIS OCCUPANCY). |
| | PLEASE SEE SQ FT ON PLANS WHICH DOES NOT CORRELATE WITH |
| | THE COVER SHEET. |
| | PLEASE SEE THE METHOD OF CONTROLS ON THE IDR SHOWS |
| | *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AN AUTOMATED |
| | SYSTEM AND DEVICES ARE BEING INSTALLED. |
| | PLEASE SEE THE INFORMATION ON THE IDR FOR ALL INTERIOR |
| | AND EXTERIOR LIGHTING FIXTURES NEEDS TO MATCH WITH |
| | PLANS. FOR EXAMPLE: |
| | PLEASE SEE THE LIGHTING ON PLANS WHICH SHOWS MORE 250W |
| | FIXTURES THAN WHAT IS LOCATED ON THE IDR. |
| | PLEASE SEE FOR EXAMPLE THE PLANS WHICH SHOWS 70W MH |
| | FIXTURES AND THE IDR SHOWS 100W AND THE NUMBER OF |
| | FIXTURES SHOWN ARE DIFFERENT THAN ON PLANS. |
| | ** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE DOOR SWING IN THE MAIN |
| | ELECTRICAL ROOM SHALL SWING OUT. 110.26 |
| | PLEASE PROVIDE INFORMATION TO THE ARCHITECT AND OTHER |
| | DESIGNERS FOR CHANGES ON ALL SHEETS. |
| | |
| | 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE NEW PROPOSED MTS. |
| | 90.7, 110.3. |
| | |
| | 7) NOTE: PLEASE SHOW THE LOCATION OF THE PROPOSED CABLE |
| | CONNECTION CABINET. |
| | NEED TO BE SURE THE CABLES TO BE INSTALLED. PLEASE KNOW |
| | CABLES MAY NOT RUN THROUGH DOOR WAY OF ELECTRICAL ROOM |
| | AS DOOR IS TO REMAIN CLOSED/LOCKED. |
| | 110.26 |
| | |
| | 8) NOTE: PLEASE SEE THE MDP! ON RISER IS SHOWN AS |
| | 1000AMPS YET THE SCHEDULE FOR THE SAME MAIN SHOWS THIS |
| | AS 1600AMPS. |
| | PLEASE CORRELATE. |
| | 230.70, 230.71, 240.4, 310.16 ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 9) NOTE: PLEASE SEE PLANS SHOWS LIGHTING FIXTURES NOTED |
| | AS EMERGENCY LIGHTS, HOWEVER THERE IS NO BATTERY BACK |
| | UP BALLAST? |
| | PLEASE SEE NFPA-101 7.8, 7.9. |
| | |
| | 10) NOTE: PLEASE SEE RISER SHOWS AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* ON THE LINE SIDE OF THE MAIN WHICH |
| | IS NOT PERMITTED PER 250.6, 250.24. |
| | PLEASE SEE THAT *EQUIPMENT GROUNDING CONDUCTORS* ARE |
| | ONLY INSTALLED AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 11) NOTE: PLEASE SEE 250.66 FOR SIZING THE GROUNDING |
| | ELECTRODE CONDUCTOR. TOO SMALL AS SHOWN. |
| | |
| | 12) NOTE: PLEASE KNOW THE LIGHTNING PROTECTION SYSTEM |
| | AS SHOWN WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT. |
| | |
| | 13) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR |
| | HORN AND STROBE DEVICE LOCATIONS AND LEVELS FOR ADA |
| | COMPLIANCE. |
| | PLEASE INDICATE ALL LOCATIONS AND LEVELS. |
| | |
| | ** PLEASE SEE COMMENTS FROM ANY OTHER TRADE WHICH MAY |
| | AFFECT THE ELECTRICAL PLANS AS SUBMITTED. |
| | |
| | ** PLEASE KNOW AS COMPLETED ELECTRICAL PLANS FOR |
| | MINIMUM CODE COMPLIANCE WAS NOT SUBMITTED THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |