Plan Review Notes
Plan Review Notes For Permit 07120513
Permit Number 07120513
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-24 16:55:39 
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07120513
 ADD: 1301 SUMMIT BLVD
 CONT: STILES
 TEL: (954)627-9150
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. SHEET A1.0 CODE
 SUMMARY INDICATES THE 2006 SUPPLEMENTS. PLEASE
 CORRECT.
  
 2) NOTICE ONLY! FBC BUILDING 3110.1.2 / CITY OF WPB
 CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED
 IN AN "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE
 WILL BE REQUIRED BEFORE THE CERTIFICATE OF OCCUPANCY
 WILL BE ISSUED.
  
 3) NOTICE: 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 4) NOTICE:109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 5) SHEETA2.1 DOOR NUMBER 113B, 114B & 131A ALL APPEAR
 NOT TO COMPLY WITH 11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 6) SHEET A2.1 ROOM 132 RADIOLOGY PLEASE PROVIDE
 COMPLIANCE WITH 435.5 .3.1, 435.5.1.2, 435.1.3 &
 435.5.1.3.1(1-6) 435.5.1.3.3.
  
 7)SHEET A2.3 THE ROOF PLAN INDICATES THE USE OF
 SCUPPERS BUT NO DETAIL INFORMATION HAS BEEN
 PROVIDEDPLEASE REVIEW 1503.4 7& 1503.4.3 . ROOF
 DRAINAGE SYSTEMS SHALL COMPLY WITH THE FLORIDA BUILDING
 CODE, PLUMBING, CHAPTER 11.AN OVERFLOW SCUPPER SHALL
 BE SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 PLUMBING.
  
 8) SHEET A2.3 ROOF ACCESS HATCH, WILL REQUIRE PRODUCT
 APPROVAL, CURRENTLY THERE IS NO APPROVALS THROUGH
 EITHER THE STATE OR MIAMI-DADE NOA. A BUILDING PROVISO
 WILL BE ISSUED BUT BEFORE THE BUILDING WILL RECEIVE A
 CERTIFICATE OF OCCUPANCY, EITHER A LOCAL PRODUCT
 APPROVAL, MIAMI-DADE NOA OR FLORIDA STATEWIDE APPROVAL
 WILL BE REQUIRED. RULE 9B-72. SEE ATTACHMENT.
  
 9) SHEET A2.3 INDICATES THROUGH THE ROOF A/C UNITS
 MOUNTED ON CURBS. S2.3 DETAIL# 10 INDICATES A/C CURB
 BUT NOT THE METHOD OF ATTACHMENT. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 10) SHHET A2.1 INDICATES A FREEZER COURT WHICH IS
 INDICATED AS EXTERIOR, PLEASE PROVIDE PRODUCT APPROVALS
 FOR THESE FREEZERS, EITHER A MIAMI-DADE COUNTY NOA OR
 FLORIDA STATE APPROVAL SEE
 RULE 9-B-72(31)(G)EXTERIOR COOLER/FREEZERS. ALSO
 DEMONSTRATE RESISTANCE TO MOMENT OF OVERTURNING, AND
 SLIDDING, 1609.1.3.
  
 11) NOT SHOWN ON A2.3 BUT SHOWN ON M1.2 THE ROOF PLAN
 INDICATES A ROOF TOP "CU-1" PLEASE CONFORM WITH: RULE
 9B-72 ALSO REQUIRING EITHER A MIAMI-DADE COUNTY NOA OR
 FLORIDA STATE APPROVAL SEE
 RULE 9-B-72(31)(G) FOR PRE-MANUFACTURED A/C STANDS.
  
 12)THE ROOF TOP CU-1 SHALL COMPLY WITH 1509.7
 CLEARENCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
 SEE TABLE FOR THE WIDTH OF UNIT THE REQUIRED
 CLEARENCE.
  
 13) SHEET A5.1 DETAIL# 9 INDICATES A FIBERGLASS CORNICE
 MOLDING " FRP CORNICE AND BRACKETS" TO BE ATTACHED PER
 MANUFACTURERS RECCOMENDATIONS, PLEASE PROVIDE
 ADDITIONAL INFORMATION, 106.1.2.
 PLEASE PROVIDE HOW CORNICE AND BRACKETS WILL BE
 APPLIED. WILL THE MANUFACTUER SUPPLY SHOP DRAWINGS AND
 CALCULATIONS FOR ATTACHMENT TO WITHSTAND THE ASSOCIATED
 POSITIVE AND NEGATIVE PRESSURES THAT WILL OCCUR?
  
 14)SHEET A5.1 DETAIL# 12 & 17 BOTH INDICATE THE USE
 OF WOOD POST EMBEDDED INTO THE EARTH BUT THERE IS NO
 MENTION OF USING A PRESSURE TREATED WOOD OR NATURALLY
 DURABLE WOOD PLEASE COMPLY
 WITH SECTION 2303.1.8.
  
 15) SHEET A5.1 DETAIL # 6 DOES INDICATE THE USE OF A
 WATER PROOFING MEMBRANE ON THE SIDE OF THE PLANTER THAT
 ABUTTS OR MAKES UP THE EXTERIOR WALL OF THE BUILDING,
 IS THERE TO BE CONSIDERATION TO WATERPROOF THE OUTER
 PLANTER WALL? IF NOT HOW WILL THE MOISTURE THAT TRAVELS
 THROUGH THE BLOCK AND STUCCO EFFECT THE FINISH, PAINT
 BLISTERING ETC?
  
 16) SHEET A5.2 ALSO INDICATES THE USE OF GLUE LAMINATED
 BEAMS AS PAART OF THE FRAMING USED IN THE PERGOLA, THIS
 MATERIAL WILL NEED TO COMPLY WITH RULE 9B-72 (31)(G)
 STRUCTURAL COMPONENTS REQUIRING
 FLORIDA PRODUCT APPROVALS.
  
 17) SHEET 2.2 INDICATES TWO AREAS WHERE USE OF THE
 PERGOLA WILL BE USED IN THIS PROJECT, SHEETA5.2
 INDICATES DETAILS FOR THE ONE PERGOLA TO BE BUILT AT
 THE FRONT ENTRY AND LOBBY, NO DETAILS ARE SUBMITTED
 FORTHE PERGOLA LOCATED TO THE EXTERIOR OF THE
 CONFERENCE ROOM. PLEASE PROVIDE ADDITIONAL
 INFORMATION.106.1.2.
  
 18) SHEET A5.2 USE OF THE PERGOLA OVER THE EXIT
 DISCHARGE WITH USE OF COMBUSTIBLE MATERIALS. ALTHOUGH
 THE CODE DISCUSSES FOR TYPE I & TYPE II BUILDING WHERE
 COMBUSTIBLE & NONCOMBUSTILE MATERIALS ARE ALLOWED
 WITHIN THE BUILDING, THE CODE DOES NOTINDICATE IN 603.1
 OUTSIDE OF THE BUILDING. WHAT WE SEE AS A ISSUE IS THIS
 IS THE MAIN ENTRY IF FIREIS TO BREAK OUT AT THE ENTRY
 THE COMBUSTIBLE MATERIALS COULD AND WOULD BLOCK THE
 EXIT AND REQUIRING THE OCCUPANTTO LOCATE ANOTHER
 EXIT. WHERE AS 1023.4 AN EXIT DISCHARGE COMPONENTS
 SHALL BE SUFFICIENTLY OPEN TO THE EXTEIOR AS TO
 MINIMIZE THE ACCUMULATION OF SMOKE AND TOXIC GASSES.
 THIS SAME DETAILS INDICATES THE USE OF GLUE LAMS,
 FIBERGLASS REINFORCED PLASTIC AND WATERPROOF FABRIC
 THESE ARE ALL ELEMENTS THAT WILL CREATE SMOKE AND THE
 FRP WILL CREATE TOXIC GASSES.
  
 19) OBSERVATION ONLY! SHEET A5.2 THIS DETAIL SEEM THE
 MAIN FRAMING MEMBERS SHOUD OF BEEN DRAWN TO CARRY OVER
 THE WOOD POST NOT CUT SHORT AND ADDED BRACKETS AND OR
 HANGERS!
  
 20) THE MAIN FRAMING MEMBERS ARE NOT SHOWN TO RESIST
 UPLIFT LOADS, THERE IS NO TIE DOWN STRAPS TO THE
 COLUMNS. 1609.6.1.1MAIN WINDFORCE RESISTING SYSTEM.
  
 21)SHEET A7.3 PLEASE PROVIDE THE HEIGHT OF THE
 MICROWAVE CONTROLS, REACH RANGES SIDE APPROACH 11-4.2.6
 AND CONTROLS AND OPERATING MECHANISMS 11-4.27.
  
 22)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 23)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT- THE NOA SUBMITTED IS MISSING THE
 TECHNICAL SHEETS 1-12, PLEASE HIGHLIGHTMULLIONS
 UNREINFORCED OR EINFORCED, THE PERIMETER FASTENER ,
 ANCHOR PATTERN / ALLOWABLE
 PRESSURES, & TYPE OF GLAZING TO BE INSTALLED.
 B) CASEMENT WINDOWS- NO REPORT SUBMITTED.
 C) EXTERIOR DOORS - INGERSOLL-RAND GLAZED AND HOLLOW
 METAL DOORS MISSING FLORIDA COVERSHEET AND DESIGNEROF
 RECORD REVIEW
 D) GUILITINE DOOR- NO PRODUCT APPROVAL SUBMITTED
 E) OVER HEAD OR ROLL UP DOOR- NO PRODUCT APPROVAL
 SUBMITTED
 F) ROOF ACCESS HATCH- NO PRODUCT APPROVAL SUBMITTED
 G) ENGINEERED LUMBER- LVLOR MICRO LAMS, NO PRODUCT
 APPROVAL SUBMITTED
 H) TRUSS STRAPS, WOOD CONNECTORS, BUCKETS, ETC- NO
 PRODUCT APPROVALS SUBMITTED
 I) EXTERIOR COOLER-FREEZERS- NO PRODUCT APPROVALS
 SUBMITTED
 J) PRE-ENGINEERED A/C STANDS- NO PRODUCT APPROVALS
 SUBMITTED
 K) ROOFING ASSEMBLIES- SIPLAST, MISSING FL COVERSHEET,
 AND THE DESIGNER OF RECORD REVIEW
  
 *** THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
  
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ MAY BE ISSUE WHEN THE SUB-SYSTEM IS PICKED. THE
 SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD THE
 FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTEREDARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _XX__ MAY BE ISSUEWHEN SUB-SYSTEM IS PICKED, THE SYSTEM
 PROVIDED INDICATES LIMITATION# 9, NO ENHANCED FASTENING
 ALLOWED.
  
 24) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 25) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 26)SHEET A4.3 SECTION 4&5 BOTH INDICATE A ANODIZED
 6'-0" ALUMINUM CANOPY WITH A NOTE ATTACHED TO
 STRUCTURAL PER STRUCTURAL, THE "S" SHEETS HAVE NO SUCH
 DETAIL, PLEASE PROVIDE ADDITIONAL ANCHORING
 INFORMATION, SHOP DRAWINGS INDICATING THE DESIGN
 CRITERIA 3105.5.1.
  
 27)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.