| 2008-01-24 16:55:39 | |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120513 |
| | ADD: 1301 SUMMIT BLVD |
| | CONT: STILES |
| | TEL: (954)627-9150 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS. SHEET A1.0 CODE |
| | SUMMARY INDICATES THE 2006 SUPPLEMENTS. PLEASE |
| | CORRECT. |
| | |
| | 2) NOTICE ONLY! FBC BUILDING 3110.1.2 / CITY OF WPB |
| | CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED |
| | IN AN "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE |
| | WILL BE REQUIRED BEFORE THE CERTIFICATE OF OCCUPANCY |
| | WILL BE ISSUED. |
| | |
| | 3) NOTICE: 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 4) NOTICE:109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 5) SHEETA2.1 DOOR NUMBER 113B, 114B & 131A ALL APPEAR |
| | NOT TO COMPLY WITH 11-4.13.6 MANEUVERING CLEARENCES AT |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 6) SHEET A2.1 ROOM 132 RADIOLOGY PLEASE PROVIDE |
| | COMPLIANCE WITH 435.5 .3.1, 435.5.1.2, 435.1.3 & |
| | 435.5.1.3.1(1-6) 435.5.1.3.3. |
| | |
| | 7)SHEET A2.3 THE ROOF PLAN INDICATES THE USE OF |
| | SCUPPERS BUT NO DETAIL INFORMATION HAS BEEN |
| | PROVIDEDPLEASE REVIEW 1503.4 7& 1503.4.3 . ROOF |
| | DRAINAGE SYSTEMS SHALL COMPLY WITH THE FLORIDA BUILDING |
| | CODE, PLUMBING, CHAPTER 11.AN OVERFLOW SCUPPER SHALL |
| | BE SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | PLUMBING. |
| | |
| | 8) SHEET A2.3 ROOF ACCESS HATCH, WILL REQUIRE PRODUCT |
| | APPROVAL, CURRENTLY THERE IS NO APPROVALS THROUGH |
| | EITHER THE STATE OR MIAMI-DADE NOA. A BUILDING PROVISO |
| | WILL BE ISSUED BUT BEFORE THE BUILDING WILL RECEIVE A |
| | CERTIFICATE OF OCCUPANCY, EITHER A LOCAL PRODUCT |
| | APPROVAL, MIAMI-DADE NOA OR FLORIDA STATEWIDE APPROVAL |
| | WILL BE REQUIRED. RULE 9B-72. SEE ATTACHMENT. |
| | |
| | 9) SHEET A2.3 INDICATES THROUGH THE ROOF A/C UNITS |
| | MOUNTED ON CURBS. S2.3 DETAIL# 10 INDICATES A/C CURB |
| | BUT NOT THE METHOD OF ATTACHMENT. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 10) SHHET A2.1 INDICATES A FREEZER COURT WHICH IS |
| | INDICATED AS EXTERIOR, PLEASE PROVIDE PRODUCT APPROVALS |
| | FOR THESE FREEZERS, EITHER A MIAMI-DADE COUNTY NOA OR |
| | FLORIDA STATE APPROVAL SEE |
| | RULE 9-B-72(31)(G)EXTERIOR COOLER/FREEZERS. ALSO |
| | DEMONSTRATE RESISTANCE TO MOMENT OF OVERTURNING, AND |
| | SLIDDING, 1609.1.3. |
| | |
| | 11) NOT SHOWN ON A2.3 BUT SHOWN ON M1.2 THE ROOF PLAN |
| | INDICATES A ROOF TOP "CU-1" PLEASE CONFORM WITH: RULE |
| | 9B-72 ALSO REQUIRING EITHER A MIAMI-DADE COUNTY NOA OR |
| | FLORIDA STATE APPROVAL SEE |
| | RULE 9-B-72(31)(G) FOR PRE-MANUFACTURED A/C STANDS. |
| | |
| | 12)THE ROOF TOP CU-1 SHALL COMPLY WITH 1509.7 |
| | CLEARENCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS. |
| | SEE TABLE FOR THE WIDTH OF UNIT THE REQUIRED |
| | CLEARENCE. |
| | |
| | 13) SHEET A5.1 DETAIL# 9 INDICATES A FIBERGLASS CORNICE |
| | MOLDING " FRP CORNICE AND BRACKETS" TO BE ATTACHED PER |
| | MANUFACTURERS RECCOMENDATIONS, PLEASE PROVIDE |
| | ADDITIONAL INFORMATION, 106.1.2. |
| | PLEASE PROVIDE HOW CORNICE AND BRACKETS WILL BE |
| | APPLIED. WILL THE MANUFACTUER SUPPLY SHOP DRAWINGS AND |
| | CALCULATIONS FOR ATTACHMENT TO WITHSTAND THE ASSOCIATED |
| | POSITIVE AND NEGATIVE PRESSURES THAT WILL OCCUR? |
| | |
| | 14)SHEET A5.1 DETAIL# 12 & 17 BOTH INDICATE THE USE |
| | OF WOOD POST EMBEDDED INTO THE EARTH BUT THERE IS NO |
| | MENTION OF USING A PRESSURE TREATED WOOD OR NATURALLY |
| | DURABLE WOOD PLEASE COMPLY |
| | WITH SECTION 2303.1.8. |
| | |
| | 15) SHEET A5.1 DETAIL # 6 DOES INDICATE THE USE OF A |
| | WATER PROOFING MEMBRANE ON THE SIDE OF THE PLANTER THAT |
| | ABUTTS OR MAKES UP THE EXTERIOR WALL OF THE BUILDING, |
| | IS THERE TO BE CONSIDERATION TO WATERPROOF THE OUTER |
| | PLANTER WALL? IF NOT HOW WILL THE MOISTURE THAT TRAVELS |
| | THROUGH THE BLOCK AND STUCCO EFFECT THE FINISH, PAINT |
| | BLISTERING ETC? |
| | |
| | 16) SHEET A5.2 ALSO INDICATES THE USE OF GLUE LAMINATED |
| | BEAMS AS PAART OF THE FRAMING USED IN THE PERGOLA, THIS |
| | MATERIAL WILL NEED TO COMPLY WITH RULE 9B-72 (31)(G) |
| | STRUCTURAL COMPONENTS REQUIRING |
| | FLORIDA PRODUCT APPROVALS. |
| | |
| | 17) SHEET 2.2 INDICATES TWO AREAS WHERE USE OF THE |
| | PERGOLA WILL BE USED IN THIS PROJECT, SHEETA5.2 |
| | INDICATES DETAILS FOR THE ONE PERGOLA TO BE BUILT AT |
| | THE FRONT ENTRY AND LOBBY, NO DETAILS ARE SUBMITTED |
| | FORTHE PERGOLA LOCATED TO THE EXTERIOR OF THE |
| | CONFERENCE ROOM. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION.106.1.2. |
| | |
| | 18) SHEET A5.2 USE OF THE PERGOLA OVER THE EXIT |
| | DISCHARGE WITH USE OF COMBUSTIBLE MATERIALS. ALTHOUGH |
| | THE CODE DISCUSSES FOR TYPE I & TYPE II BUILDING WHERE |
| | COMBUSTIBLE & NONCOMBUSTILE MATERIALS ARE ALLOWED |
| | WITHIN THE BUILDING, THE CODE DOES NOTINDICATE IN 603.1 |
| | OUTSIDE OF THE BUILDING. WHAT WE SEE AS A ISSUE IS THIS |
| | IS THE MAIN ENTRY IF FIREIS TO BREAK OUT AT THE ENTRY |
| | THE COMBUSTIBLE MATERIALS COULD AND WOULD BLOCK THE |
| | EXIT AND REQUIRING THE OCCUPANTTO LOCATE ANOTHER |
| | EXIT. WHERE AS 1023.4 AN EXIT DISCHARGE COMPONENTS |
| | SHALL BE SUFFICIENTLY OPEN TO THE EXTEIOR AS TO |
| | MINIMIZE THE ACCUMULATION OF SMOKE AND TOXIC GASSES. |
| | THIS SAME DETAILS INDICATES THE USE OF GLUE LAMS, |
| | FIBERGLASS REINFORCED PLASTIC AND WATERPROOF FABRIC |
| | THESE ARE ALL ELEMENTS THAT WILL CREATE SMOKE AND THE |
| | FRP WILL CREATE TOXIC GASSES. |
| | |
| | 19) OBSERVATION ONLY! SHEET A5.2 THIS DETAIL SEEM THE |
| | MAIN FRAMING MEMBERS SHOUD OF BEEN DRAWN TO CARRY OVER |
| | THE WOOD POST NOT CUT SHORT AND ADDED BRACKETS AND OR |
| | HANGERS! |
| | |
| | 20) THE MAIN FRAMING MEMBERS ARE NOT SHOWN TO RESIST |
| | UPLIFT LOADS, THERE IS NO TIE DOWN STRAPS TO THE |
| | COLUMNS. 1609.6.1.1MAIN WINDFORCE RESISTING SYSTEM. |
| | |
| | 21)SHEET A7.3 PLEASE PROVIDE THE HEIGHT OF THE |
| | MICROWAVE CONTROLS, REACH RANGES SIDE APPROACH 11-4.2.6 |
| | AND CONTROLS AND OPERATING MECHANISMS 11-4.27. |
| | |
| | 22)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 23)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) STOREFRONT- THE NOA SUBMITTED IS MISSING THE |
| | TECHNICAL SHEETS 1-12, PLEASE HIGHLIGHTMULLIONS |
| | UNREINFORCED OR EINFORCED, THE PERIMETER FASTENER , |
| | ANCHOR PATTERN / ALLOWABLE |
| | PRESSURES, & TYPE OF GLAZING TO BE INSTALLED. |
| | B) CASEMENT WINDOWS- NO REPORT SUBMITTED. |
| | C) EXTERIOR DOORS - INGERSOLL-RAND GLAZED AND HOLLOW |
| | METAL DOORS MISSING FLORIDA COVERSHEET AND DESIGNEROF |
| | RECORD REVIEW |
| | D) GUILITINE DOOR- NO PRODUCT APPROVAL SUBMITTED |
| | E) OVER HEAD OR ROLL UP DOOR- NO PRODUCT APPROVAL |
| | SUBMITTED |
| | F) ROOF ACCESS HATCH- NO PRODUCT APPROVAL SUBMITTED |
| | G) ENGINEERED LUMBER- LVLOR MICRO LAMS, NO PRODUCT |
| | APPROVAL SUBMITTED |
| | H) TRUSS STRAPS, WOOD CONNECTORS, BUCKETS, ETC- NO |
| | PRODUCT APPROVALS SUBMITTED |
| | I) EXTERIOR COOLER-FREEZERS- NO PRODUCT APPROVALS |
| | SUBMITTED |
| | J) PRE-ENGINEERED A/C STANDS- NO PRODUCT APPROVALS |
| | SUBMITTED |
| | K) ROOFING ASSEMBLIES- SIPLAST, MISSING FL COVERSHEET, |
| | AND THE DESIGNER OF RECORD REVIEW |
| | |
| | *** THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| | FOLLOW ITEMS: |
| | |
| | __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE USED. |
| | |
| | _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | _2&3__ . |
| | |
| | _XX__ MAY BE ISSUE WHEN THE SUB-SYSTEM IS PICKED. THE |
| | SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD THE |
| | FASTENER RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A |
| | REVISED FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTEREDARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | _XX__ MAY BE ISSUEWHEN SUB-SYSTEM IS PICKED, THE SYSTEM |
| | PROVIDED INDICATES LIMITATION# 9, NO ENHANCED FASTENING |
| | ALLOWED. |
| | |
| | 24) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 25) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 26)SHEET A4.3 SECTION 4&5 BOTH INDICATE A ANODIZED |
| | 6'-0" ALUMINUM CANOPY WITH A NOTE ATTACHED TO |
| | STRUCTURAL PER STRUCTURAL, THE "S" SHEETS HAVE NO SUCH |
| | DETAIL, PLEASE PROVIDE ADDITIONAL ANCHORING |
| | INFORMATION, SHOP DRAWINGS INDICATING THE DESIGN |
| | CRITERIA 3105.5.1. |
| | |
| | 27)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |