| Plan Review Notes For Permit 07120512 |
| Permit Number |
07120512 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-01-02 14:38:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 1.)CHANGES TO THE ISSUED PERMIT ARE TO BE SUBMITTED | | | AS REVISIONS TO THE PRIMARY PERMIT.THE METAL ROOF | | | ISSUED WITH THE PERMIT WAS FOR BEMO 305 ALUMINUM | | | STANDING SEAM.YOUR APPLICATION STATES "SERIES 2000" | | | BUT NO PAPERWORK WAS SUBMITTED. | | | | | | 2.)PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | FOR EACH ROOF SYSTEM, FAC9B72.THIS IS IN ADDITION TO | | | THE EVALUATION REPORT (NOA).WWW.FLORIDABUILDING.ORG | | | | | | 3.)ADDRESSED. | | | | | | 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | | OF RECORD PRIOR TO SUBMITTAL, FBC*106.3.3. | | | | | | THIS WAS DONE FOR THE METAL ROOF BUT NOT FOR THE BUILT | | | UP ROOF. | | | | | | 5.)ADDRESSED. | | | | | | 6.)SEE GENERAL LIMITATION #7 OF THE JOHNS MANVILLE | | | BUR.ENHANCED FASTENING CALCS ARE TO BE PREPARED BY AN | | | ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT. | | | PRESSURES SPECIFIED BY THE ENGINEER FOR THIS PROJECT | | | ARE -47, -79, -119 FOR ZONES 1, 2, AND 3 RESPECTIVELY. | | | |
|