| 2007-12-20 15:25:27 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | |
| | 1.)CHANGES TO THE ISSUED PERMIT ARE TO BE SUBMITTED |
| | AS REVISIONS TO THE PRIMARY PERMIT.THE METAL ROOF |
| | ISSUED WITH THE PERMIT WAS FOR BEMO 305 ALUMINUM |
| | STANDING SEAM.YOUR APPLICATION STATES "SERIES 2000" |
| | BUT NO PAPERWORK WAS SUBMITTED. |
| | |
| | 2.)PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | FOR EACH ROOF SYSTEM, FAC9B72.THIS IS IN ADDITION TO |
| | THE EVALUATION REPORT (NOA).WWW.FLORIDABUILDING.ORG |
| | |
| | 3.)PROVIDE PRODUCT APPROVAL FOR THE METAL ROOF. |
| | |
| | 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD PRIOR TO SUBMITTAL, FBC*106.3.3. |
| | |
| | 5.)FOR THE LOW SLOPE ROOF, INDICATE WHICH APPROVED |
| | ASSEMBY YOU WILL BE USING. |
| | |
| | 6.)SEE GENERAL LIMITATION #7 OF THE JOHNS MANVILLE |
| | BUR.ENHANCED FASTENING CALCS ARE TO BE PREPARED BY AN |
| | ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT. |
| | PRESSURES SPECIFIED BY THE ENGINEER FOR THIS PROJECT |
| | ARE -47, -79, -119 FOR ZONES 1, 2, AND 3 RESPECTIVELY. |
| | |
| | |
| | 7.)IF THE METAL ROOF HAS DIFFERENT FASTENING OPTIONS, |
| | PLEASE INDICATE WHICH SYSTEM YOU WILL BE USING.IF |
| | ENGINEERING IS REQUIRED, PLEASE SUBMIT. |