| 2008-02-20 07:41:56 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120497 |
| | ADD: 1661 WORTHINGTON RD. #100 |
| | CONT: A CUSTOM ELECTRIC. |
| | TEL: (561)868-6809 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND 2-20-08 |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)OK |
| | 1C)OK |
| | |
| | 1D) INFORMATIONAL:FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 2)OK |
| | |
| | 3) ENGINEERING CALCULATIONS SUBMITTED FROM PROTEK |
| | ENGINEERING ALSO INCLUDE CALCULATIONS FOR THE MOMENT OF |
| | OVERTURNING BUT NOT AGAINST SLIDING AS FOUND IN |
| | 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND |
| | SLIDING. PLEASE PROVIDE THE CALCULATIONS FOR SLIDING, |
| | CO-EFFICIENT OF FRICTION OR PROVIDE CALCULATIONS FOR |
| | ANCHORS. THE ENGINEER OF RECORD IS RESPONSIBLE FOR THE |
| | ANCHORAGE OF THE GENERATORS. |
| | 4) THE ELEVATION CERTIFICATE IS SET FOR 13?-0? WHICH IS |
| | 6? TO LOW, THE CITY IS MORE RESTRICTIVE WITH AN |
| | ADDITIONAL 6? SEE.HOW CAN THE ELEVATION CERTIFICATE |
| | BE COMPLETED BEFORE THE GENERATOR IS INSTALLED? |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |