Plan Review Notes
Plan Review Notes For Permit 07120497
Permit Number 07120497
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 12:41:46** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE FBC 108.3 AS VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, AND DESIGN COST ETC
 EVEN IF ANY EQUIPMENT OR OTHER ITEMS ARE OWNER
 SUPPLIED.
 PLEASE ADJUST VALUE.
  
 3) NOTE: PLEASE VERIFY SCOPE AND SIZE OF GENERATOR UNIT
 BEING INSTALLED AS THE PERMIT APPLICATION STATES 500KW
 AND ELECTRICAL PLANS AS WELL AS THE STRUCTURAL
 CALCULATIONS INDICATE 400KW.?
 AS THESE ARE BOTH DIFFERENT MINIMUM CODE COMPLIANCE AS
 SHOWN ON PLANS NOT BE VERIFIED. IF UNIT IS 500KW MANY
 ITEMS ON ELECTRICAL PLANS WILL CHANGE.
 240.4, 310.16, ETC
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES FOR SIZE
 OF FUEL TANK TO BE SPECIFIC.
 PLEASE BE SURE THE MANUFACTURE SPECS/CUTS SHEETS
 APPLIED TO PLANS CONTAINS ALL MINIMUM CLEARANCES.
 PLEASE SEE 110.3, 90.7 AS THESE WILL BE REQUIRED TO BE
 ON PLANS OR SUPPORTING DOCUMENTATION TO BE SUBMITTED.
  
 5) NOTE: PLEASE SEE MISSING DISCONNECT PER
 225.31-225.39, 702.11.
 PLEASE KNOW AS ZONING REVIEW WILL REQUIRED AN CLOSURE
 AROUND UNIT AND BASED ON PLANS THE MEANS OF DISCONNECT
 WILL NOT BE READILY AVAILABLE.
 PLEASE KNOW THE DISCONNECTING MEANS WILL NOT REQUIRE
 OVER CURRENT PROTECTION ONLY A RATED DISCONNECT FOR
 FEEDERS COMING INTO BUILDING.
 PLEASE SEE 225.34, 702.8 AND PLACE NOTES ON PLANS
 ACCORDINGLY.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 HAVE AN AFFECT ON ALL PLANS AND PROJECT AS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]