| 2008-02-04 08:47:14 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE THE ELECTRICAL PLANS CONTAIN A LOT |
| | OF INFORMATION WHICH IS VERY FAINT AND NOT EASILY READ. |
| | PLEASE SEE THERE ARE SEVERAL WALLS AND MOST IMPORTANTLY |
| | THE ROOM AND AREA DESIGNATIONS WHICH CAN NOT BE READ. |
| | IN ORDER TO REVIEW MANY ITEMS FOR OTHER CODE SECTIONS |
| | PLEASE REPRINT SHEETS SO A COMPLETE REVIEW CAN BE |
| | DONE. |
| | FBC ADMIN SECTION 106.1.1, 106.1.3 |
| | |
| | 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND WITH ALL |
| | FIXTURES WHICH ARE SHOWN ON PLANS. PLEASE BE SURE TO |
| | COORDINATE ALL FIXTURES WITH THE LIGHTING ALLOWANCES. |
| | FOR EXAMPLE: PLEASE SEE STORAGE ROOM 209 FIXTURE IS NOT |
| | FIGURED, IS NOT ON LEGEND ETC. |
| | THIS IS ONE EXAMPLE. |
| | FBC 13-415.1.ABC.1.1, .1.2, 13-415.2 |
| | |
| | 3) NOTE: PLEASE SEE THE RESPONSE WITH RESPECT TO USE OF |
| | METHOD *A* WITHIN A TENANT SPACE DOES NOT MEET *WHOLE |
| | BUILDING*. |
| | PLEASE KNOW THIS WAS CONFIRMED WITH THE FLORIDA |
| | BUILDING COMMISSION BY THIS OFFICE ON SEPTEMBER 26TH, |
| | 2007. PLEASE KNOW THE METHOD *A* INPUT DATA REPORT DOES |
| | NOT COORDINATE WITH PLANS AT THIS TIME IN EITHER CASE. |
| | ADDRESS ON METHOD *A* STILL SHOWN FOR BOCA LOCATION. |
| | FOR EXAMPLE: 88W LUMINAIRE, YET FIXTURE LEGEND DOES NOT |
| | INCLUDE ANY OF THESE. |
| | PLEASE SEE THE REST OF THIS COMMENT WITH RESPECT TO |
| | *METHOD *A* AND CALCULATIONS NEEDED. |
| | |
| | PLEASE SEE THE LIGHTING POWER ALLOWANCES REQUIRED PER |
| | 13-415.2. THE PLANS DO SHOW A TABLE FOR METHOD *B* |
| | SPACE BY SPACE, YET THERE IS INFORMATION STILL NEEDED. |
| | THE WAY THIS IS SET UP AND SHOWN IS OK, ONLY NEEDS SOME |
| | COORDINATION AND COMPLETION OF SOME ADDITIONAL |
| | INFORMATION. |
| | PLEASE SEE THERE ARE SEVERAL LOCATIONS (ROOMS) WHERE |
| | THE ALLOWANCE IS OVER THE PERMITTED ALLOWANCE. AS THERE |
| | IS NO TOTAL FOR DESIGN AND NO TOTAL FOR ALLOWANCE, |
| | PLEASE COMPLETE TABLE FOR THESE. |
| | |
| | |
| | 4) NOTE: PLEASE SEE THE FLOOR LAYOUTS ON ELECTRICAL |
| | PLANS ARE NOT THE SAME AS THAT OF THE LIFE SAFETY OR |
| | ARCHITECTURAL PLANS. |
| | PLEASE SEE FOR EXAMPLE: WALL ON ELECTRICAL PLANS FOR |
| | GYM IS MISSING WHEN SHOWN ON OTHER PLANS. |
| | PLEASE SEE FOR EXAMPLE: EGRESS PATH ON ELECTRICAL PLANS |
| | AT CUBICLE IS SMALLER THAN THAT OF LIFE SAFETY PLANS. |
| | PLEASE COORDINATE. FBC ADMIN SECTION 106.1.2 FOR |
| | COORDINATION. |
| | |
| | 5) NOTE: PLEASE BE SURE TO INCLUDE SUITE/UNIT NUMBERS |
| | ON TITLE BLOCKS ONCE DETERMINED. THIS IS ONCE TENANT |
| | SPACE NOT FOUR AS STATED ON PERMIT APPLICATION. |
| | THIS INFORMATION WAS SENT TO ADDRESSING REVIEWER. |
| | FAC 61G15-23.002, FAC 61G1-16.004, FBC ADMIN SECTION |
| | 106.5 ETC |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-02-01 19:11:36 | 2008-02-01 19:11:36 |
| | |
| | IN ELEC FOR ERVIEW, NOTES TO FOLLOW. |