| 2008-02-05 12:10:59 | BUILDING PLAN REVIEW |
| | PERMIT: 07120492 |
| | ADD: 2475 ? MERCER AVE |
| | CONT: SEAL-TITE |
| | TEL: (561)346-8191 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | 2-5-08 |
| | |
| | 1A)OK |
| | |
| | 1B) OK |
| | |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 REVISIONS. |
| | |
| | 2)OK |
| | 4)OK |
| | 5)OK |
| | |
| | **NOTED: HOWEVER, DETAIL #5 ON SHEET A-3 SHOWS NO |
| | CHANGE. THE DOORS ARE IN THE SAME LOCATION. |
| | 6)ON SHEET A-3 DETAIL #5 THE GALLEY KITCHEN SINK |
| | SHALL MEET THE FOLLOWING REQUIREMENTS: A. 11-4.24.3 |
| | KNEE CLEARANCE / B. 11-4.24.4 SINK DEPTH ///// |
| | /C.11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH) |
| | REQUIRED MAXIMUM 19 INCHES UNDERNEATH THE SINK. NO |
| | CABINET DOORS ALLOWED IN THE CLEAR FLOOR SPACE. / D |
| | 11-4.24.6 EXPOSE PIPES & SURFACES AND E. 11-4.24.7 |
| | FAUCETS |
| | |
| | **NOTED HOWEVER, SHOWER STALLS THAT ARE 30 INCHES BY 60 |
| | INCHES MINIMUM SHALL NOT HAVE CURBS. 11-4-21.7** |
| | 7)THE SHOWER STALL SHALL MEET THE REQUIREMENTS OF FBC |
| | 11-4.21. PROVIDE ELEVATION DETAIL DRAWINGS SHOWING ALL |
| | DIMENSIONS AND ELEVATIONS FOR THE SEAT 11-4.21.3/ GRAB |
| | BARS 11-4.21.4 / CONTROLS 11-4.21.5 / SHOWER UNIT |
| | 11-4.21.6 / CURBS 11-4-21.7 / SHOWER ENCLOSURE |
| | 11-4.21.8. THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING |
| | SPACE SHALL ALSO BE INDICATED ON THE PLANS. |
| | |
| | 8)OK |
| | 9)OK |
| | 10)OK |
| | |
| | **NEW**HOW CAN A PROJECT IN THE CITY OF WEST PALM BEACH |
| | HAVE A BOCA RATON ADDRESS? ALL PAGES SHALL HAVE THE |
| | SAME ADDRESS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE WORK |
| | PROPOSED. FBC 106.1.1. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |