| 2007-12-23 09:34:43 | ** DENIED** |
| | |
| | |
| | 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE |
| | NEEDED AS FOLLOWS |
| | 2004 FBC W/2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101(SHOWS 2006) |
| | 2002 NFPA-72 (SHOWS 2007) |
| | |
| | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS |
| | LIGHTING CONTROLS ARE REQUIRED FOR ALL AREAS. FOR |
| | EXAMPLE: PLEASE SEE ROOMS 209, 231, BATHROOM ETC |
| | WITHOUT ANY CONTROLS. |
| | PLEASE LIST MAXIMUM TIMES ON DEVICES. |
| | |
| | 3) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR EGRESS |
| | THROUGH WORK STATION CUBICLE FROM BUILDING AND FIRE |
| | MARSHAL REVIEW. THIS WOULD AFFECT ELECTRICAL PLANS. |
| | THIS IS NOTED FOR INFORMATION AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE THE ELECTRICAL PANELS AND LOCATION |
| | SHOWN ARE NOT PERMITTED IN THE STORAGE ROOM. |
| | 110.26, 240.24, 408.17 |
| | |
| | 5) NOTE: PLEASE SEE THE PACKAGE AS SUBMITTED CONTAINED |
| | METHOD *A* CALCULATIONS FOR *WHOLE BUILDING*. THIS IS |
| | NOT A WHOLE BUILDING. PLEASE ALSO SEE THESE SAME |
| | CALCULATIONS ARE SHOWN WITH PROJECT LOCATED IN BOCA |
| | RATON ON SOUTH FEDERAL HWY. |
| | PLEASE KNOW AS ASSUMPTIONS WERE MADE UNDER THE BASE |
| | BUILDING AND THIS IS NOT A WHOLE BUILDING PLEASE |
| | VERIFY. PLEASE KNOW THAT IN ANY CASETHE INPUT DATA |
| | REPORT AS SUBMITTED DOES NOT COORDINATE WITH PLANS FOR |
| | NUMBER OF LIGHT FIXTURES, CONTROLS, AND WATTAGES. |
| | PLEASE SEE THE PLANS DO INDICATE THE LIGHTING |
| | PERFORMANCE CALCULATIONS HOWEVER AS THESE SHOW TABLE |
| | *C* BEING PERFORMED, THE TOTAL WATTS PER SQ FT IS |
| | EXCEED BASED ON THE OFFICE NOTED AS 1.0 PER SQ FT. |
| | PLEASE COMPLETE FIXTURE DESIGNATIONS ON PLANS WHICH |
| | CORRELATE WITH THE FIXTURE LEGEND. |
| | PLEASE BE SURE TO SEE 13-415.2 AND ADJUST CALCULATIONS |
| | AS NEEDED. |
| | |
| | 6) NOTE: PLEASE VERIFY ROOM ON PLANS WHICH IS SHOWN AS |
| | AN *IT* ROOM. THIS ROOM DOES NOT APPEAR TO CONFORM TO |
| | 645.4 OF THE NEC. IF THIS IS AN IT ROOM PLEASE ADJUST |
| | PLANS. IF THIS IS A SERVER ROOM PLEASE ADJUST |
| | DESIGNATION. |
| | |
| | 7) NOTE: PLEASE SEE 422.1, 110.26, 240.24 ETC FOR OVER |
| | CURRENT PROTECTION ON WHAT APPEARS TO BE A TANK-LESS |
| | WATER HEATER. PLEASE KNOW IF THE DISCONNECT AS SHOWN |
| | UNDER CABINET CONTAINS OVER CURRENT PROTECTION THIS |
| | WILL BE REQUIRED TO BE RELOCATED. THIS IS A FIRE/LIFE |
| | SAFETY HAZARD. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| | UNIT. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE ADDRESS IS TO BE STATED ON |
| | TITLE BLOCKS. (2475 MERCER AVE). |
| | PLEASE KNOW ONCE A SUITE OR UNIT NUMBER HAS BEEN |
| | GENERATED, THIS SHOULD ALSO BE PLACED ON PLANS. THIS |
| | HAS BEEN ROUTED TO ADDRESSING FOR SUITE/UNIT |
| | DETERMINATION. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |