| Date |
Text |
| 2007-12-31 13:41:24 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120492 |
| | ADD: 2475 ? MERCER AVE |
| | CONT: SEAL-TITE |
| | TEL: (561)346-8191 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | 12/31/07 |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 REVISIONS. |
| | |
| | 2)SHEET A-1 SHOWS WALL TYPE #4 AND #5 WITH THE SAME |
| | SYMBOL. EACH TYPE OF WALL SHALL HAVE ITS OWN SYMBOL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. FBC 106.1.1. |
| | |
| | 4)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | 5)SUBMIT AN EXISTING AND A PROPOSED FLOOR PLAN |
| | INDICATE ALL CHANGES TO THE OLD FLOOR PLAN. |
| | |
| | 6)ON SHEET A-3 DETAIL #5 THE GALLEY KITCHEN SINK |
| | SHALL MEET THE FOLLOWING REQUIREMENTS: A. 11-4.24.3 |
| | KNEE CLEARANCE / B. 11-4.24.4 SINK DEPTH ///// |
| | /C.11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH) |
| | REQUIRED MAXIMUM 19 INCHES UNDERNEATH THE SINK. NO |
| | CABINET DOORS ALLOWED IN THE CLEAR FLOOR SPACE. / D |
| | 11-4.24.6 EXPOSE PIPES & SURFACES AND E. 11-4.24.7 |
| | FAUCETS |
| | |
| | 7)THE SHOWER STALL SHALL MEET THE REQUIREMENTS OF FBC |
| | 11-4.21. PROVIDE ELEVATION DETAIL DRAWINGS SHOWING ALL |
| | DIMENSIONS AND ELEVATIONS FOR THE SEAT 11-4.21.3/ GRAB |
| | BARS 11-4.21.4 / CONTROLS 11-4.21.5 / SHOWER UNIT |
| | 11-4.21.6 / CURBS 11-4-21.7 / SHOWER ENCLOSURE |
| | 11-4.21.8. THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING |
| | SPACE SHALL ALSO BE INDICATED ON THE PLANS. |
| | |
| | 8)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 9)INDICATE IF THE GLASS IN WALL TYPE #3A IS TEMPERED |
| | OR IMPACT GLASS. THE SHOWER DOOR SHALL BE TEMPERED |
| | GLASS PER FBC 2406.3. |
| | |
| | 10)SUBMIT THE LIFE SAFETY PLAN SHOWING THE MEANS OF |
| | EGRESS WHICH SHALL INCLUDE THE EXIT ACCESS, EXIT AND |
| | THE EXIT DISCHARGE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |