| 2007-12-27 15:03:25 | |
| | *** DENIED REVIEW*** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE REFLECTED ON ELECTRICAL PLANS AND PROJECT. |
| | 2004 FBC W/2007 SUPPLEMENTS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE BE SURE ALL CODE REFERENCES ARE FROM |
| | THE MOST CURRENT ADOPTED CODES UNDER FLORIDA STATUTES |
| | 553.73 AND CHAPTER 27 OF THE FLORIDA BUILDING CODE. |
| | FOR EXAMPLE: PLEASE SEE CODE REFERENCES WHICH ARE FROM |
| | THE 1999 NEC. NOTE #20 ON E.1 |
| | |
| | 3) NOTE: PLEASE BE SURE THE SUITE/UNITNUMBER IS |
| | STATED ON TITLE BLOCKS. THIS MAY BE HAND PRINTED FOR |
| | ALL SHEETS WHICH DO NOT NEED TO BE RE-PRINTED. (SUITE # |
| | IS 158) |
| | FAC61G1-16.004, 61G15-23.002, FBC ADMIN 106.1.2, 106.5 |
| | ETC |
| | |
| | 4) NOTE: PLEASE SEE THE COLOR CODING STATED ON ES-1 FOR |
| | 277/480V SYSTEMS IS NOT CORRECT. |
| | PLEASE KNOW THE COLOR CODING SHALL BE AS FOLLOWS (A) |
| | BROWN, (B) PURPLE AND (C) YELLOW. THESE SEEM TO HAVE |
| | BEEN REVERSED OR MISPRINTED. |
| | AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND ARE OF |
| | PRIVATE PROVIDER THESE CAN NOT BE RED-LINED. |
| | 210.5, 215.12, 90.4 |
| | |
| | 5) NOTE: PLEASE SEE 422.11 AND 422.13 AS THE MINIMUM |
| | BRANCH CIRCUIT SIZING AND OVERCURRENT PROTECTION FOR |
| | THE WATERS HEATERS SHALL BE 125%. |
| | PLEASE SEE THE WATER HEATERS AND LOAD AS SHOWN DOES NOT |
| | CONTAIN THE 1255 SIZING FOR BRANCH CIRCUIT CONDUCTORS |
| | AND OCP. |
| | PLEASE ADJUST. |
| | |
| | 6) NOTE: PLEASE SEE 220.43B AND SHOW ON LOAD |
| | CALCULATIONS HOW THE TRACK LIGHTING REQUIRED LOADS WERE |
| | FIGURED INTO SERVICE. |
| | |
| | 7) NOTE: PLEASE CLARIFY NOTE ON THE LIGHTING |
| | CALCULATIONS ON SHEET E-2 WHICH STATES *BUILDING |
| | DEPARTMENT NOTES*. THIS IS THE FIRST REVIEW UNDER |
| | PERMIT APPLICATION FOR THIS PROJECT. PLEASE EXPLAIN. |
| | PLEASE SEE METHOD *B* CALCULATIONS UNDER THE 2004 FBC |
| | BEFORE CODE CHANGES OF DECEMBER 8TH, 2006 WERE |
| | SUBMITTED. (VERSION 2.11 SUBMITTED MAY NOT BE USED |
| | AFTER DATE ABOVE. |
| | PLEASE SEE 13-400.3.B |
| | PLEASE EXPLAIN HOW THESE MAY BE SUBMITTED AND USED. |
| | PLEASE ALSO SEE COMMENTS FROM MECHANICAL REVIEWER FOR |
| | INFORMATION WHICH IS PLACED IN THE INPUT DATA REPORT |
| | WHICH DOES NOT CORRELATE WITH ACTUAL KNOWN COMPONENTS |
| | OF THE EXISTING BUILDING. |
| | PLEASE SEE 13-415.2.ABC.1.2 (1) AND CLARIFY IF ALL |
| | WATTAGES FIGURED ARE BASED ON FIXTURES AND NOT BULBS |
| | AND PART (2) THE VA RATING OF THE BALLAST. |
| | PLEASE SEE 13-415.2.ABC.1.3 AS THE PLANS DO INDICATE |
| | EXTERIOR LIGHTS YET THESE ARE NOT SHOWN ON THE LIGHTING |
| | PERFORMANCE CALCULATIONS ON PLANS AND THEY ARE SHOWN ON |
| | THE IDR. |
| | PLEASE COMPLETE FIXTURE INFORMATION AND FIXTURE LEGEND. |
| | |
| | PLEASE VERIFY ALLOWANCES GIVEN FOR STATED FUTURE LIGHT |
| | FIXTURE AS NOTED IN CODED NOTE #4. |
| | *** PLEASE VERIFY THAT COMMON AREA FIXTURES AS SHOWN |
| | ARE INDEED FED FROM THE TENANT ELECTRICAL SERVICE AND |
| | SPACE. |
| | |
| | 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). PLEASE |
| | SHOW THE MINIMUM LEVELS OF DEVICES ON PLANS FOR ADA |
| | COMPLIANCE. |
| | |
| | 9) NOTE: PLEASE SHEET ED-1 NOTE FOR DOOR SYSTEM STATES |
| | RECEPTACLE TO BE INSTALLED ABOVE CEILING. PLEASE SEE |
| | 400.8 (1-7) AS THIS IS NOT PERMITTED FOR USE AS SHOWN. |
| | |
| | 10) NOTE: PLEASE SEE LIGHTING PLANS WHICH ONLY SHOWN |
| | ONE OVER RIDE SWITCH AT THE REAR DOOR AS NOTED ON |
| | LIGHTING CODED NOTES# 3. |
| | PLEASE CORRELATE AND SHOW LOCATIONS. |
| | 13-415.1.ABC.1.1 AND .1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE ELECTRICAL PLANS CONTAIN NOT |
| | CONTAIN SCALE ON SHEETS. |
| | PLEASE CLARIFY WHERE THIS IS SHOWN. |
| | 110.26, |
| | FBC 106.3.1 MIN SCALE REQUIREMENTS. |
| | |
| | 12) NOTE: PLEASE SEE 210.62 AS THE SHOW WINDOW |
| | RECEPTACLES SHALL BE ABOVE WINDOW(S). PLEASE SEE NOTE |
| | ON PLANS STATES BELOW WINDOW WHICH IS NOT PERMITTED. |
| | THIS IS DIFFERENT FROM THE OTHER NOTE ON PLANS WHICH |
| | MENTIONS *ABOVE WINDOW* |
| | PLEASE CLARIFY WHICH DEVICES ARE ABOVE WINDOW; PLEASE |
| | SEE AS NOTED ABOVE IN NOTE #9, ABOVE WINDOW MAY NOT BE |
| | ABOVE CEILING. |
| | |
| | 13) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE ONLY |
| | THE LOW VOLTAGE WHICH IS SHOWN ON PLANS IS REQUIRED TO |
| | BE UNDER SEPARATE PERMIT(S). |
| | THESE PLANS MAY BE REFERENCED FOR WORK. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |