Plan Review Notes
Plan Review Notes For Permit 07120491
Permit Number 07120491
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-27 15:03:25 
 *** DENIED REVIEW***
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE REFLECTED ON ELECTRICAL PLANS AND PROJECT.
 2004 FBC W/2007 SUPPLEMENTS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE BE SURE ALL CODE REFERENCES ARE FROM
 THE MOST CURRENT ADOPTED CODES UNDER FLORIDA STATUTES
 553.73 AND CHAPTER 27 OF THE FLORIDA BUILDING CODE.
 FOR EXAMPLE: PLEASE SEE CODE REFERENCES WHICH ARE FROM
 THE 1999 NEC. NOTE #20 ON E.1
  
 3) NOTE: PLEASE BE SURE THE SUITE/UNITNUMBER IS
 STATED ON TITLE BLOCKS. THIS MAY BE HAND PRINTED FOR
 ALL SHEETS WHICH DO NOT NEED TO BE RE-PRINTED. (SUITE #
 IS 158)
 FAC61G1-16.004, 61G15-23.002, FBC ADMIN 106.1.2, 106.5
 ETC
  
 4) NOTE: PLEASE SEE THE COLOR CODING STATED ON ES-1 FOR
 277/480V SYSTEMS IS NOT CORRECT.
 PLEASE KNOW THE COLOR CODING SHALL BE AS FOLLOWS (A)
 BROWN, (B) PURPLE AND (C) YELLOW. THESE SEEM TO HAVE
 BEEN REVERSED OR MISPRINTED.
 AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND ARE OF
 PRIVATE PROVIDER THESE CAN NOT BE RED-LINED.
 210.5, 215.12, 90.4
  
 5) NOTE: PLEASE SEE 422.11 AND 422.13 AS THE MINIMUM
 BRANCH CIRCUIT SIZING AND OVERCURRENT PROTECTION FOR
 THE WATERS HEATERS SHALL BE 125%.
 PLEASE SEE THE WATER HEATERS AND LOAD AS SHOWN DOES NOT
 CONTAIN THE 1255 SIZING FOR BRANCH CIRCUIT CONDUCTORS
 AND OCP.
 PLEASE ADJUST.
  
 6) NOTE: PLEASE SEE 220.43B AND SHOW ON LOAD
 CALCULATIONS HOW THE TRACK LIGHTING REQUIRED LOADS WERE
 FIGURED INTO SERVICE.
  
 7) NOTE: PLEASE CLARIFY NOTE ON THE LIGHTING
 CALCULATIONS ON SHEET E-2 WHICH STATES *BUILDING
 DEPARTMENT NOTES*. THIS IS THE FIRST REVIEW UNDER
 PERMIT APPLICATION FOR THIS PROJECT. PLEASE EXPLAIN.
 PLEASE SEE METHOD *B* CALCULATIONS UNDER THE 2004 FBC
 BEFORE CODE CHANGES OF DECEMBER 8TH, 2006 WERE
 SUBMITTED. (VERSION 2.11 SUBMITTED MAY NOT BE USED
 AFTER DATE ABOVE.
 PLEASE SEE 13-400.3.B
 PLEASE EXPLAIN HOW THESE MAY BE SUBMITTED AND USED.
 PLEASE ALSO SEE COMMENTS FROM MECHANICAL REVIEWER FOR
 INFORMATION WHICH IS PLACED IN THE INPUT DATA REPORT
 WHICH DOES NOT CORRELATE WITH ACTUAL KNOWN COMPONENTS
 OF THE EXISTING BUILDING.
 PLEASE SEE 13-415.2.ABC.1.2 (1) AND CLARIFY IF ALL
 WATTAGES FIGURED ARE BASED ON FIXTURES AND NOT BULBS
 AND PART (2) THE VA RATING OF THE BALLAST.
 PLEASE SEE 13-415.2.ABC.1.3 AS THE PLANS DO INDICATE
 EXTERIOR LIGHTS YET THESE ARE NOT SHOWN ON THE LIGHTING
 PERFORMANCE CALCULATIONS ON PLANS AND THEY ARE SHOWN ON
 THE IDR.
 PLEASE COMPLETE FIXTURE INFORMATION AND FIXTURE LEGEND.
  
 PLEASE VERIFY ALLOWANCES GIVEN FOR STATED FUTURE LIGHT
 FIXTURE AS NOTED IN CODED NOTE #4.
 *** PLEASE VERIFY THAT COMMON AREA FIXTURES AS SHOWN
 ARE INDEED FED FROM THE TENANT ELECTRICAL SERVICE AND
 SPACE.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). PLEASE
 SHOW THE MINIMUM LEVELS OF DEVICES ON PLANS FOR ADA
 COMPLIANCE.
  
 9) NOTE: PLEASE SHEET ED-1 NOTE FOR DOOR SYSTEM STATES
 RECEPTACLE TO BE INSTALLED ABOVE CEILING. PLEASE SEE
 400.8 (1-7) AS THIS IS NOT PERMITTED FOR USE AS SHOWN.
  
 10) NOTE: PLEASE SEE LIGHTING PLANS WHICH ONLY SHOWN
 ONE OVER RIDE SWITCH AT THE REAR DOOR AS NOTED ON
 LIGHTING CODED NOTES# 3.
 PLEASE CORRELATE AND SHOW LOCATIONS.
 13-415.1.ABC.1.1 AND .1.2
  
 11) NOTE: PLEASE SEE THE ELECTRICAL PLANS CONTAIN NOT
 CONTAIN SCALE ON SHEETS.
 PLEASE CLARIFY WHERE THIS IS SHOWN.
 110.26,
 FBC 106.3.1 MIN SCALE REQUIREMENTS.
  
 12) NOTE: PLEASE SEE 210.62 AS THE SHOW WINDOW
 RECEPTACLES SHALL BE ABOVE WINDOW(S). PLEASE SEE NOTE
 ON PLANS STATES BELOW WINDOW WHICH IS NOT PERMITTED.
 THIS IS DIFFERENT FROM THE OTHER NOTE ON PLANS WHICH
 MENTIONS *ABOVE WINDOW*
 PLEASE CLARIFY WHICH DEVICES ARE ABOVE WINDOW; PLEASE
 SEE AS NOTED ABOVE IN NOTE #9, ABOVE WINDOW MAY NOT BE
 ABOVE CEILING.
  
 13) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE ONLY
 THE LOW VOLTAGE WHICH IS SHOWN ON PLANS IS REQUIRED TO
 BE UNDER SEPARATE PERMIT(S).
 THESE PLANS MAY BE REFERENCED FOR WORK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]