| 2007-12-21 13:18:39 | REVIEW #: 1ST |
| | ACTION: PASSED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: METHOD B ENERGY CALCULATIONS HAVE BEEN PROVIDED |
| | WITH THIS PERMIT APPLICATION. THESE CALCULATIONS HAVE |
| | NOT BEEN REVIEWED FOR THE PURPOSE OF BEING INCLUDED IN |
| | THE PERMIT SET OF PLANS FOR THE FOLLOWING REASONS: |
| | A) FORM 400B-2004 V2.11 HAS BEEN SUBMITTED. AS OF |
| | DECEMBER 8, 2006, THE CORRECT FORM IS 400B-04R (V2.5 OR |
| | HIGHER) IN ACCORDANCE WITH FBC 13-400.3.B. |
| | B) IF THIS FORM WERE TO BE USED TO DEMONSTRATE |
| | COMPLIANCE, IT HAS NOT BEEN ACCURATELY COMPLETED AS |
| | REQUIRED BY THE SAME SECTION. EXAMPLE: THIS IS A FIRST |
| | FLOOR TENANT SPACE IN A TWO STORY BUILDING. IT IS NOT |
| | POSSIBLE FOR THIS SPACE TO HAVE A METAL BUILDING ROOF |
| | WITH R-19 BATTS AS INDICATED IN THE INPUT DATA REPORT. |
| | C) THIS WORK IS WITHIN THE CONFINES OF AN EXISTING |
| | BUILDING AND THE WORK PERFORMED DOES NOT MEET THE |
| | THRESHOLD FOR A RENOVATION AS DEFINED IN FBC 13-202. |
| | THEREFORE COMPLIANCE WITH FBC CHAPTER 13 IS SUBJECT TO |
| | FBC 13-400.0.C.4 AND FBC 13-101.6. METHOD B IS NOT AN |
| | APPLICABLE COMPLIANCE METHOD FOR THIS SPACE. |
| | |
| | THIS DOES NOT HAVE AN IMPACT ON MECHANICAL CODE |
| | COMPLIANCE FOR THIS PROJECT AS ALL COMPONENTS SHOWN ON |
| | PLANS RELATED TO MECHANICAL, SUCH AS DUCTWORK, |
| | INSULATION AND THE AHU, ARE WITHIN THE MINIMUM |
| | PRESCRIPTIVE REQUIREMENTS OF CHAPTER 13. THIS NOTE IS |
| | ONLY TO SERVE AS NOTICE THAT THE METHOD B FORM |
| | SUBMITTED WAS NOT CONSIDERED AS PART OF THIS |
| | APPLICATION AND WILL NOT BE INCLUDED AS PART OF THE |
| | PERMIT RECORD. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |
| | |