| 2007-12-20 16:58:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. NOTE: THERE IS NOT AN APPROVED GENERATOR FOR THIS |
| | RESIDENCE. THE REFERENCED GENERATOR FOR THE PROPOSED |
| | GAS SYSTEM WILL NEED A SEPERATE PERMIT. PLEASE |
| | REFERENCE THE RESIDENTIAL GENERATOR PLAN REVIEW |
| | REQUIREMENTS ATTACHED TO THESE GAS COMMENTS FOR |
| | INFORMATION REQUIRED FOR THAT PERMIT. A GAS PERMIT CAN |
| | NOT BE ISSUED UNTIL A GEN/RES PERMIT APPLICATION HAS |
| | BEEN APPLIED FOR AND APPROVED BY ZONING FOR THE |
| | GENERATOR LOCATION. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE |
| | CORRESPONDING LENGTHS INDICATED AS REQUIRED. REFERENCE |
| | THE YELLOW HIGHLIGHTER WITH MISSING CORRESPONDING |
| | LENGTHS. |
| | |
| | 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | **NOTE: THIS VALVE IS NOT ON THE SUBMITTED GAS RISER |
| | DIAGRAM. PLEASE INDICATE THIS REQUIRED VALVE ON THE |
| | RESUBMITTAL. |
| | |
| | 4. NOTE: THE MP REGULATOR FOR THE POOL HEATER WILL |
| | NEED TO BE A MAXITROL 325-7L. THE INDICATED MAXITROL |
| | 325-5AL FOR MAXIMUM INDIVIDUAL LOAD IS ONLY GOOD FOR |
| | 300,000 BTU'S. THE POOL HEATER IS 400,000 BTU'S. PLEASE |
| | INDICATE THIS REQUIRED CHANGE ON THE RESUBMITTAL. |
| | |
| | 5. SUBMIT TWO COPIES OF SURVEY OR SITE PLANS |
| | INDICATING THE PROPOSED LOCATION OF THE GENERATOR. |
| | INDICATE ALL DIMENSIONS FROM PROPERTY LINES AND ALL |
| | STRUCTURES OF THE PROPOSED GENERATOR. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NOTE: SHEETS REQUIRED FOR THE GENERATOR, COOK TOP, |
| | STOVE, WATER HEATER, AND POOL HEATER TO VERIFY THE BTU |
| | LOAD AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL). FOR THE GENERATOR MANUFACTURER |
| | SETBACK RECOMMENDATIONS FROM STRUCTURES IS ALSO |
| | REQUIRED. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |