| Plan Review Notes For Permit 07120476 |
| Permit Number |
07120476 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-01-08 12:22:28 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.FOUR DIFFERENT NOAS FOR DOORS WAS SUBMITTD, TWO ARE | | | EXPIRED.PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE | | | DOORS YOU ARE INTSTALLING.IF YOU ARE INSTALLING MORE | | | THAN ONE TYPE OF DOOR, INDICATE LOCATION AND TYPE ON | | | THE FLOOR PLAN. | | | | | | 2ND REVIEW, NOT ADDRESSED. | | | | | | 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR | | | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED. | | | | | | 2ND REVIEW, RETURNED INCOMPLETE.SHUTTER CONNECTION | | | MOUNTING TYPE SHOULD CORRELATE WITH THE ANCHOR SCHEDULE | | | ON THE PRODUCT APPROVAL.THE ANCHOR SPACING WAS LEFT | | | BLANK. | | | | | | 3.NEW COMMENT; SUBMIT TWO IDENTIAL, COLLATED SETS FOR | | | PERMIT ISSUANCE.REMOVE UNNECESSARY PAPERWORK. | | | | | | |
|