Plan Review Notes
Plan Review Notes For Permit 07120476
Permit Number 07120476
Review Stop B
Sequence Number 2
Notes
Date Text
2008-01-08 12:22:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.FOUR DIFFERENT NOAS FOR DOORS WAS SUBMITTD, TWO ARE
 EXPIRED.PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE
 DOORS YOU ARE INTSTALLING.IF YOU ARE INSTALLING MORE
 THAN ONE TYPE OF DOOR, INDICATE LOCATION AND TYPE ON
 THE FLOOR PLAN.
  
 2ND REVIEW, NOT ADDRESSED.
  
 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
  
 2ND REVIEW, RETURNED INCOMPLETE.SHUTTER CONNECTION
 MOUNTING TYPE SHOULD CORRELATE WITH THE ANCHOR SCHEDULE
 ON THE PRODUCT APPROVAL.THE ANCHOR SPACING WAS LEFT
 BLANK.
  
 3.NEW COMMENT; SUBMIT TWO IDENTIAL, COLLATED SETS FOR
 PERMIT ISSUANCE.REMOVE UNNECESSARY PAPERWORK.
  
  