Plan Review Notes
Plan Review Notes For Permit 07120462
Permit Number 07120462
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-26 15:31:32 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A PANEL SCHEDULE FOR THE PANEL FEEDING THE
 NEW EQUIPMENT AS IT IS CURRENTLY, PER 408.4. INCLUDE
 OCP AND CONDUCTOR SIZES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718