| 2008-01-17 16:58:32 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | **PREVIOUS PLAN REVIEW COMMENTS** |
| | |
| | 1. **OK** COMMENT ADDRESSED. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. NOTE: COMMENT RESPONSE NOTED, HOWEVER SEE NEW |
| | COMMENTS BELOW ORIGINAL COMMENT. |
| | **PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| | PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS |
| | REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND |
| | COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS, |
| | LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW |
| | PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE |
| | WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER |
| | ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED |
| | (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) |
| | **604.9. |
| | |
| | **NEW COMMENTS FOR COMMENT #3** |
| | |
| | A} ADD COLD WATER SUPPLY AND WATER-HAMMER ARRESTOR FOR |
| | ICE MAKER "G". PER FBC PLUMBING SECTION *601.1 SCOPE |
| | AND SECTION *604.9 WATER HAMMER. |
| | |
| | B} INDICATE WATER-HAMMER ARRESTORS FOR WASHING MACHINE |
| | CLOSER TO THE WATER OUTLET PER MANUFACTURER'S |
| | RECOMMENDATIONS, NOT ON TOP OF RISER. PER FBC PLUMBING |
| | SECTION *601.1 SCOPE AND SECTION *604.9 WATER HAMMER. |
| | |
| | C} PLEASE CORRECT THE FOLLOWING: THE HOT AND COLD |
| | WATER ARE CROSSED (COLD SHOULD BE ON THE RIGHT AND HOT |
| | SHOULD BE ON THE ON LEFT) FOR THE WASHING MACHINE AND |
| | THE HAND SINK BY THE 3 COMP. SINK. PER FBC PLUMBING |
| | SECTION *601.1 SCOPE. |
| | |
| | D} PLEASE DELETE THE FOLLOWING: THE EXTRA COLD WATER |
| | FOR THE 3 COMP. SINK OR IDENTIFY WHAT IT IS FOR AND THE |
| | TEE FITTINGS FOR BOTH THE COLD AND HOT WATER AFTER THE |
| | VALVES TO THE 3 COMP. SINKS. PER FBC PLUMBING SECTION |
| | *601.1 SCOPE. |
| | |
| | E} PLEASE CLEARLY INDICATE THAT THERE IS AN EXISTING |
| | BACKFLOW PREVENTER OR A NEW ONE WILL BE INSTALLED AND |
| | THAT THE EXISTING WATER HEATER IS PROTECTED FROM |
| | EXPANSION CONTROL. PER FBC PLUMBING SECTIONS 608 AND |
| | 607.3. |
| | |
| | 4. **OK** COMMENT ADDRESSED. |
| | |
| | 5. **OK** COMMENT ADDRESSED. |
| | |
| | 6. **OK** COMMENT ADDRESSED. |
| | |
| | 7. **OK** COMMENT ADDRESSED. |
| | |
| | 8. **OK** COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |