2008-01-17 16:58:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS PLAN REVIEW COMMENTS**
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. NOTE: COMMENT RESPONSE NOTED, HOWEVER SEE NEW
 COMMENTS BELOW ORIGINAL COMMENT.
 **PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 **NEW COMMENTS FOR COMMENT #3**
  
 A} ADD COLD WATER SUPPLY AND WATER-HAMMER ARRESTOR FOR
 ICE MAKER "G". PER FBC PLUMBING SECTION *601.1 SCOPE
 AND SECTION *604.9 WATER HAMMER.
  
 B} INDICATE WATER-HAMMER ARRESTORS FOR WASHING MACHINE
 CLOSER TO THE WATER OUTLET PER MANUFACTURER'S
 RECOMMENDATIONS, NOT ON TOP OF RISER. PER FBC PLUMBING
 SECTION *601.1 SCOPE AND SECTION *604.9 WATER HAMMER.
  
 C} PLEASE CORRECT THE FOLLOWING: THE HOT AND COLD
 WATER ARE CROSSED (COLD SHOULD BE ON THE RIGHT AND HOT
 SHOULD BE ON THE ON LEFT) FOR THE WASHING MACHINE AND
 THE HAND SINK BY THE 3 COMP. SINK. PER FBC PLUMBING
 SECTION *601.1 SCOPE.
  
 D} PLEASE DELETE THE FOLLOWING: THE EXTRA COLD WATER
 FOR THE 3 COMP. SINK OR IDENTIFY WHAT IT IS FOR AND THE
 TEE FITTINGS FOR BOTH THE COLD AND HOT WATER AFTER THE
 VALVES TO THE 3 COMP. SINKS. PER FBC PLUMBING SECTION
 *601.1 SCOPE.
  
 E} PLEASE CLEARLY INDICATE THAT THERE IS AN EXISTING
 BACKFLOW PREVENTER OR A NEW ONE WILL BE INSTALLED AND
 THAT THE EXISTING WATER HEATER IS PROTECTED FROM
 EXPANSION CONTROL. PER FBC PLUMBING SECTIONS 608 AND
 607.3.
  
 4. **OK** COMMENT ADDRESSED.
  
 5. **OK** COMMENT ADDRESSED.
  
 6. **OK** COMMENT ADDRESSED.
  
 7. **OK** COMMENT ADDRESSED.
  
 8. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731