| 2008-01-15 10:59:57 | |
| | |
| | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE SEE ALMOST EVERY COMMENT FROM THE PREVIOUS |
| | REVIEW IS THE EXACT SAME COMMENT WITHOUT ANY CHANGES OR |
| | CORRECTIONS MADE. |
| | ** THERE ARE RESPONSE LETTERS FOR PLUMBING REVIEW |
| | HOWEVER NOT FOR ELECTRICAL OR OTHER TRADES. |
| | |
| | |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE BE SURE |
| | ADDRESS COMMENTS. THIS IS ONLY AN NOTICE AT THIS TIME. |
| | ONE SET OF PLANS WILL BE RETAINED |
| | |
| | 2) NOTE:SAME COMMENT: |
| | PLEASE SEE CODES TO BE STATED ON PLANS ARE NEEDED AS |
| | FOLLOWS |
| | 2004 FBC W/2007 REVISIONS |
| | 2005 NFPA-70 (SHOWS 2002) |
| | 2003 NFPA-101 |
| | |
| | 3) NOTE:SAME COMMENT: |
| | PLEASE SEE WHAT APPEARS TO BE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER PER FAC 61G1-16.004 AND FS |
| | 481.219. PLEASE SEE FS 481.219 AS STATED AS A *DESIGN |
| | FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY NOT |
| | DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM AS |
| | SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE PROVIDE |
| | THE CA NUMBER AS REQUIRED. |
| | PLEASE CONFIRM. |
| | |
| | 4) NOTE: SAME COMMENT: |
| | PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW AND |
| | INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR |
| | CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL |
| | BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN |
| | THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL |
| | SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS |
| | INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON |
| | PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF |
| | MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE |
| | SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED. |
| | NEC 408.4, 310.16, 240.4 ETC |
| | FBC106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE:SAME COMMENT: CALCULATIONS WERE ADJUSTED WITH |
| | SOME MINOR CHANGES HOWEVER THEYA RE NOT CODE COMPLIANT |
| | FOR COMMERCIAL. |
| | |
| | PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON PANEL ARE |
| | THAT FOR A RESIDENCE. PLEASE SEE 220.12, 220.14, |
| | 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42 FOR |
| | CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%. PLEASE |
| | SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR SIGN |
| | CIRCUIT IS 1200VA. |
| | PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE |
| | SHOWN PER 220.43 |
| | PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET |
| | COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT |
| | CALCULATIONS CAN NOT BE DONE AT THIS TIME. |
| | |
| | 6) NOTE:SAME COMMENT: |
| | PLEASE SEE THE PLANS INDICATE TWO PANELS YET THE PLANS |
| | ONLY SHOW ONE? |
| | PLEASE COMPLETE AND CORRELATE. |
| | 408.4, 240.24, ETC |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | |
| | 7) NOTE: SAME COMMENT: |
| | PLEASE SEE THE DRYER AS SHOWN ON PANEL SCHEDULE IS |
| | SHOWN AS 5KW YET THE BRANCH CIRCUIT IS SHOWN AS A |
| | 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD EXCEEDS |
| | THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT A |
| | 2-POLE CIRCUIT? |
| | PLEASE SEE 240.4, 310.16, ETC |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: COMMENT OK FOR COOLER UNDER SEPARATE PERMIT. |
| | |
| | 9) NOTE:SAME COMMENT: |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED |
| | SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS |
| | A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K |
| | SQ FT. |
| | PLEASE CLEARLY SHOW NEW WORK AND EXISTING. |
| | PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2. |
| | PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME |
| | AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE |
| | COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON |
| | FIXTURES AS SHOWN. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 10) NOTE: SAME COMMENT: |
| | PLEASE CLARIFY WHAT APPEARS TO BE A FIRE ALARM DEVICE |
| | ON PLANS. PLANS INDICATE A FA IN A BOX HOWEVER AS THE |
| | SYMBOL LEGEND DOES NOT SHOW THIS IT IS UNCLEAR WHAT |
| | THIS IS? |
| | PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE |
| | SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR |
| | ADA. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |