Plan Review Notes
Plan Review Notes For Permit 07120459
Permit Number 07120459
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-15 10:59:57 
  
 ** DENIED2ND REVIEW **
  
 ** PLEASE SEE ALMOST EVERY COMMENT FROM THE PREVIOUS
 REVIEW IS THE EXACT SAME COMMENT WITHOUT ANY CHANGES OR
 CORRECTIONS MADE.
 ** THERE ARE RESPONSE LETTERS FOR PLUMBING REVIEW
 HOWEVER NOT FOR ELECTRICAL OR OTHER TRADES.
  
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE BE SURE
 ADDRESS COMMENTS. THIS IS ONLY AN NOTICE AT THIS TIME.
 ONE SET OF PLANS WILL BE RETAINED
  
 2) NOTE:SAME COMMENT:
 PLEASE SEE CODES TO BE STATED ON PLANS ARE NEEDED AS
 FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70 (SHOWS 2002)
 2003 NFPA-101
  
 3) NOTE:SAME COMMENT:
 PLEASE SEE WHAT APPEARS TO BE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER PER FAC 61G1-16.004 AND FS
 481.219. PLEASE SEE FS 481.219 AS STATED AS A *DESIGN
 FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY NOT
 DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM AS
 SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE PROVIDE
 THE CA NUMBER AS REQUIRED.
 PLEASE CONFIRM.
  
 4) NOTE: SAME COMMENT:
 PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW AND
 INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR
 CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL
 BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN
 THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL
 SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS
 INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON
 PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF
 MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE
 SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED.
 NEC 408.4, 310.16, 240.4 ETC
 FBC106.1.2, 106.3.5.1.2
  
 5) NOTE:SAME COMMENT: CALCULATIONS WERE ADJUSTED WITH
 SOME MINOR CHANGES HOWEVER THEYA RE NOT CODE COMPLIANT
 FOR COMMERCIAL.
  
 PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON PANEL ARE
 THAT FOR A RESIDENCE. PLEASE SEE 220.12, 220.14,
 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42 FOR
 CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%. PLEASE
 SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR SIGN
 CIRCUIT IS 1200VA.
 PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE
 SHOWN PER 220.43
 PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET
 COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT
 CALCULATIONS CAN NOT BE DONE AT THIS TIME.
  
 6) NOTE:SAME COMMENT:
 PLEASE SEE THE PLANS INDICATE TWO PANELS YET THE PLANS
 ONLY SHOW ONE?
 PLEASE COMPLETE AND CORRELATE.
 408.4, 240.24, ETC
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 7) NOTE: SAME COMMENT:
 PLEASE SEE THE DRYER AS SHOWN ON PANEL SCHEDULE IS
 SHOWN AS 5KW YET THE BRANCH CIRCUIT IS SHOWN AS A
 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD EXCEEDS
 THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT A
 2-POLE CIRCUIT?
 PLEASE SEE 240.4, 310.16, ETC
 FBC 106.1.2
  
 8) NOTE: COMMENT OK FOR COOLER UNDER SEPARATE PERMIT.
  
 9) NOTE:SAME COMMENT:
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED
 SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS
 A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K
 SQ FT.
 PLEASE CLEARLY SHOW NEW WORK AND EXISTING.
 PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME
 AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE
 COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON
 FIXTURES AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: SAME COMMENT:
 PLEASE CLARIFY WHAT APPEARS TO BE A FIRE ALARM DEVICE
 ON PLANS. PLANS INDICATE A FA IN A BOX HOWEVER AS THE
 SYMBOL LEGEND DOES NOT SHOW THIS IT IS UNCLEAR WHAT
 THIS IS?
 PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE
 SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR
 ADA.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]