Plan Review Notes
Plan Review Notes For Permit 07120459
Permit Number 07120459
Review Stop B
Sequence Number 2
Notes
Date Text
2008-01-15 16:34:30 
 BUILDING PLAN REVIEW
 PERMIT: 07120459
 ADD: 8989 OKEECHOBEE BLVD #212
 CONT: CHOEN INC.
 TEL: (561)362-4217
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 1/15/08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **NO RESPONSE NOT ADDRESSED**
 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)THE SQUARE FOOTAGE PER OCCUPANT LOAD FOR A
 MERCANTILE OCCUPANCY IS NOT 15. SEE FBC TABLE 1004.1.2
 FOR THE CORRECT SQUARE FOOTAGE PER OCCUPANT LOAD.
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE ACCESSIBLE COUNTER ON SHEET A1 SHALL INDICATE
 THE HEIGHT AND LENGTH OF THE COUNTER. FBC 11-7(2) (I)
 STATES, A PORTION OF THE MAIN COUNTER SHALL BE A
 MINIMUM OF 36 INCHES IN LENGTH AND 36 INCH HIGH. SEE
 SECTION 11-7 FOR MORE INFORMATION PERTAINING CHECK-OUT
 AISLES.
  
 **NO RESPONSE NOT ADDRESSED**
 4)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PERTAINING TO
 THE PROJECT. SEE SECTIONS 303, 304 AND 305 OF THIS
 CODE.
  
 **NO RESPONSE NOT ADDRESSED**
 5) ON THE APPLICATION CLEARLY DESCRIBE THE PROJECT TO
 AVOID DELAYS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. FBC
 106.1.1.INDICATE THE WIDTH OF EACH AISLE ON THE
 PLANS.
  
 **NO RESPONSE NOT ADDRESSED**
 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 **NEW**
 A)THE NEW DRINKING FOUNTAIN LOCATION WILL HAVE TO
 COMPLY WITH FBC 1016.2 (EXCEPTIONS) #2. THE CORRIDOR
 WIDTH SHALL BE 36 INCHES WHEN THE OCCUPANT LOAD IS 50
 OR LESS. THE INSTALLATION OF THE DRINKING FOUNTAIN AT
 THIS LOCATION WILL PROHIBIT A PERSON IN A WHEELCHAIR
 ACCESS TO THE BATHROOM. THE SPACE INDICATED ON THE
 DRAWINGS IS 30 INCHES. SHEET A2 SHOWS FOUR DIFFERENT
 TYPES OF DRINKING FOUNTAINS; CIRCLE THE ONE WHICH WILL
 BE INSTALLED.
 .
 B)61G1-16.004 THE TITLE BLOCK ON THE DRAWINGS SHALL
 INCLUDE.
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]