| Date |
Text |
| 2007-12-27 11:46:57 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A1 SANITARY ISOMETRIC PLUMBING RISER DIAGRAM: |
| | THE TWO 3 COMPARTMENT SINKS SHALL DISCHARGE THROUGH AN |
| | INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. PER |
| | *802.1.1, FOOD HANDLING. SIZING OF THE COMBINATION |
| | WASTE AND VENT SYSTEM SHALL BE PER SECTION *912, TABLE |
| | *912.3. |
| | |
| | 2. A DRINKING FOUNTAIN IS REQUIRED PER TABLE *403.1(6) |
| | MERCANTILE AND SHALL BE ACCESSIBLE PER THE FOLLOWING |
| | REQUIREMENTS. |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| | PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS |
| | REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND |
| | COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS, |
| | LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW |
| | PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE |
| | WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER |
| | ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED |
| | (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) |
| | **604.9. |
| | |
| | 4. SHEET A1 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY |
| | INDICATE ON THE RESUBMITTAL THE FOLLOWING FOR THE |
| | WASHING MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | **INDICATE THE REQUIRED STANDPIPE. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED AT |
| | 4' A.F.F. |
| | |
| | 5. SHEET A1 SANITARY ISOMETRIC RISER DIAGRAM: PER |
| | *708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| | THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE JUNCTION OF |
| | THE BUILDING DRAIN AND THE BUILDING SEWER. **CLEARLY |
| | INDICATE THAT THERE IS AN EXISTING ONE OR THAT A NEW |
| | ONE WILL BE PROVIDED ON THE RESUBMITTAL. |
| | |
| | 6. SHEET A1 NEW FLOOR PLAN WALK-IN COOLER: CLEARLY |
| | INDICATE IF THIS COOLER WILL HAVE A CONENSATE DRAIN AND |
| | WHERE IT WILL DISCHARGE. |
| | 314.2.1 CONDENSATE DISPOSAL. |
| | CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL |
| | BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED |
| | PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO |
| | A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A |
| | NUISANCE. |
| | |
| | 7. SHEET A1 EXISTING FLOOR PLAN DEMOLITION. |
| | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE |
| | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS |
| | SHALL BE PROHIBITED. A PLUMBING PERMIT AND INSPECTION |
| | REQUIRED OF DEMO WORK PRIOR TO COVERING DEMO WORK WITH |
| | FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS. |
| | **CLEARLYINDICATE THESE REQUIREMENTS ON THE |
| | RESUBMITTED PLANS. |
| | |
| | 8. SHEET A1 PLUMBING NOTES #3 PLEASE DELETE AND ADD |
| | THE FOLLOWING: MINIMUM SLOPE OF HORIZONTAL DRAINAGE |
| | PIPE PER TABLE *704.1. PIPE SIZE 2-1/2" OR LESS MINIMUM |
| | SLOPE IS 1/4" PER FOOT, PIPE 3" TO 6" MINIMUM SLOPE IS |
| | 1/8" PER FOOT, PIPE 8" OR LARGER MINIMUM SLOPE IS 1/16" |
| | PER FOOT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |
| | |