Plan Review Notes
Plan Review Notes For Permit 07120459
Permit Number 07120459
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-12-28 10:44:38***DENIED***
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE.
  
 2) MINIMUM RATED 2A- 10B,CFIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT DISTANCES NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 3) STORAGE SHELVING SHALL NOT OBSTRUCT OR INTERFERE
 WITH FIRE SPRINKLER COVERAGE.
  
 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 5) PLEASE CLARIFY FA AS THAT SYMBOL IS NOT REFLECTED ON
 PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756