| Plan Review Notes For Permit 07120459 |
| Permit Number |
07120459 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-28 10:44:38 | ***DENIED*** | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE. | | | | | | 2) MINIMUM RATED 2A- 10B,CFIRE EXTINGUISHERS ARE | | | REQUIRED TO BE MOUNTED AT DISTANCES NOT TO EXCEED 75' | | | TRAVEL DISTANCE. | | | | | | 3) STORAGE SHELVING SHALL NOT OBSTRUCT OR INTERFERE | | | WITH FIRE SPRINKLER COVERAGE. | | | | | | 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 5) PLEASE CLARIFY FA AS THAT SYMBOL IS NOT REFLECTED ON | | | PLANS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|