Plan Review Notes
Plan Review Notes For Permit 07120459
Permit Number 07120459
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 08:29:58** DENIED**
  
  
 1) NOTE: PLEASE CLARIFY PROPOSED SCOPE OF WORK AND
 OCCUPANCY. THE PERMIT APPLICATION ORIGINALLY INDICATED
 A *MASSAGE THERAPY* FIT-OUT, THEN THAT WAS CROSSED OUT
 FOR * FOOD RETAIL*. THE PACKAGE CONTAINS A LETTER FROM
 GESULT DESIGN STUDIO WHICH IS ADDRESSED TO PALM BEACH
 COUNTY BLDG DEPT, AND SEEMS TO RESPOND TO COMMENTS.
 THIS LETTER SPECIFIES THE OCCUPANCY AS FRESH FRUIT
 BOUQUET CO.
 PLEASE INDICATE AND CORRELATEALL .
  
 2) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70 (SHOWS 2002)
 2003 NFPA-101
  
 3) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER PER FAC 61G1-16.004
 AND FS 481.219. PLEASE SEE FS 481.219 AS STATED AS A
 *DESIGN FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY
 NOT DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM
 AS SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE
 PROVIDE THE CA NUMBER AS REQUIRED.
 PLEASE CONFIRM.
  
 4) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW
 AND INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR
 CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL
 BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN
 THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL
 SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS
 INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON
 PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF
 MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE
 SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED.
 NEC 408.4, 310.16, 240.4 ETC
 FBC106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON
 PANEL ARE THAT FOR A RESIDENCE. PLEASE SEE 220.12,
 220.14, 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42
 FOR CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%.
 PLEASE SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR
 SIGN CIRCUIT IS 1200VA.
 PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE
 SHOWN PER 220.43
 PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET
 COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT
 CALCULATIONS CAN NOT BE DONE AT THIS TIME.
  
 6) NOTE: PLEASE SEE THE PLANS INDICATE TWO PANELS YET
 THE PLANS ONLY SHOW ONE?
 PLEASE COMPLETE AND CORRELATE.
 408.4, 240.24, ETC
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SEE THE DRYER AS SHOWN ON PANEL
 SCHEDULE IS SHOWN AS 5KW YET THE BRANCH CIRCUIT IS
 SHOWN AS A 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD
 EXCEEDS THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT
 A 2-POLE CIRCUIT?
 PLEASE SEE 240.4, 310.16, ETC
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE PLANS MENTIONS COOLER IS TO BE
 INSTALLED BY OTHERS HOWEVER ELECTRICAL IS NEEDED AT
 THIS TIME UNLESS ALL WILL BE UNDER SEPARATE PERMITS OR
 REVISED AT A LATER DATE?
 240,220, 310, ETC
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED
 SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS
 A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K
 SQ FT.
 PLEASE CLEARLY SHOW NEW WORK AND EXISTING.
 PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME
 AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE
 COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON
 FIXTURES AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE CLARIFY WHAT APPEARS TO BE A FIRE
 ALARM DEVICE ON PLANS. PLANS INDICATE A FA IN A BOX
 HOWEVER AS THE SYMBOL LEGEND DOES NOT SHOW THIS IT IS
 UNCLEAR WHAT THIS IS?
 PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE
 SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR
 ADA.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]