Date Text
2008-03-15 07:17:39 
  
  
 DENIED
  
 THE FOLLOWING COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED:
  
 1)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS AND APPLICABLE
 CERTIFYING INFORMATION/DRAWINGS WHEN AVAILABLE. THEY
 CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED. ******THE CORRESPONDING DRAWINGS THAT ARE THE
 COMPLIANCE METHOD FOR THE FLORIDA STATEWIDE PRODUCT
 APPROVALS WERE NOT SUBMITTED, PLEASE SUBMIT FOR EACH
 PRODUCT. LINKS TO THE DRAWINGS CAN BE FOUND ON THE
 INDIVIDUAL PRODUCT APPROVAL PAGES(SEE ALUMINUM PANEL
 PRODUCT APPROVAL THESE DRAWINGS WERE DOWNLOADED BY PLAN
 REVIEW, NOTE SECOND PAGE OF STATE SHEETS FOR LINK TO
 EVALUATION REPORTS/DRAWINGS, ETC.)********
  
 **********INCORRECT DRAWINGS SUBMITTED FOR ACCORDIAN
 SHUTTERS AND CLEAR PANELS. I HAVE ONCE AGAIN PRINTED
 THE CORRECT PRODUCT APPROVALS AND DRAWINGS AS AN
 EXAMPLE, PLEASE NOTE OLD APPROVAL, COMPARE AND REMOVE
 FROM SUBMITTAL********
  
 2ND REVIEW COMMENTS NOT ADDRESSED:
  
 1)MAKE THE FOLLOWING CORRECTIONS TO THE SHUTTER
 SCHEDULE:
 A)NOTE THE MIN EDGE DISTANCE IN THE DRAWINGS IS 3"
 FOR THE ALUMINUM PANELS AND 3 1/2" FOR THE ACCORDIONS
 AND CLEAR PANELS
 B) PANELS WITH H HEADERS ARE INSTALLED VERTICALLY C)
 SHUTTER SPANS FOR PANELS EQUAL OPENING SIZE + TOTAL
 EDGE DISTANCE+ APPROX. 1". SHUTTER SPANS FOR
 ACCORDIONS EQUAL OPENING SIZE + 1/2 OF TOTAL EDGE
 DISTANCE
 D) THE MAXIMUM SPAN FOR THE CLEAR PANELS AT -80 PSF IS
 5'-6" THIS IS EXCEEDED BOTH HORIZONTALLY (78" + 8") AND
 VERTICALLY (64" + 8") THEREFORE PRODUCT WILL NOT WORK
 IN THIS CONDITION.
 E) PROVIDE ALL ANCHOR SPACINGS
  
 ***********PLEASE NOTE THAT IF THE CORRECT ENGINEERING
 IS PROVIDED THAT THE CLEAR PANEL SPANS WOULD BE FINE,
 HOUSES ARE CONSIDERED ENCLOSED BUILDINGS FOR
 DETERMINING WIND LOADS THIS IN TURN WOULD LOWER THE
 ZONE 4 & 5 PRESSURES AND INCREASE PANEL LENGTH.THESE
 PRESSURE CHANGES SHOULD BE NOTED ON THE SCHEDULE AND IN
 THE DRAWINGS.************
  
 PLEASE NOTE THAT AS CONTRACTORS IT IS YOUR
 RESPONSIBILITY TO PROVIDE ALL CORRECT AND UP TO DATE
 INFORMATION, THIS IN TURN WILL SPEED UP REVIEW AND
 PERMIT ISSUANCE
  
 BLDG PLAN REVIEW