2008-02-19 17:38:29 
  
 DENIED
  
 THE FOLLOWING COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED:
  
 1)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS AND APPLICABLE
 CERTIFYING INFORMATION/DRAWINGS WHEN AVAILABLE. THEY
 CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED. ******THE CORRESPONDING DRAWINGS THAT ARE THE
 COMPLIANCE METHOD FOR THE FLORIDA STATEWIDE PRODUCT
 APPROVALS WERE NOT SUBMITTED, PLEASE SUBMIT FOR EACH
 PRODUCT. LINKS TO THE DRAWINGS CAN BE FOUND ON THE
 INDIVIDUAL PRODUCT APPROVAL PAGES(SEE ALUMINUM PANEL
 PRODUCT APPROVAL THESE DRAWINGS WERE DOWNLOADED BY PLAN
 REVIEW, NOTE SECOND PAGE OF STATE SHEETS FOR LINK TO
 EVALUATION REPORTS/DRAWINGS, ETC.)********
  
 2)PLEASE NOTE THAT ONLY ONE COPY OF THE CLEAR PANEL
 PRODUCT APPROVAL WAS SUBMITTED AND IT HAS BEEN REVISED
 WITH NEW DRAWINGS. NOTE THAT FLORIDA APPROVAL NUMBERS
 AND THEIR REQUIRED DRAWING NUMBERS ARE MARKED ON OLD
 NOA'S. *******REVISED DRAWINGS WERE NOT
 SUBMITTED*******
  
 NEW COMMENTS
  
 1)MAKE THE FOLLOWING CORRECTIONS TO THE SHUTTER
 SCHEDULE:
 A)NOTE THE MIN EDGE DISTANCE IN THE DRAWINGS IS 3"
 FOR THE ALUMINUM PANELS AND 3 1/2" FOR THE ACCORDIONS
 AND CLEAR PANELS
 B) PANELS WITH H HEADERS ARE INSTALLED VERTICALLY C)
 SHUTTER SPANS FOR PANELS EQUAL OPENING SIZE + TOTAL
 EDGE DISTANCE+ APPROX. 1". SHUTTER SPANS FOR
 ACCORDIONS EQUAL OPENING SIZE + 1/2 OF TOTAL EDGE
 DISTANCE
 D) THE MAXIMUM SPAN FOR THE CLEAR PANELS AT -80 PSF IS
 5'-6" THIS IS EXCEEDED BOTH HORIZONTALLY (78" + 8") AND
 VERTICALLY (64" + 8") THEREFORE PRODUCT WILL NOT WORK
 IN THIS CONDITION.
 E) PROVIDE ALL ANCHOR SPACINGS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716